Division B
Acceptable Solutions
Part 9 — Housing and Small Buildings
Section 9.23. Wood-Frame Construction
9.23.1. Application
9.23.1.1. Limitations
(See Appendix A.)
This Section applies to constructions where wall, floor and roof planes are generally comprised of lumber frames of small repetitive structural members, or
engineered components, and where
Where the conditions in Sentence (1) are exceeded for wood constructions, the design of the framing and fastening shall
conform to Subsection 4.3.1.9.23.2. General
9.23.2.1. Strength and Rigidity
All members shall be so framed, anchored, fastened, tied and braced to provide the necessary strength and rigidity.
9.23.2.2. Protection from Decay
Ends of wood joists, beams and other members framing into masonry or concrete shall be treated to prevent decay where the bottom of
the member is at or below ground level, or a 12 mm air
space shall be provided at the end and sides of the member.
Air spaces required in Sentence (1) shall not be blocked by insulation, vapour barriers or airtight materials.
9.23.2.3. Protection from Dampness
Except as permitted in Sentence (2), wood framing members that are not pressure-treated with a wood preservative and that are supported on concrete in contact with the
ground or fill shall be separated from the concrete by not less than 0.05 mm polyethylene film or
Type S roll roofing.
Dampproofing material referred to in Sentence (1) is not required where the wood member is at least 150 mm above the ground. 9.23.2.4. Lumber
Lumber shall conform to Subsection 9.3.2.9.23.3. Fasteners
9.23.3.1. Standards for Nails and Screws
Except as provided in Sentence (2) and unless otherwise indicated, nails specified in this Section shall be
common steel wire nails or common spiral nails conforming to 

| Table 9.23.3.1. Diameter of Nails Forming part of Sentence 9.23.3.1.(2) |
|
| Minimum Length of Nails, mm | Diameter of Nails, mm |
| 57 | 2.87 |
| 63 | 3.25 |
| 76 | 3.66 |
| 82 | 3.66 |
| 101 or greater | 4.88 |

9.23.3.2. Length of Nails
All nails shall be long enough so that not less than half their required length penetrates into the second member.
9.23.3.3. Prevention of Splitting
Splitting of wood members shall be minimized by staggering the nails in the direction of the grain and by keeping nails well in from
the edges. (See Appendix A.)9.23.3.4. Nailing of Framing
Where the bottom wall plate or sole plate of an exterior wall is not nailed to
floor
joists,
rim joists
or blocking in conformance with Table 9.23.3.4., the exterior wall is permitted to be fastened to the floor framing by| Table 9.23.3.4. Nailing for Framing Forming part of Sentence 9.23.3.4.(1) | ||
| Construction Detail | Minimum Length of Nails, mm | Minimum Number or Maximum Spacing of Nails |
|
Floor joist |
82 |
2 |
|
|
|
|
| Wood or metal strapping to underside of floor joists | 57 | 2 |
| Cross bridging to joists | 57 | 2 at each end |
| Double header or trimmer joists | 76 |
300 mm (o.c.) |
| Floor joist to stud (balloon construction) | 76 | 2 |
| Ledger strip to wood beam | 82 | 2 per joist |
|
Joist to joist splice (see also Table 9.23.14.8.) |
76 | 2 at each end |
| Tail joist to adjacent header joist | 82 | 5 |
| (end nailed) around openings | 101 | 3 |
| Each header joist to adjacent trimmer joist | 82 | 5 |
| (end nailed) around openings | 101 | 3 |
| Stud to wall plate (each end) toe nail | 63 | 4 |
| or end nail | 82 | 2 |
| Doubled studs at openings, or studs at walls or wall intersections and corners | 76 |
750 mm (o.c.) |
| Doubled top wall plates | 76 |
600 mm (o.c.) |
|
Bottom wall plate or sole plate
to |
82 |
400 mm (o.c.) |
|
|
|
|
| Interior walls to framing or subflooring | 82 |
600 mm (o.c.) |
|
|
|
|
|
Horizontal member over openings in non-loadbearing walls – each end |
82 | 2 |
| Lintels to studs | 82 | 2 at each end |
| Ceiling joist to plate – toe nail each end | 82 | 2![]() |
|
Roof rafter, roof truss or roof joist to plate – toe nail(2) |
82 | 3 |
| Rafter plate to each ceiling joist | 101 | 2 |
| Rafter to joist (with ridge supported) | 76 | 3 |
| Rafter to joist (with ridge unsupported) | 76 |
see Table 9.23.14.8. |
| Gusset plate to each rafter at peak | 57 | 4 |
| Rafter to ridge board – toe nail – end nail | 82 | 3 |
| Collar tie to rafter – each end | 76 | 3 |
| Collar tie lateral support to each collar tie | 57 | 2 |
| Jack rafter to hip or valley rafter | 82 | 2 |
| Roof strut to rafter | 76 | 3 |
|
Roof strut to loadbearing wall – toe nail |
82 | 2 |
|
38 mm × 140 mm or less plank decking to support |
82 | 2 |
|
Plank decking wider than 38 mm × 140 mm to support |
82 | 3 |
|
38 mm edge laid plank decking to support (toe nail) |
76 | 1 |
|
38 mm edge laid plank to each other |
76 |
450 mm (o.c.) |
| Notes to Table 9.23.3.4.: | |
|
|
|
| (1) | See Sentence 9.23.3.4.(2). |
| (2) | See Sentence 9.23.3.4.(3).![]() |

Where the 1-in-50 hourly wind pressure is equal to or greater than 0.8 kPa, roof rafters, joists or trusses shall be
tied to the wall framing with connectors that will resist a factored
uplift load of 3 kN.
