Division B
Acceptable Solutions

Part 9 — Housing and Small Buildings

Section 9.23. Wood-Frame Construction

9.23.1. Application

9.23.1.1. Limitations
(See Appendix A.)
1) Intent StatementThis Section applies to constructions where wall, floor and roof planes are generally comprised of lumber frames of small repetitive structural members, or engineered components, and where
a) roof and wall planes are clad, sheathed or braced on at least one side,
b) the small repetitive structural members are spaced not more than 600 mm o.c.,
c) the constructions do not serve as foundations,
d) the specified live load on supported subfloors and floor framing does not exceed 2.4 kPa, and
e) the span of any structural member does not exceed 12.20 m.
(See Appendix A.)
2) Intent StatementWhere the conditions in Sentence (1) are exceeded for wood constructions, the design of the framing and fastening shall conform to Subsection 4.3.1.

9.23.2. General

9.23.2.1. Strength and Rigidity
1) Intent StatementAll members shall be so framed, anchored, fastened, tied and braced to provide the necessary strength and rigidity.
9.23.2.2. Protection from Decay
1) Intent StatementEnds of wood joists, beams and other members framing into masonry or concrete shall be treated to prevent decay where the bottom of the member is at or below ground level, or a 12 mm air space shall be provided at the end and sides of the member.
2) Intent StatementAir spaces required in Sentence (1) shall not be blocked by insulation, vapour barriers or airtight materials.
9.23.2.3. Protection from Dampness
1) Intent StatementExcept as permitted in Sentence (2), wood framing members that are not pressure-treated with a wood preservative and that are supported on concrete in contact with the ground or fill shall be separated from the concrete by not less than 0.05 mm polyethylene film or Type S roll roofing.
2) Intent StatementDampproofing material referred to in Sentence (1) is not required where the wood member is at least 150 mm above the ground.
9.23.2.4. Lumber
1) Intent StatementLumber shall conform to Subsection 9.3.2.

9.23.3. Fasteners

9.23.3.1. Standards for Nails and Screws
1) change beginExcept as provided in Sentence (2) and unless otherwise indicated, nails specified in this Section shall be common steel wire nails or common spiral nails conforming to

contentHistory

2) Nails used to comply with Table 9.23.3.4. shall have a diameter not less than that stated in Table 9.23.3.1. (See Appendix A.)

contentHistory

Table 9.23.3.1.
Diameter of Nails
Forming part of Sentence 9.23.3.1.(2)
Minimum Length of Nails, mm Diameter of Nails, mm
57 2.87
63 3.25
76 3.66
82 3.66
101 or greater 4.88
3) Wood screws specified in this Section shall conform to ASME B18.6.1, “Wood Screws (Inch Series).” (See Appendix A.)change end
9.23.3.2. Length of Nails
1) Intent StatementAll nails shall be long enough so that not less than half their required length penetrates into the second member.
9.23.3.3. Prevention of Splitting
1) Intent StatementSplitting of wood members shall be minimized by staggering the nails in the direction of the grain and by keeping nails well in from the edges. (See Appendix A.)
9.23.3.4. Nailing of Framing
1) Intent StatementExcept as provided in Sentence (2), nailing of framing shall conform to Table 9.23.3.4.
2) Intent StatementWhere the bottom wall plate or sole plate of an exterior wall is not nailed to change beginfloorchange end joists, change beginrim joistschange end or blocking in conformance with Table 9.23.3.4., the exterior wall is permitted to be fastened to the floor framing by
a) having plywood, OSB or waferboard sheathing extend down over floor framing and fastened to the floor framing by nails or staples conforming to Article 9.23.3.5., or
b) tying the wall framing to the floor framing by galvanized-metal strips
i) 50 mm wide,
ii) not less than 0.41 mm thick,
iii) spaced not more than 1.2 m apart, and
iv) fastened at each end with at least two 63 mm nails.
Table 9.23.3.4.
Nailing for Framing
Forming part of Sentence 9.23.3.4.(1)
Construction Detail Minimum Length of Nails, mm Minimum Number or Maximum Spacing of Nails

Floor joist change beginor blocking perpendicular to sill plate or top wall plate belowchange end – toe nail

82

2 change beginper floor joist or blockingchange end

change beginRim joist, trimmer joist or blocking – supporting walls with required braced wall panels – to sill plate or top wall plate – toe nailchange end

change begin82change end

change begin150 mm (o.c.)change end

Wood or metal strapping to underside of floor joists 57 2
Cross bridging to joists 57 2 at each end
Double header or trimmer joists 76

300 mm (o.c.)

