Appendix A — Division B

Explanatory Material

change beginA-10.2.1.1.(3) Deletedchange end

contentHistory

change beginA-10.2.3.2.(2) Thermal Energy Demand Intensity (TEDI)
TEDI does not include receptacle loads and energy use from unusual uses such as spas and computer server rooms.
A-10.2.3.3.(2) Energy Model Calculations for Step 1
Although the total energy use intensity and thermal energy demand intensity are not required for NECB conformance, they must still be calculated in conformance with change beginArticle 10.2.3.4.change end and reported in accordance with Subsection 2.2.9. of Division C.
A-10.2.3.4.(1)(a) and (2) Energy Model Calculations for Steps 2 to 4
Notwithstanding the requirements of Part 8 of the NECB, a reference building and building energy target are not required for compliance with the requirements of Steps 2 to 4 in Article 10.2.3.3. The performance requirements of change beginTable 10.2.3.3.A and Table 10.2.3.3.Bchange end are used to determine compliance.
A-10.2.3.4.(3) Air Leakage Rates
Air Leakage Rate in Energy Model Calculations
The requirement to account for the air leakage rate as tested in all energy model calculations, other than for Step 1 buildings, supersedes the NECB, which permits an assumed air leakage value of 0.25 L/(s⋅m2) to be used for energy model calculations. For buildings that must conform to the requirements of any of Steps 2 to 4, higher than expected air leakage may require the building design to be altered and the energy model calculations to be repeated. Alternatively, the air leakage rate could be retested after making alterations to the air barrier system to attain the desired air leakage rate.
Air Leakage Rate in Energy Model Calculations for Step 1
Although the air leakage rate as tested of the building need not be used for the purposes of conforming with Part 8 of the NECB and Sentence 10.2.3.4.(2), Article 2.2.9.1. of Division C requires that the air leakage rate as tested be used in the calculation of the total energy use intensity and thermal energy demand intensity for reporting purposes on the drawings and specifications. This will typically require Step 1 energy model calculations to be redone after the airtightness test. It is not intended that the results of the airtightness test for buildings that must conform to the requirements of Step 1 influence the compliance of the building with Article 10.2.3.3.
Air Leakage Rate
The air leakage rate of 0.25 L/(s⋅m2), which is a typical infiltration rate at 5 Pa, is for calculation purposes and may not reflect the real rate encountered under actual operating conditions; it is based on assumed typical operating pressure differentials.
A-10.2.3.5.(1) Building Airtightness Testing Requirements
The intent of this testing is to quantify the airtightness level of the air barrier system, not airtightness of the building at in-service operating conditions.change end

contentHistory