Galvanized-steel straps are deemed to comply with Sentence (3), provided they are
9.23.3.5. Fasteners for Sheathing or Subflooring

Except as provided in Sentences (2) and (3),
fastening of sheathing and subflooring shall conform to Table 9.23.3.5.A. | Table 9.23.3.5.A Fasteners for Subflooring and for Sheathing where HWP is Less Than 0.8 kPa and Sa(0.2) is Not More
Than 0.70![]() Forming part of Sentence 9.23.3.5.(1) | |||||
| Element | Minimum Length of Fasteners, mm | Minimum Number or Maximum Spacing of Fasteners | |||
| Common or Spiral Nails | Ring Thread Nails or Screws | Roofing Nails | Staples | ||
|
Board lumber 184 mm or less wide |
51 | 45 | n/a | 51 | 2 per support |
|
Board lumber more than 184 mm wide |
51 | 45 | n/a | 51 | 3 per support |
|
Fibreboard sheathing up to 13 mm thick |
n/a | n/a | 44 | 28 | 150 mm (o.c.) along edges and 300 mm (o.c.) along intermediate supports |
|
Gypsum sheathing up to 13 mm thick |
n/a | n/a | 44 | n/a | |
| Plywood, OSB or waferboard up to 10 mm thick | 51 | 45 | n/a | 38 | |
Plywood,
OSB or waferboard over 10 mm and up to 20 mm thick | 51 | 45 | n/a | 51 | |
Plywood, OSB or waferboard over 20 mm and up to 25 mm thick | 57 | 51 | n/a | n/a | |

Fastening of roof sheathing and sheathing in required braced wall panels shall conform to Table 9.23.3.5.B, where| Table 9.23.3.5.B Fasteners for Sheathing where HWP is Equal to or Greater Than 0.8 kPa and Less Than 1.2 kPa or where Sa(0.2) is Greater Than 0.70 and Not More Than 1.2 Forming part of Sentence 9.23.3.5.(2) | ||||
| Element | Minimum Length of Fasteners, mm | Minimum Number or Maximum Spacing of Fasteners | ||
| Common, Spiral or Ring Thread Nails | Screws | 14-Gage Staples | ||
|
Board lumber 184 mm or less wide |
63 | 51 | 63 | 2 per support |
|
Board lumber more than 184 mm wide |
63 | 51 | 63 | 3 per support |
|
Plywood, OSB or waferboard up to 20 mm thick(1) |
63 | 51 | 63 | 150 mm (o.c.) along edges and 300 mm (o.c.) along intermediate supports; and for roof sheathing where HWP is equal to or greater than 0.8 kPa and less than 1.2 kPa, 50 mm (o.c.) within 1 m of the edges of the roof |
|
Plywood, OSB or waferboard over 20 mm and up to 25 mm thick |
63 | 57 | n/a | |
| Notes to Table 9.23.3.5.B: | |
|
|
|
| (1) | See Appendix A. |
Fastening of sheathing shall conform to Part 4,
Staples shall not be less than 1.6 mm in diameter or thickness, with not less than a 9.5 mm crown driven
with the crown parallel to framing.
Roofing nails for the attachment of fibreboard or gypsum sheathing shall not be less than 3.2 mm in diameter with a minimum
head diameter of 11.1 mm.
9.23.4. Maximum Spans
9.23.4.1. Application
Spans provided in this Subsection for joists, beams and lintels supporting floors shall apply only where
Spans for joists, beams and lintels supporting floors shall be determined according to Subsection 4.1.3. where the
supported floors9.23.4.2. Spans for Joists, Rafters and Beams
(See Appendix A.)
Except as required in Sentence (2) and Article 9.23.14.10., spans for wood joists and rafters shall conform to the spans shown in Tables A-1 to A-7 for the
uniform live loads shown in the Tables. (See Article 9.4.2.2.)
Spans for floor joists that are not selected from Tables A-1 and A-2 and that are required to be designed for the same
loading conditions, shall not exceed the design requirements for uniform
loading and vibration criteria. (See Appendix A.)
Spans for built-up wood and glued-laminated timber floor beams shall conform to the spans in Tables A-8 to A-11 (See Article 9.4.2.2.)
Spans for roof ridge beams shall conform to the spans in Table A-12 for the uniform snow load shown. (See Articles 9.4.2.2. and 9.23.14.8.) 9.23.4.3. Steel Beams
The spans for steel floor beams with laterally supported top flanges shall conform to Table 9.23.4.3. (See Appendix A.)| Table 9.23.4.3. Maximum Spans for Steel Beams Supporting Floors in Dwelling Units(1) Forming part of Sentence 9.23.4.3.(1) | |||||||
| Section | Supported Joist Length, m (half the sum of joist spans on both sides of the beam) | ||||||
| 2.4 | 3.0 | 3.6 | 4.2 | 4.8 | 5.4 | 6.0 | |
|
One Storey Supported |
|||||||
| W150 x 22 | 5.5 | 5.2 | 4.9 | 4.8 | 4.6 | 4.5 | 4.3 |
| W200 x 21 | 6.5 | 6.2 | 5.9 | 5.7 | 5.4 | 5.1 | 4.9 |
| W200 x 27 | 7.3 | 6.9 | 6.6 | 6.3 | 6.1 | 5.9 | 5.8 |
| W200 x 31 | 7.8 | 7.4 | 7.1 | 6.8 | 6.6 | 6.4 | 6.2 |
| W250 x 24 | 8.1 | 7.6 | 7.3 | 7.0 | 6.6 | 6.2 | 5.9 |
| W250 x 33 | 9.2 | 8.7 | 8.3 | 8.0 | 7.7 | 7.5 | 7.3 |
| W250 x 39 | 10.0 | 9.4 | 9.0 | 8.6 | 8.4 | 8.1 | 7.9 |
| W310 x 31 | 10.4 | 9.8 | 9.4 | 8.9 | 8.4 | 8.0 | 7.6 |
| W310 x 39 | 11.4 | 10.7 | 10.2 | 9.8 | 9.5 | 9.2 | 9.0 |
|
Two Storeys Supported |
|||||||
| W150 x 22 | 4.9 | 4.4 | 4.1 | 3.8 | 3.5 | 3.4 | 3.2 |
| W200 x 21 | 5.6 | 5.1 | 4.6 | 4.3 | 4.1 | 3.8 | 3.7 |
| W200 x 27 | 6.4 | 6.1 | 5.6 | 5.3 | 4.9 | 4.7 | 4.4 |
| W200 x 31 | 6.9 | 6.5 | 6.2 | 5.8 | 5.4 | 5.1 | 4.9 |
| W250 x 24 | 6.8 | 6.1 | 5.6 | 5.2 | 4.9 | 4.6 | 4.4 |
| W250 x 33 | 8.2 | 7.7 | 7.0 | 6.5 | 6.1 | 5.8 | 5.5 |
| W250 x 39 | 8.8 | 8.3 | 7.8 | 7.2 | 6.8 | 6.4 | 6.1 |
| W310 x 31 | 8.7 | 7.8 | 7.2 | 6.7 | 6.2 | 5.9 | 5.6 |
| W310 x 39 | 10.0 | 9.3 | 8.5 | 7.9 | 7.4 | 7.0 | 6.7 |
| Notes to Table 9.23.4.3.: | |
|
|
|
| (1) | See Appendix A. |
Beams described in Sentence (1) shall at least meet the requirements for Grade 350 W steel
contained in CAN/CSA-G40.21, “General Requirements for Rolled or Welded Structural Quality Steel.”9.23.4.4. Concrete Topping
(See Appendix A.)
Except as permitted in Sentence (2), where a floor is required to support a concrete topping, the joist spans shown in Table A-1 or the spacing of the members
shall be reduced to allow for the loads due to the topping.