Floor joist to stud (balloon construction) 76 2
Ledger strip to wood beam 82 2 per joist

Joist to joist splice (see also Table 9.23.14.8.)

76 2 at each end
Tail joist to adjacent header joist 82 5
(end nailed) around openings 101 3
Each header joist to adjacent trimmer joist 82 5
(end nailed) around openings 101 3
Stud to wall plate (each end) toe nail 63 4
or end nail 82 2
Doubled studs at openings, or studs at walls or wall intersections and corners 76

750 mm (o.c.)

Doubled top wall plates 76

600 mm (o.c.)

Bottom wall plate or sole plate to change beginfloor joists, rim joistschange end or blocking (exterior walls)(1)

82

400 mm (o.c.)

change beginBottom wall plate or sole plate – in required braced wall panels – to floor joists, rim joists or blocking (exterior walls)(1)change end

change begin82change end

change begin150 mm (o.c.)change end

Interior walls to framing or subflooring 82

600 mm (o.c.)

change beginRequired braced wall panels – in interior walls – to framing above and belowchange end

change begin82change end

change begin150 mm (o.c.)change end

Horizontal member over openings in non-loadbearing walls – each end

82 2
Lintels to studs 82 2 at each end
Ceiling joist to plate – toe nail each end 82 2change end

Roof rafter, roof truss or roof joist to plate – toe nail(2)

82 3
Rafter plate to each ceiling joist 101 2
Rafter to joist (with ridge supported) 76 3
Rafter to joist (with ridge unsupported) 76

see Table 9.23.14.8.

Gusset plate to each rafter at peak 57 4
Rafter to ridge board – toe nail – end nail 82 3
Collar tie to rafter – each end 76 3
Collar tie lateral support to each collar tie 57 2
Jack rafter to hip or valley rafter 82 2
Roof strut to rafter 76 3

Roof strut to loadbearing wall – toe nail

82 2

38 mm × 140 mm or less plank decking to support

82 2

Plank decking wider than 38 mm × 140 mm to support

82 3

38 mm edge laid plank decking to support (toe nail)

76 1

38 mm edge laid plank to each other

76

450 mm (o.c.)

Notes to Table 9.23.3.4.:

(1) See Sentence 9.23.3.4.(2).
(2) change beginSee Sentence 9.23.3.4.(3).change end
3) Intent Statementchange beginWhere the 1-in-50 hourly wind pressure is equal to or greater than 0.8 kPa, roof rafters, joists or trusses shall be tied to the wall framing with connectors that will resist a factored uplift load of 3 kN.
4) Intent StatementGalvanized-steel straps are deemed to comply with Sentence (3), provided they are
a) 50 mm wide,
b) not less than 0.91 mm thick, and
c) fastened at each end with at least four 63 mm nails.change end
9.23.3.5. Fasteners for Sheathing or Subflooring
1) Intent Statementchange beginExcept as provided in Sentences (2) and (3),change end fastening of sheathing and subflooring shall conform to Table 9.23.3.5.A.
Table 9.23.3.5.A
Fasteners for Subflooring change beginand for Sheathing where HWP is Less Than 0.8 kPa and Sa(0.2) is Not More Than 0.70change end
Forming part of Sentence 9.23.3.5.(1)
Element Minimum Length of Fasteners, mm Minimum Number or Maximum Spacing of Fasteners
Common or Spiral Nails Ring Thread Nails or Screws Roofing Nails Staples

Board lumber 184 mm or less wide

51 45 n/a 51 2 per support

Board lumber more than 184 mm wide

51 45 n/a 51 3 per support

Fibreboard sheathing up to 13 mm thick

n/a n/a 44 28 150 mm (o.c.) along edges and 300 mm (o.c.) along intermediate supports

Gypsum sheathing up to 13 mm thick

n/a n/a 44 n/a
Plywood, OSB or waferboard up to 10 mm thick 51 45 n/a 38
Plywood, OSB or waferboard change beginoverchange end 10 mm and up to 20 mm thick 51 45 n/a 51
Plywood, OSB or waferboard change beginover 20 mm and up to 25 mmchange end thick 57 51 n/a n/a
2) Intent Statementchange beginFastening of roof sheathing and sheathing in required braced wall panels shall conform to Table 9.23.3.5.B, where
a) the 1-in-50 hourly wind pressure (HWP) is equal to or greater than 0.8 kPa and less than 1.2 kPa, or
b) the seismic spectral response acceleration, Sa(0.2), is greater than 0.70 and not more than 1.2.
Table 9.23.3.5.B
Fasteners for Sheathing where HWP is Equal to or Greater Than 0.8 kPa and Less Than 1.2 kPa or where Sa(0.2) is Greater Than 0.70 and Not More Than 1.2
Forming part of Sentence 9.23.3.5.(2)
Element Minimum Length of Fasteners, mm Minimum Number or Maximum Spacing of Fasteners
Common, Spiral or Ring Thread Nails Screws 14-Gage Staples

