Division B
Acceptable Solutions

Part 9 — Housing and Small Buildings

Section 9.22. Fireplaces

9.22.1. General

9.22.1.1. Application
1) Intent StatementExcept when otherwise specifically stated herein, this Section applies to masonry fireplaces constructed on-site.
9.22.1.2. Masonry and Concrete
1) Intent StatementExcept as otherwise stated in this Section, unit masonry shall conform to Section 9.20. and concrete to Section 9.3.
2) Intent StatementMasonry above openings shall be supported by steel lintels conforming to Sentence 9.20.5.2.(2), reinforced concrete or a masonry arch.
9.22.1.3. Footings
1) Intent StatementFootings for masonry and concrete fireplaces shall conform to Section 9.15.
9.22.1.4. Combustion Air
1) Intent StatementWhere a supply of combustion air is provided directly to the fire chamber of a fireplace, including a factory-built fireplace, the installation shall comply with the “Outdoor Air Supply” requirements provided in CAN/CSA-A405-M, “Design and Construction of Masonry Chimneys and Fireplaces.”

9.22.2. Fireplace Liners

9.22.2.1. Brick or Steel Liners
1) Intent StatementExcept where a fireplace is equipped with a steel liner, every fireplace shall have a firebrick liner.
9.22.2.2. Firebrick Liners
1) Intent StatementFirebrick liners shall be not less than
a) 50 mm thick for the sides and back, and
b) 25 mm thick for the floor.
2) Intent StatementFirebrick liners shall be laid with high temperature cement mortar conforming to CAN/CGSB-10.3, “Air Setting Refractory Mortar.”
3) Intent StatementJoints between a firebrick liner and the adjacent backing masonry shall be offset.
9.22.2.3. Steel Liners
1) Intent StatementSteel liners for fireplaces shall conform to CAN/ULC-S639-M, “Steel Liner Assemblies for Solid-Fuel Burning Masonry Fireplaces,” and shall be installed in accordance with the installation instructions in that standard.

9.22.3. Fireplace Walls

9.22.3.1. Thickness of Walls
1) Intent StatementExcept as provided in Sentence (2), the thickness of the back and sides of a fireplace, including the thickness of any firebrick liner, shall be not less than 190 mm where a metal liner or a firebrick liner less than 51 mm thick is used.
2) Intent StatementWhen a steel fireplace liner is used with an air circulating chamber surrounding the firebox, the back and sides of the fireplace shall consist of
a) solid masonry units not less than 90 mm thick, or
b) hollow masonry units not less than 190 mm thick.

9.22.4. Fire Chamber

9.22.4.1. Fire Chamber Dimensions
1) Intent StatementThe distance from the back of the fire chamber to the plane of the fireplace opening shall be not less than 300 mm.

9.22.5. Hearth

9.22.5.1. Hearth Extension
1) Intent StatementExcept as required in Sentence (2), fireplaces shall have a noncombustible hearth extending not less than 400 mm in front of the fireplace opening and not less than 200 mm beyond each side of the fireplace opening.
2) Intent StatementWhere the fire chamber floor is elevated more than 150 mm above the hearth, the dimension of the hearth measured perpendicular to the plane of the fireplace opening shall be increased by not less than
a) 50 mm for an elevation above 150 mm and not more than 300 mm, and
b) an additional 25 mm for every 50 mm in elevation above 300 mm.
9.22.5.2. Support of Hearth
1) Intent StatementExcept as permitted in Sentence (2), the fire chamber floor and hearth shall be supported on a reinforced concrete slab not less than 100 mm thick at its supports and, if cantilevered, not less than 50 mm thick at its unsupported edge.
2) Intent StatementA hearth for a fireplace with an opening raised not less than 200 mm from a combustible floor is permitted to be supported on that floor provided the requirements of Clauses 5.3.6.5. to 5.3.6.7. of CAN/CSA-A405-M, “Design and Construction of Masonry Chimneys and Fireplaces,” are followed.

9.22.6. Damper

9.22.6.1. Required Damper and Size
1) Intent StatementThe throat of every fireplace shall be equipped with a metal damper sufficiently large to cover the full area of the throat opening.

9.22.7. Smoke Chamber

9.22.7.1. Slope of Smoke Chamber
1) Intent StatementThe sides of the smoke chamber connecting a fireplace throat with a flue shall not be sloped at an angle greater than 45° to the vertical.
9.22.7.2. Wall Thickness
1) Intent StatementThe thickness of masonry walls surrounding the smoke chamber shall be not less than 190 mm at the sides, front and back, except that the portions of the back exposed to the outside may be 140 mm thick.

9.22.8. Factory-Built Fireplaces

9.22.8.1. Conformance to Standard
1) Intent StatementFactory-built fireplaces and their installation shall conform to CAN/ULC-S610-M, “Factory-Built Fireplaces.”

9.22.9. Clearance of Combustible Material

9.22.9.1. Clearance to the Fireplace Opening
1) Intent StatementCombustible material shall not be placed on or near the face of a fireplace within 150 mm of the fireplace opening, except that where the combustible material projects more than 38 mm out from the face of the fireplace above the opening, such material shall be not less than 300 mm above the top of the opening.
9.22.9.2. Metal Exposed to the Interior
1) Intent StatementMetal exposed to the interior of a fireplace such as the damper control mechanism shall have not less than a 50 mm clearance from any combustible material on the face of the fireplace where such metal penetrates through the face of the fireplace.
9.22.9.3. Clearance to Combustible Framing
1) Intent StatementNot less than a 100 mm clearance shall be provided between the back and sides of a fireplace and combustible framing, except that a 50 mm clearance is permitted where the fireplace is located in an exterior wall.
2) Intent StatementNot less than a 50 mm clearance shall be provided between the back and sides of the smoke chamber of a fireplace and combustible framing, except that a 25 mm clearance is permitted where the fireplace is located in an exterior wall.
9.22.9.4. Heat-Circulating Duct Outlets
1) Intent StatementThe clearance of combustible material above heat-circulating duct outlets from those outlets shall be not less than
a) 300 mm where the combustible material projects not less than 38 mm from the face, and
b) 150 mm where the projection is less than 38 mm.

9.22.10. Fireplace Inserts and Hearth-Mounted Stoves

9.22.10.1. Appliance Standard
1) Intent StatementFireplace inserts and hearth-mounted stoves vented through the throat of a fireplace shall conform to ULC-S628, “Fireplace Inserts.”
9.22.10.2. Installation
1) Intent StatementThe installation of fireplace inserts and hearth-mounted stoves vented through the throat of a fireplace shall conform to CAN/CSA-B365, “Installation Code for Solid-Fuel-Burning Appliances and Equipment.”