Where a floor is required to support a concrete topping, joist spans are permitted to be selected from Table A-2 provided the concrete
Where a floor is required to support a concrete topping not more than 51 mm thick, the allowable beam spans shown
in Tables A-8 to A-11 shall be multiplied by 0.8 or the supported length
of the floor joists shall be reduced to allow for the loads due to
the topping.
9.23.4.5. Heavy Roofing Materials
Where a roof is required to support an additional uniform dead load from roofing materials such as concrete roofing tile, or materials other than as specified in Section 9.27., such as clay roofing tiles, the additional
load shall be allowed for by reducing9.23.5. Notching and Drilling
9.23.5.1. Holes Drilled in Framing Members
Holes drilled in roof, floor or ceiling framing members shall be not larger than one-quarter the depth of the member and shall be
located not less than 50 mm from the edges, unless the
depth of the member is increased by the size of the hole.
9.23.5.2. Notching of Framing Members
Floor, roof and ceiling framing members are permitted to be notched provided the notch is located on the top of the member within
half the joist depth from the edge of bearing and is not deeper than
one-third the joist depth, unless the depth of the member is increased
by the size of the notch.
9.23.5.3. Wall Studs
Wall studs shall not be notched, drilled or otherwise damaged so that the undamaged portion of the stud is less than two-thirds
the depth of the stud if the stud is loadbearing or 40 mm if the stud is non-loadbearing, unless the weakened studs are suitably reinforced. 9.23.5.4. Top Plates
Top plates in walls shall not be notched, drilled or otherwise weakened to reduce the undamaged width to less than 50 mm unless the weakened plates are suitably reinforced.
9.23.5.5. Roof Trusses
Roof truss members shall not be notched, drilled or otherwise weakened unless such notching or drilling is allowed for in the design
of the truss.
9.23.6. Anchorage
9.23.6.1. Anchorage of Building Frames
Except as required by Sentence 9.23.6.3.(1), building frames shall be anchored to the foundation unless a structural analysis of wind and earthquake pressures shows anchorage is not required.
Except as provided in
Sentences (3) and (5)
, anchorage shall be provided by
For buildings with 2 or more floors supported by frame walls that are in areas where the seismic spectral response acceleration,
Sa(0.2), is equal to or greater than 0.70 but not greater than 1.2
or the 1-in-50 hourly wind pressure is equal to or greater than 0.80
kPa but not greater than 1.20 kPa, anchorage shall be
provided by fastening the sill plate to the foundation with not less than two anchor bolts per braced wall panel, where all anchor bolts used are

Anchor bolts referred to in Sentences (2)
and (3)
shall be
Where the seismic spectral response acceleration, Sa(0.2), is greater than 1.2 or the 1-in-50 hourly wind pressure is equal to or greater than 1.2 kPa, anchorage shall be designed according
to Part 4.
9.23.6.2. Anchorage of Columns and Posts
Except as provided in Sentences (2) and (3), exterior columns and posts shall be anchored to resist uplift and lateral movement.
Except as provided in Sentence (3), where columns or posts support balconies, decks, verandas or other exterior platforms, and the distance from finished ground to the underside
of the joists is not more than 600 mm,
Anchorage is not required for platforms described in Sentence (2) that9.23.6.3. Anchorage of Smaller Buildings
Buildings not more than 4.3 m wide and not more than 1 storey in building height that are not anchored in accordance with Sentence 9.23.6.1.(1) shall be anchored in conformance with the requirements of CSA Z240.10.1, “Site Preparation, Foundation, and Anchorage of Manufactured Homes.”9.23.7. Sill Plates
9.23.7.1. Size of Sill Plates
Where sill plates provide bearing for the floor system, they shall be not less than 38 mm by 89 mm material.
9.23.7.2. Levelling and Sealing of Sill Plates
Sill plates shall be
The joint between the sill plate for exterior walls and the foundation shall be sealed in accordance with Subsection 9.25.3.9.23.8. Beams to Support Floors
9.23.8.1. Bearing for Beams
Beams shall have even and level bearing and the bearing at end supports shall be not less than 89 mm long, except as stated in the notes to Tables A-8 to A-119.23.8.2. Priming of Steel Beams
9.23.8.3. Built-up Wood Beams
(See Appendix A.)
Where a beam is made up of individual pieces of lumber that are nailed together, the individual members shall be 38 mm or greater in thickness and installed on edge.
Except as permitted in Sentence (3), where individual members of a built-up beam are butted together to form a joint, the joint shall occur over a support.
Where a beam is continuous over more than one span, individual members are permitted to be butted together to form a joint at or
within 150 mm of the end quarter points of the clear
spans, provided the quarter points are not those closest to the ends
of the beam.
Joints in individual members of a beam that are located at or near the end quarter points shall not occur in adjacent members at
the same quarter point and shall not reduce the effective beam width
by more than half.
Not more than one butt joint shall occur in any individual member of a built-up beam within any one span.
Except as provided in Sentence (8), where 38 mm members are laid on edge to form a built-up beam, individual members shall be nailed together with a double row
of nails not less than 89 mm in length, spaced not more
than 450 mm apart in each row with the end nails located 100 mm to 150 mm from the end of each piece.
Where 38 mm members in built-up wood beams are not nailed together as provided in Sentence (7), they shall be bolted together with not less than 12.7 mm diam bolts equipped with washers and spaced not more than 1.2 m o.c., with the end bolts located not more than 600 mm from the ends of the members. 9.23.9. Floor Joists
9.23.9.1. End Bearing for Joists
Except when supported on ribbon boards, floor joists shall have not less than 38 mm length of end bearing.
Ribbon boards referred to in Sentence (1) shall be not less than 19 mm by 89 mm lumber let into the studs. 9.23.9.2. Joists Supported by Beams
When framed into the side of a wood beam, joists referred to in Sentence (1) shall be supported on
When framed into the side of a steel beam, joists referred to in Sentence (1) shall be supported on the bottom flange of the beam or on not less than 38 mm by 38 mm lumber bolted to the web with not less than 6.3 mm diam bolts spaced not more than 600 mm apart.
Joists referred to in Sentence (3) shall be spliced above the beam with not less than 38 mm by 38 mm lumber at least 600 mm long to support the flooring.
Not less than a 12 mm space shall be provided between the splice required in Sentence (4) and the beam to allow for shrinkage of the wood joists.
9.23.9.3. Restraint of Joist Bottoms
Except as provided in Sentence 9.23.9.4.(1), bottoms of floor joists shall be restrained from twisting at each end by toe-nailing
to the supports, end-nailing to the header joists or by providing
continuous strapping, blocking between the joists or cross-bridging
near the supports.