Board lumber 184 mm or less wide

63 51 63 2 per support

Board lumber more than 184 mm wide

63 51 63 3 per support

Plywood, OSB or waferboard up to 20 mm thick(1)

63 51 63 150 mm (o.c.) along edges and 300 mm (o.c.) along intermediate supports; and for roof sheathing where HWP is equal to or greater than 0.8 kPa and less than 1.2 kPa, 50 mm (o.c.) within 1 m of the edges of the roof

Plywood, OSB or waferboard over 20 mm and up to 25 mm thick

63 57 n/a
Notes to Table 9.23.3.5.B:

(1) See Appendix A.
3) Intent StatementFastening of sheathing shall conform to Part 4,
a) where the 1-in-50 hourly wind pressure is equal to or greater than 1.2 kPa, or
b) for required braced wall panels, where the seismic spectral response acceleration, Sa(0.2), is greater than 1.2.change end
4) Intent StatementStaples shall not be less than 1.6 mm in diameter or thickness, with not less than a 9.5 mm crown driven with the crown parallel to framing.
5) Intent StatementRoofing nails for the attachment of fibreboard or gypsum sheathing shall not be less than 3.2 mm in diameter with a minimum head diameter of 11.1 mm.
6) Intent StatementFlooring screws shall not be less than 3.2 mm in diameter.

9.23.4. Maximum Spans

9.23.4.1. Application
1) Intent StatementSpans provided in this Subsection for joists, beams and lintels supporting floors shall apply only where
a) the floors serve residential areas as described in Table 4.1.5.3., or
b) the uniformly distributed live load on the floors does not exceed that specified for residential areas as described in Table 4.1.5.3.
2) Intent StatementSpans for joists, beams and lintels supporting floors shall be determined according to Subsection 4.1.3. where the supported floors
a) serve other than residential areas, or
b) support a uniform live load in excess of that specified for residential areas.
9.23.4.2. Spans for Joists, Rafters and Beams
(See Appendix A.)
1) Intent StatementExcept as required in Sentence (2) and Article 9.23.14.10., spans for wood joists and rafters shall conform to the spans shown in Tables A-1 to A-7 for the uniform live loads shown in the Tables. (See Article 9.4.2.2.)
2) Intent StatementSpans for floor joists that are not selected from Tables A-1 and A-2 and that are required to be designed for the same loading conditions, shall not exceed the design requirements for uniform loading and vibration criteria. (See Appendix A.)
3) Intent StatementSpans for built-up wood and glued-laminated timber floor beams shall conform to the spans in Tables A-8 to A-11 (See Article 9.4.2.2.)
4) Intent StatementSpans for roof ridge beams shall conform to the spans in Table A-12 for the uniform snow load shown. (See Articles 9.4.2.2. and 9.23.14.8.)
9.23.4.3. Steel Beams
1) Intent StatementThe spans for steel floor beams with laterally supported top flanges shall conform to Table 9.23.4.3.  (See Appendix A.)
Table 9.23.4.3.
Maximum Spans for Steel Beams Supporting Floors in Dwelling Units(1)
Forming part of Sentence 9.23.4.3.(1)
Section Supported Joist Length, m (half the sum of joist spans on both sides of the beam)
2.4 3.0 3.6 4.2 4.8 5.4 6.0

One Storey Supported

W150 x 22 5.5 5.2 4.9 4.8 4.6 4.5 4.3
W200 x 21 6.5 6.2 5.9 5.7 5.4 5.1 4.9
W200 x 27 7.3 6.9 6.6 6.3 6.1 5.9 5.8
W200 x 31 7.8 7.4 7.1 6.8 6.6 6.4 6.2
W250 x 24 8.1 7.6 7.3 7.0 6.6 6.2 5.9
W250 x 33 9.2 8.7 8.3 8.0 7.7 7.5 7.3
W250 x 39 10.0 9.4 9.0 8.6 8.4 8.1 7.9
W310 x 31 10.4 9.8 9.4 8.9 8.4 8.0 7.6
W310 x 39 11.4 10.7 10.2 9.8 9.5 9.2 9.0