9.23.9.4. Strapping, Bridging, Furring and Ceilings in Tables A-1 and A-2
(See A-9.23.4.2.(2) in Appendix A.)
Except as permitted by Sentence (5), where strapping is specified in Table A-1, it
shall be
Where bridging is specified in Table A-1,
it shall consist of not less than 19 mm by 64 mm or 38 mm by 38 mm cross bridging located
not more than 2 100 mm from each support or other rows
of bridging.
Where bridging and strapping are specified in Table A-1,
Bridging specified in Table A-2 shall consist
of
Strapping described in Sentence (1) and Clause (3)(b) is not required
where
Where a ceiling attached to wood furring is specified in Table A-2,9.23.9.5. Header Joists
9.23.9.6. Trimmer Joists
Trimmer joists around floor openings shall be doubled when the length of the header joist exceeds 800 mm.
When the header joist exceeds 2 m in length the size of the trimmer joists shall be determined by calculations.
9.23.9.7. Support of Tail and Header Joists
When tail joists and header joists are supported by the floor framing, they shall be supported by suitable joist hangers or nailing
in accordance with Table 9.23.3.4.9.23.9.8. Support of Walls
Non-loadbearing walls parallel to the floor joists shall be supported by joists beneath the wall or
on blocking between the joists.
Blocking referred to in Sentence (1) for the support of non-loadbearing walls shall be
except as required for the fastening of walls constructed with required braced wall panels,
spaced not more than 1.2 m apart. 
Except as provided in Sentence (6),
non-loadbearing interior walls at right angles to the floor joists are not restricted as to location.
Loadbearing interior walls parallel to floor joists shall be supported by beams or walls of sufficient
strength to safely transfer the specified live loads to the vertical supports.

Unless the joist size is designed to support such loads,
loadbearing interior walls at right angles to floor joists shall be located
Loadbearing and non-loadbearing walls constructed with required braced wall panels shall be continuously supported by floor joists, blocking or rim joists to allow for the required fastening (see Table 9.23.3.4.).
9.23.9.9. Cantilevered Floor Joists
Floor joists supporting roof loads shall not be cantilevered more than 400 mm beyond their supports where 38 mm by 184 mm joists are used and not more than 600 mm beyond their supports where 38 mm by 235 mm or larger joists are used.
The cantilevered portions referred to in Sentence (1) shall not support floor loads from other storeys unless calculations are provided to show that the design resistances of the cantilevered joists are not exceeded.
Where cantilevered floor joists described in Sentences (1) and (2) are at right angles to the main floor joists, the tail joists in the cantilevered portion
shall extend inward away from the cantilever support a distance equal
to not less than 6 times the length of the cantilever, and shall be
end nailed to an interior doubled header joist in conformance with Table 9.23.3.4.9.23.10. Wall Studs
9.23.10.1. Stud Size and Spacing
The size and spacing of studs shall conform to Table 9.23.10.1.| Table 9.23.10.1. Size and Spacing of Studs Forming part of Sentence 9.23.10.1.(1) | ||||
| Type of Wall |
Supported Loads (including dead loads) |
Minimum Stud Size, mm | Maximum Stud Spacing, mm | Maximum Unsupported Height, m |
| Interior | No load | 38 x 38 | 400 | 2.4 |
|
38 x 89 flat(1) |
400 | 3.6 | ||
| Attic not accessible by a stairway | 38 x 64 | 600 | 3.0 | |
|
38 x 64 flat(1) |
400 | 2.4 | ||
| 38 x 89 | 600 | 3.6 | ||
|
38 x 89 flat(1) |
400 | 2.4 | ||
|
Attic
accessible by a stairway plus one floor |
38 x 89 | 400 | 3.6 | |
|
Roof load |
38 x 64 | 400 | 2.4 | |
| 38 x 89 | 600 | 3.6 | ||
|
Attic
accessible by a stairway plus 2 floors |
38 x 89 | 300 | 3.6 | |
| 64 x 89 | 400 | 3.6 | ||
| 38 x 140 | 400 | 4.2 | ||
|
Attic
accessible by a stairway plus 3 floors |
38 x 140 | 300 | 4.2 | |
| Exterior | Roof with or without attic storage | 38 x 64 | 400 | 2.4 |
| 38 x 89 | 600 | 3.0 | ||
| Roof with or without attic storage plus one floor | 38 x 89 | 400 | 3.0 | |
| 38 x 140 | 600 | 3.0 | ||
| Roof with or without attic storage plus 2 floors | 38 x 89 | 300 | 3.0 | |
| 64 x 89 | 400 | 3.0 | ||
| 38 x 140 | 400 | 3.6 | ||
| Roof with or without attic storage plus 3 floors | 38 x 140 | 300 | 1.8 | |
| Notes to Table 9.23.10.1.: | |
|
|
|
| (1) | See Article 9.23.10.3. |
9.23.10.2. Bracing and Lateral Support
Where loadbearing interior walls are not finished in accordance with
Section 9.29.
, blocking or strapping shall be fastened to the studs at mid-height to prevent sideways buckling.
9.23.10.3. Orientation of Studs
Except as permitted in Sentences (2) and (3), all studs shall be placed at right angles to the wall face.
Studs on the flat are permitted to be used in gable ends of roofs that contain only unfinished space or in non-loadbearing interior walls within the limits described in Article 9.23.10.1.
Wall studs that support only a load from an attic not accessible by a stairway are permitted to be placed on the flat within the limits
permitted in Article 9.23.10.1. provided9.23.10.4. Continuity of Studs
Wall studs shall be continuous for the full storey height except at openings and shall not be spliced except by fingerjoining with a structural adhesive. (See Appendix A.) 9.23.10.5. Support for Cladding, Sheathing and Finishing Materials
Corners and intersections shall be designed to provide adequate support for the vertical edges of interior finishes, sheathing and
cladding materials, and in no instance shall exterior corners be framed
with less than the equivalent of 2 studs.
Where the vertical edges of interior finishes at wall intersections are supported at vertical intervals by blocking or furring, the vertical
distance between such supports shall not exceed the maximum distance
between supports specified in Section 9.29.9.23.10.6. Studs at Sides of Openings
Where the lintel spanning the opening is more than 3 m long, studs shall be tripled on each side of the opening so that
Except as provided in Sentence (3), where the lintel spanning the opening is not more than 3 m long, studs shall be doubled on each side of the opening
so that
Single studs are permitted to be used on either side of openings9.23.11. Wall Plates
9.23.11.1. Size of Wall Plates
Except as provided in Sentence (2), wall plates shall be
In non-loadbearing walls and in loadbearing walls where the studs are located directly over framing members, the bottom wall plate is permitted
to be 19 mm thick.
9.23.11.2. Bottom Wall Plates
The bottom plate in exterior walls shall not project more than one-third the plate width over the support.
9.23.11.3. Top Plates
Except as permitted in Sentences (2) to (4), at least 2 top plates shall be provided in loadbearing walls.
A single top plate is permitted to be used in a section of a loadbearing wall containing a lintel provided the top plate forms a tie across the lintel.
A single top plate is permitted to be used in loadbearing walls where the concentrated loads from ceilings, floors and roofs are not more than 50 mm to one side
of the supporting studs and in all non-loadbearing walls.
The top plates need not be provided in a section of loadbearing wall containing a lintel provided the lintel is tied to the adjacent wall section with not less than9.23.11.4. Joints in Top Plates
Joints in the top plates of loadbearing walls shall be staggered not less than one stud spacing.
The top plates in loadbearing walls shall be lapped or otherwise tied at corners and intersecting walls
in accordance with Sentence (4).
Joints in single top plates used with loadbearing walls shall be tied in accordance with Sentence (4).
Ties referred to in Sentences (2) and (3) shall be the equivalent of not less than 75 mm by 150 mm by 0.91 mm thick galvanized steel nailed to each wall with at least three 63 mm nails.
9.23.12. Framing over Openings
9.23.12.1. Openings in Non-Loadbearing Walls
Except as provided in Sentence (2), openings in non-loadbearing walls shall be framed with not less than 38 mm material the
same width as the studs, securely nailed to adjacent studs.
Openings for doors in non-loadbearing walls required to be fire separations with a fire-resistance rating shall be framed with the equivalent of at least two 38 mm thick
members that are the same width as the wall plates.
9.23.12.2. Openings in Loadbearing Walls
Openings in loadbearing walls greater than the required stud spacing shall be framed with lintels designed
to carry the superimposed loads to adjacent studs. (See A-9.23.10.6.(3) in Appendix A.)
Except as provided in Sentence 9.23.12.3.(2), where 2 or more members are used in lintels, they shall be fastened together
with not less than 82 mm nails in a double row, with
nails not more than 450 mm apart in each row.
9.23.12.3. Lintel Spans and Sizes
Spans and sizes of wood lintels shall conform to the spans shown in Tables A-12 to A-16
In loadbearing exterior and interior walls of 38 mm by 64 mm framing members,
lintels shall consist of
Lintels referred to in Sentence (2)9.23.13.
Bracing to Resist Lateral Loads Due to Wind and Earthquake
(See Appendix A.)9.23.13.1. Requirements for Low to Moderate Wind and Seismic Forces
(See Appendix A.)
This Article applies in locations where the seismic spectral response acceleration, Sa(0.2), is not more than 0.70 and
the 1-in-50 hourly wind pressure is less than 0.80 kPa.
Subsection 9.23.17.
and fastened in accordance with Table 9.23.3.5.A, or
9.23.13.2. Requirements for High Wind and Seismic Forces
Except as provided in Article 9.23.13.1., this Article applies in locations where
Bracing to resist lateral loads shall be designed and constructed in accordance with9.23.13.3. Requirements for Extreme Wind and Seismic Forces
Except as provided in Articles 9.23.13.1. and 9.23.13.2., this Article applies in locations where
Bracing to resist lateral loads shall be designed and constructed in accordance with9.23.13.4. Braced Wall Bands
(See Appendix A.)
Braced wall bands shall
For split-level buildings, a braced wall band shall be located where there is a change in floor level greater than the depth of one floor joist.
9.23.13.5. Braced Wall Panels in Braced Wall Bands
Except as provided in Sentences (2) to (5) and Article 9.23.13.7., braced wall panels shall| Table 9.23.13.5. Spacing and Dimensions of Braced Wall Bands and Braced Wall Panels Forming part of Sentences 9.23.13.4.(1) and 9.23.13.5.(1) | ||
| Description | Spacing and Dimensions of Braced Wall Bands and Braced Wall Panels(1)(2)(3) | |
| Seismic and Wind Loads | ||
| 0.70 < Sa(0.2) < 1.0 | 1.0 ≤ Sa(0.2) ≤ 1.2 or 0.80 ≤ HWP < 1.2 kPa |
|
| Maximum distance between centre lines of adjacent braced wall bands measured from the furthest points between centres of the bands | 10.6 m | 7.6 m |
| Maximum distance between required braced wall panels measured from the edges of the panels | 6.4 m | 6.4 m |
| Maximum distance from the end of a braced wall band to the edge of the closest required braced wall panel | 2.4 m | 2.4 m |
| Minimum length of individual braced wall panels: | ||
| • panel located at the end of a braced wall band where the braced wall panel connects to an intersecting braced wall panel | 600 mm | |
| • panel not located at the end of a braced wall band or braced wall panel located at the end of a braced wall band where the braced wall panel does not connect to an intersecting braced wall panel | 750 mm | |
| Minimum total length of all braced wall panels in a braced wall band | ||
| • supporting 3 floors, light construction | 75% of length of braced wall band | |
| • supporting 2 floors, heavy construction(4) | 75% of length of braced wall band | |
| • supporting 2 floors, light construction | 40% of length of braced wall band | |
| • supporting 1 floor, heavy construction(4) | 40% of length of braced wall band | |
| • supporting 1 floor, light construction | 25% of length of braced wall band | |
| • not supporting a floor | 25% of length of braced wall band | |
| Notes to Table 9.23.13.5.: | |
|
|
|
| (1) | See Appendix A. |
| (2) | All constructions include support of a roof load in addition to the indicated number of floors. |
| (3) | See Article 9.23.13.7. for alternative methods of compliance. |
| (4) | See Sentence 9.23.13.3.(1) for overall limit on application to heavy construction. |
In basements or crawl spaces where the perimeter foundation walls extend from the footings to the underside of the supported floor, braced wall bands constructed with braced wall panels shall be spaced not more than
Portions of the perimeter of a single open or enclosed space need not comply with Sentence (1), where
Walls in detached garages and in accessory buildings serving a single dwelling unit, and the front wall of attached garages serving a single dwelling unit need not comply with Sentence (1) where these walls do not support a floor.
Braced wall panels in the braced wall band at the front of an attached garage serving a single dwelling unit need not comply with Sentence (1), provided9.23.13.6. Materials in Braced Wall Panels

| Table 9.23.13.6. Minimum Thicknesses of Cladding, Sheathing or Interior Finish for Braced Wall Panels Forming part of Sentence 9.23.13.6.(1) | ||
| Panel-Type Cladding, Sheathing or Interior Finish | Minimum Thickness | |
| With supports 400 mm o.c. | With supports 600 mm o.c. | |
| Gypsum board interior finish(1) | 12.7 mm | 15.9 mm |
| Sheathing complying with CAN/CSA-O325 | W16 | W24 |
| OSB O-1 and O-2 grades and waferboard R-1 grade | 9.5 mm | 12.5 mm |
| Plywood | 9.5 mm | 12.5 mm |
| Diagonal lumber | 17 mm | 17 mm |
| Notes to Table 9.23.13.6.: | |
|
|
|
| (1) | See Sentences (5) and (6). |
Except as provided in Sentence (3), required interior braced wall panels shall be
Required interior braced wall panels of wood-based material may be sheathed on one side only, provided
For stacked braced wall bands, where the construction of any one braced wall panel is required to be of a wood-based material, a wood-based material shall be installed in all the
required braced wall panels in that braced wall band.
Gypsum board interior finish shall not be considered as an acceptable sheathing material to provide the required bracing in exterior walls.
(See A-9.23.13.6.(5) and (6) in Appendix A.)
At braced wall band spacing intervals of not more than 15 m, braced wall panels shall be constructed with OSB, plywood or diagonal
lumber. (See A-9.23.13.6.(5) and (6) in Appendix A.)
9.23.13.7. Additional System Considerations
Except as provided in Sentences (2) and (3), one exterior wall of the uppermost storey in each orthogonal direction may be set back from the exterior wall of the storey below, provided the adjacent interior braced wall band of the storey below the setback
Where the exterior wall of the uppermost storey is set back from the exterior wall of the storey below, the roof and floor space supporting the setback wall shall be sheathed with a wood-based material between the exterior wall of
the storey below the setback and the adjacent interior braced wall bands of the storey below the setback.
Where the exterior wall of the uppermost storey is set back from the exterior wall of the storey below, the exterior walls perpendicular to the setback wall shall
The maximum distance between adjacent required braced wall panels in a braced wall band, measured from the edge of the panels, may be increased to 7.3 m provided that, throughout the height
of the building, the length of any braced wall panel within the braced wall band is not less than 1.2 m.
The maximum spacing between the centre lines of required braced wall bands given in Table 9.23.13.5. may be increased from 7.6 m to no more than 10.6 m, provided that the interior braced wall band whose spacing is being increased is replaced with an interior braced wall band that
For each orthogonal direction of the building, the length of required braced wall panels of one exterior wall given in Table 9.23.13.5. may be reduced from 40% to no less than 25% of the length of the braced wall band, provided an additional parallel and adjacent interior braced wall band is constructed that

9.23.14. Roof and Ceiling Framing
9.23.14.1. Continuity of Rafters and Joists
Roof rafters and joists and ceiling joists shall be continuous or shall be spliced over vertical supports that extend to suitable
bearing.
9.23.14.2. Framing around Openings
Roof and ceiling framing members shall be doubled on each side of openings greater than 2 rafter or joist spacings wide.
9.23.14.3. End Bearing Length
9.23.14.4. Location and Attachment of Rafters
Rafters shall be located directly opposite each other and tied together at the peak, or may be offset by their own thickness if nailed
to a ridge board not less than 17.5 mm thick.
Except as permitted in Sentence (3), framing members shall be connected by gusset plates or nailing at the peak in conformance with Table 9.23.3.4.
Where the roof framing on opposite sides of the peak is assembled separately, such as in the case of factory-built houses, the roof
framing on opposite sides is permitted to be fastened together with
galvanized-steel strips not less than 200 mm by 75 mm by 0.41 mm thick spaced not more than 1.2 m apart and nailed at each end to the framing by at least
two 63 mm nails.
9.23.14.5. Shaping of Rafters
Rafters shall be shaped at supports to provide even bearing surfaces and supported directly above the exterior walls.
9.23.14.6. Hip and Valley Rafters
Hip and valley rafters shall be not less than 50 mm greater in depth than the common rafters and not less than 38 mm thick, actual dimension. 9.23.14.7. Intermediate Support for Rafters and Joists
Ceiling joists and collar ties of not less than 38 mm by 89 mm lumber are permitted to be assumed to provide intermediate support to reduce the span for rafters and joists where
the roof slope is 1 in 3 or greater.
Collar ties referred to in Sentence (1) more than 2.4 m long shall be laterally supported near their centres by not less than 19 mm by 89
mm continuous members at right angles to the collar ties.
Dwarf walls and struts are permitted to be used to provide intermediate support to reduce the span for rafters and joists.
When struts are used to provide intermediate support they shall be not less than 38 mm by 89 mm material
extending from each rafter to a loadbearing wall at an angle of not less than 45° to the horizontal.
When dwarf walls are used for rafter support, they shall be framed in the same manner as loadbearing walls and securely fastened top and bottom to the roof and ceiling framing to prevent over-all movement.
Solid blocking shall be installed between floor joists beneath dwarf walls referred to in Sentence (5) that enclose finished rooms. 9.23.14.8. Ridge Support
Except as provided in Sentence (4), roof rafters and joists shall be supported at the ridge of the roof by
Except as provided in Sentence (3), the ridge beam referred to in Sentence (1) shall conform to the sizes and spans shown in Table A-12, provided
The ridge beam referred to in Sentence (1) need not comply with Sentence (2) where
When the roof slope is 1 in 3 or more, ridge support need not be provided when the lower ends of the rafters are adequately tied
to prevent outward movement.
Ties required in Sentence (4) are permitted to consist of tie rods or ceiling joists forming a continuous
tie for opposing rafters and nailed in accordance with Table 9.23.14.8.| Table 9.23.14.8. Rafter-to-Joist Nailing (Unsupported Ridge) Forming part of Sentences 9.23.14.8.(5) and (6) | |||||||||||||
| Roof Slope | Rafter Spacing, mm |
Minimum Number of Nails not less than 76 mm Long |
|||||||||||
| Rafter Tied to every Joist |
Rafter Tied to Joist every 1.2 m |
||||||||||||
|
Building Width up to 8 m |
Building Width up to 9.8 m |
Building Width up to 8 m |
Building Width up to 9.8 m |
||||||||||
| Roof Snow Load, kPa | Roof Snow Load, kPa | Roof Snow Load, kPa | Roof Snow Load, kPa | ||||||||||
| 1.0 or less | 1.5 | 2.0 or more | 1.0 or less | 1.5 | 2.0 or more | 1.0 or less | 1.5 | 2.0 or more | 1.0 or less | 1.5 | 2.0 or more | ||
| 1 in 3 | 400 | 4 | 5 | 6 | 5 | 7 | 8 | 11 | — | — | — | — | — |
| 600 | 6 | 8 | 9 | 8 | — | — | 11 | — | — | — | — | — | |
| 1 in 2.4 | 400 | 4 | 4 | 5 | 5 | 6 | 7 | 7 | 10 | — | 9 | — | — |
| 600 | 5 | 7 | 8 | 7 | 9 | 11 | 7 | 10 | — | — | — | — | |
| 1 in 2 | 400 | 4 | 4 | 4 | 4 | 4 | 5 | 6 | 8 | 9 | 8 | — | — |
| 600 | 4 | 5 | 6 | 5 | 7 | 8 | 6 | 8 | 9 | 8 | — | — | |
| 1 in 1.71 | 400 | 4 | 4 | 4 | 4 | 4 | 4 | 5 | 7 | 8 | 7 | 9 | 11 |
| 600 | 4 | 4 | 5 | 5 | 6 | 7 | 5 | 7 | 8 | 7 | 9 | 11 | |
| 1 in 1.33 | 400 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 5 | 6 | 5 | 6 | 7 |
| 600 | 4 | 4 | 4 | 4 | 4 | 5 | 4 | 5 | 6 | 5 | 6 | 7 | |
| 1 in 1 | 400 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 5 |
| 600 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 5 | |
Ceiling joists referred to in Sentence (5) shall be fastened together with at least one more nail per joist splice than required for the rafter to joist connection
shown in Table 9.23.14.8.
Members referred to in Sentence (6) are permitted to be fastened together either directly or through a gusset plate.
9.23.14.9. Restraint of Joist Bottoms
Roof joists supporting a finished ceiling, other than plywood, OSB or waferboard, shall be restrained from twisting along the bottom
edges by means of furring, blocking, cross bridging or strapping conforming
to Article 9.23.9.3.9.23.14.10. Ceiling Joists Supporting Roof Load
Except as permitted in Sentence (2), ceiling joists supporting part of the roof load from the rafters shall be not less than 25 mm greater in depth than required
for ceiling joists not supporting part of the roof load.
When the roof slope is 1 in 4 or less, the ceiling joist sizes referred to in Sentence (1) shall be determined from the span tables for roof joists.
9.23.14.11. Roof Trusses
Roof trusses which are not designed in accordance with Part 4 shall| Table 9.23.14.11. Maximum Roof Truss Deflections Forming part of Sentence 9.23.14.11.(1) | ||
| Truss Span | Type of Ceiling | Maximum Deflection |
|
4.3 m or less |
Plaster or gypsum board | 1/360 of the span |
| Other than plaster or gypsum board | 1/180 of the span | |
|
Over 4.3 m |
Plaster or gypsum board | 1/360 of the span |
| Other than plaster or gypsum board | 1/240 of the span | |
The joint connections used in trusses described in Sentence (1) shall be designed in conformance with the requirements in Subsection 4.3.1. (See Appendix A.)
Where the length of compression web members in roof trusses described in Sentence (1) exceeds 1.83 m, such web members shall be provided with continuous bracing to prevent buckling.
Bracing required in Sentence (3) shall consist of not less than 19 mm by 89 mm lumber
nailed at right angles to the web members near their centres with
at least two 63 mm nails for each member.
Where the ability of a truss design to satisfy the requirements of Sentence (1) is demonstrated by testing, it shall consist of a full scale load test carried out in conformance
with CSA S307-M, “Load Test Procedure for Wood Roof Trusses for Houses and Small Buildings.”
Where the ability of a truss design to satisfy the requirements of Sentence (1) is demonstrated by analysis, it shall be carried out in accordance with good engineering practice
such as that described in TPIC 2007, “Truss Design Procedures and Specifications for Light Metal Plate Connected
Wood Trusses.”
9.23.15. Subflooring
9.23.15.1. Subflooring Required
Subflooring shall be provided beneath finish flooring where the finish flooring does not have adequate strength to support the
specified live loads (see Subsection 9.30.3.).
9.23.15.2. Material Standards
Except as provided in Sentence (2), wood-based panels for subfloors shall conform to
Particleboard subflooring may be used only where a building is constructed in a factory so that the subfloor will not be exposed to the weather.
Subflooring described in Sentence (2) shall conform to grade D-2 or D-3 in ANSI A208.1, “Particleboard.”
Subflooring described in Sentence (2) shall have its upper surface and all edges treated to restrict water absorption, where the subfloor is used in bathrooms, kitchens,
laundry rooms or other areas subject to periodic wetting. (See Appendix A.) 9.23.15.3. Edge Support
Where the edges of panel-type subflooring are required to be supported (see Sentence 9.30.2.1.(2)), such support shall consist of tongue-and-groove panel edges or not less than 38 mm by 38 mm blocking securely nailed between framing members.
9.23.15.4. Direction of Installation
Plywood subflooring shall be installed with the surface grain at right angles to the joists and with joints parallel to floor joists
staggered.
OSB subflooring conforming to CAN/CSA-O325, “Construction Sheathing,” or to O-1 and O-2 grades in CSA O437.0, “OSB and Waferboard,” and waferboard subflooring conforming to R-1 grade in CSA O437.0 shall be installed so that the direction of face orientation is at right angles to the joists and the joints parallel
to the floor joists are staggered. (See Appendix A.) 9.23.15.5. Subfloor Thickness or Rating
Except as provided in Sentences (2) and (3), subfloors shall conform to either Table 9.23.15.5.A or Table 9.23.15.5.B| Table 9.23.15.5.A Thickness of Subflooring Forming part of Sentences 9.23.15.5.(1) and 9.23.16.7.(1) | ||||
|
Maximum Spacing of Supports, mm (in.) |
Minimum Thickness, mm (in.) |
|||
| Plywood and OSB, O-2 Grade | OSB, O-1 Grade, and Waferboard, R-1 Grade | Particleboard | Lumber | |
|
400 (16) |
15.5 (⅝) |
15.9 (⅝) |
15.9 (⅝) |
17.0 (11/16) |
|
500 (20) |
15.5 (⅝) |
15.9 (⅝) |
19.0 (¾) |
19.0 (¾) |
|
600 (24) |
18.5 (¾) |
19.0 (¾) |
25.4 (1) |
19.0 (¾) |
| Table 9.23.15.5.B Rating for Subfloor when Applying CAN/CSA-O325 Forming part of Sentences 9.23.15.5.(1) and 9.23.16.7.(1) | ||
| Maximum Spacing of Supports, mm | Panel Mark | |
| Subfloor | Used with Panel-Type Underlay | |
| 400 | 1F16 | 2F16 |
| 500 | 1F20 | 2F20 |
| 600 | 1F24 | 2F24 |
Where the finished flooring consists of not less than 19 mm matched wood strip flooring laid at right angles to joists spaced not more than 600 mm o.c., subflooring
shall be permitted to consist of not less than
Except where the flooring consists of ceramic tiles applied with adhesive, where a separate panel-type underlay or concrete topping
is applied to a subfloor on joists spaced not more than 400
mm o.c., the subfloor is permitted to consist of not less than9.23.15.6. Annular Grooved Nails
When resilient flooring is applied directly to an OSB, waferboard, particleboard or plywood subfloor, the subfloor shall be fastened
to the supports with annular grooved nails.
9.23.15.7. Lumber Subflooring
9.23.16. Roof Sheathing
9.23.16.1. Required Roof Sheathing

Except where the 1-in-50 hourly wind pressure is less than 0.8 kPa and the seismic spectral response
acceleration, Sa(0.2), is less than or equal to 0.70,
continuous lumber or panel-type roof sheathing shall be installed to support the roofing.
9.23.16.2. Material Standards
Wood-based panels used for roof sheathing shall conform to the requirements of9.23.16.3. Direction of Installation
Plywood roof sheathing shall be installed with the surface grain at right angles to the roof framing.
OSB roof sheathing conforming to CAN/CSA-O325, “Construction Sheathing,” or to O-1 and O-2 grades as specified in CSA O437.0, “OSB and Waferboard,” shall be installed with the direction of face orientation at right angles to the roof
framing members. (See A-9.23.15.4.(2) in Appendix A.)
9.23.16.4. Joints in Panel-Type Sheathing
Panel-type sheathing board shall be applied so that joints perpendicular to the roof ridge are staggered where9.23.16.5. Lumber Roof Sheathing
Lumber roof sheathing shall not be more than 286 mm wide and shall be applied so that all ends are supported with end joints staggered.
Lumber roof sheathing shall be installed diagonally, where
or

Lumber roof sheathing shall be designed according to Part 4, where
9.23.16.6. Edge Support
Where panel-type roof sheathing requires edge support, the support shall consist of metal H clips or not less than 38 mm by 38 mm blocking securely nailed between framing members.
9.23.16.7. Thickness or Rating
The thickness or rating of roof sheathing on a flat roof used as a walking deck shall conform to either Table 9.23.15.5.A or Table 9.23.15.5.B for subfloors.
The thickness or rating of roof sheathing on a roof not used as a walking deck shall conform to either Table 9.23.16.7.A or Table 9.23.16.7.B
CAN/ULC-S706, “Wood Fibre Insulating Boards for Buildings,”
is permitted to be used as a roof sheathing over supports spaced not more than 400 mm o.c. provided the roofing consists of
All edges of sheathing described in Sentence (3) shall be supported by blocking or framing. | Table 9.23.16.7.A Thickness of Roof Sheathing Forming part of Sentence 9.23.16.7.(2) | |||||
|
Maximum Spacing of Supports, mm |
Minimum Thickness, mm |
||||
| Plywood, and OSB, O-2 Grade | OSB, O-1 Grade, and Waferboard, R-1 Grade | Lumber | |||
| Edges Supported | Edges Unsupported | Edges Supported | Edges Unsupported | ||
|
300 |
7.5 |
7.5 |
9.5 |
9.5 |
17.0 |
|
400 |
7.5 |
9.5 |
9.5 |
11.1 |
17.0 |
|
600 |
9.5 |
12.5 |
11.1 |
12.7 |
19.0 |

| Table 9.23.16.7.B Rating for Roof Sheathing When Applying CAN/CSA-O325 Forming part of Sentence 9.23.16.7.(2) | ||
|
Maximum Spacing of Supports, mm (in.) |
Panel Mark | |
| Edges Supported | Edges Unsupported | |
|
400 (16) |
2R16 | 1R16 |
|
500 (20) |
2R20 | 1R20 |
|
600 (24) |
2R24 | 1R24 |
9.23.17. Wall Sheathing
9.23.17.1. Required Sheathing
Exterior walls and gable ends shall be sheathed when the exterior cladding requires intermediate fastening between supports or if the
exterior cladding requires solid backing.
9.23.17.2. Thickness, Rating and Material Standards
Where wall sheathing is required
for the purpose of complying with this Section,
it shall conform to either Table 9.23.17.2.A or B.
(See also Article 9.25.5.1.)
| Table 9.23.17.2.A Wall Sheathing Thickness and Specifications Forming part of Sentence 9.23.17.2.(1) | |||
| Type of Sheathing |
Minimum Thickness, mm(1) | Material Standards | |
|
With Supports
|
With Supports
|
||
| Fibreboard (insulating) | 9.5 | 11.1 |
CAN/ULC-S706 |
| Gypsum sheathing | 9.5 | 12.7 |
CAN/CSA-A82.27-M |
| Lumber | 17.0 | 17.0 |
See Table 9.3.2.1. |
| Mineral Fibre, Rigid Board, Type 2 | 25 | 25 | |
| OSB, O-2 Grade | 6.0 | 7.5 |
CSA O437.0 |
| OSB, O-1 Grade, and Waferboard, R-1 Grade | 6.35 | 7.9 |
CSA O437.0 |
| Phenolic, faced | 25 | 25 | |
| Plywood (exterior type) | 6.0 | 7.5 | |
| Polystyrene, Types 1 and 2 | 38 | 38 |
CAN/ULC-S701 |
| Polystyrene, Types 3 and 4 | 25 | 25 |
CAN/ULC-S701 |
|
Polyurethane and Polyisocyanurate Type 1, faced |
38 | 38 |
CAN/ULC-S704 |
|
Polyurethane and Polyisocyanurate Types 2 and 3, faced |
25 | 25 |
CAN/ULC-S704 |
| Notes to Table 9.23.17.2.A: | |
|
|
|
| (1) | See also Sentences 9.27.5.1.(2) to (4). |
| Table 9.23.17.2.B Rating for Wall Sheathing when Applying CAN/CSA-O325 Forming part of Sentence 9.23.17.2.(1) | |
| Maximum Spacing of Supports, mm | Panel Mark |
| 400 | W16 |
| 500 | W20 |
| 600 | W24 |
9.23.17.3. Attachment of Cladding to Sheathing
Gypsum sheathing, rigid insulation and fibreboard shall not be used for the attachment of cladding materials.
9.23.17.4. Lumber Sheathing
Where lumber wall sheathing is required to provide bracing according to Article 9.23.10.2., it shall be applied with end joints staggered.
9.23.17.5. Joints in Panel-Type Sheathing
A gap of not less than 2 mm shall be left between sheets of plywood, OSB, waferboard or fibreboard.
9.23.17.6. Mansard Style Roofs
Where the bottom portions of mansard style roofs are vented, the vertical framing members behind the sloping portions shall be
considered on the same basis as exterior wall studs and shall conform
to Articles 9.27.3.2. to 9.27.3.6.