Two Storeys Supported

W150 x 22 4.9 4.4 4.1 3.8 3.5 3.4 3.2
W200 x 21 5.6 5.1 4.6 4.3 4.1 3.8 3.7
W200 x 27 6.4 6.1 5.6 5.3 4.9 4.7 4.4
W200 x 31 6.9 6.5 6.2 5.8 5.4 5.1 4.9
W250 x 24 6.8 6.1 5.6 5.2 4.9 4.6 4.4
W250 x 33 8.2 7.7 7.0 6.5 6.1 5.8 5.5
W250 x 39 8.8 8.3 7.8 7.2 6.8 6.4 6.1
W310 x 31 8.7 7.8 7.2 6.7 6.2 5.9 5.6
W310 x 39 10.0 9.3 8.5 7.9 7.4 7.0 6.7
Notes to Table 9.23.4.3.:

(1) See Appendix A.
2) Intent StatementBeams described in Sentence (1) shall at least meet the requirements for Grade 350 W steel contained in CAN/CSA-G40.21, “General Requirements for Rolled or Welded Structural Quality Steel.”
9.23.4.4. Concrete Topping
(See Appendix A.)
1) Intent StatementExcept as permitted in Sentence (2), where a floor is required to support a concrete topping, the joist spans shown in Table A-1 or the spacing of the members shall be reduced to allow for the loads due to the topping.
2) Intent StatementWhere a floor is required to support a concrete topping, joist spans are permitted to be selected from Table A-2 provided the concrete
a) is 38 to 51 mm thick,
b) is normal weight,
c) is placed directly on the subflooring, and
d) has not less than 20 MPa compressive strength after 28 days.
3) Intent StatementWhere a floor is required to support a concrete topping not more than 51 mm thick, the allowable beam spans shown in Tables A-8 to A-11 shall be multiplied by 0.8 or the supported length of the floor joists shall be reduced to allow for the loads due to the topping.
9.23.4.5. Heavy Roofing Materials
1) Intent StatementWhere a roof is required to support an additional uniform dead load from roofing materials such as concrete roofing tile, or materials other than as specified in Section 9.27., such as clay roofing tiles, the additional load shall be allowed for by reducing
a) the spans for roof joists and rafters in Tables A-4 to A-7, or the spacing of the members, and
b) the spans for ridge beams and lintels in Tables A-12 to A-16.
(See A-9.23.4.2. in Appendix A.)

9.23.5. Notching and Drilling

9.23.5.1. Holes Drilled in Framing Members
1) Intent StatementHoles drilled in roof, floor or ceiling framing members shall be not larger than one-quarter the depth of the member and shall be located not less than 50 mm from the edges, unless the depth of the member is increased by the size of the hole.
9.23.5.2. Notching of Framing Members
1) Intent StatementFloor, roof and ceiling framing members are permitted to be notched provided the notch is located on the top of the member within half the joist depth from the edge of bearing and is not deeper than one-third the joist depth, unless the depth of the member is increased by the size of the notch.
9.23.5.3. Wall Studs
1) Intent StatementWall studs shall not be notched, drilled or otherwise damaged so that the undamaged portion of the stud is less than two-thirds the depth of the stud if the stud is loadbearing or 40 mm if the stud is non-loadbearing, unless the weakened studs are suitably reinforced.
9.23.5.4. Top Plates
1) Intent StatementTop plates in walls shall not be notched, drilled or otherwise weakened to reduce the undamaged width to less than 50 mm unless the weakened plates are suitably reinforced.
9.23.5.5. Roof Trusses
1) Intent StatementRoof truss members shall not be notched, drilled or otherwise weakened unless such notching or drilling is allowed for in the design of the truss.

9.23.6. Anchorage

9.23.6.1. Anchorage of Building Frames
1) Intent StatementExcept as required by Sentence 9.23.6.3.(1), building frames shall be anchored to the foundation unless a structural analysis of wind and earthquake pressures shows anchorage is not required.
2) Intent StatementExcept as provided in change beginSentences (3) and (5)change end, anchorage shall be provided by
a) embedding the ends of the first floor joists in concrete, or
b) fastening the sill plate to the foundation with not less than 12.7 mm diam anchor bolts spaced not more than 2.4 m o.c.
3) change beginFor buildings with 2 or more floors supported by frame walls that are in areas where the seismic spectral response acceleration, Sa(0.2), is equal to or greater than 0.70 but not greater than 1.2 or the 1-in-50 hourly wind pressure is equal to or greater than 0.80 kPa but not greater than 1.20 kPa, anchorage shall be provided by fastening the sill plate to the foundation with not less than two anchor bolts per braced wall panel, where all anchor bolts used are
a) not less than 15.9 mm in diameter, located within 0.5 m of the end of the foundation, and spaced not more than 2.4 m o.c, or
b) not less than 12.7 mm in diameter, located within 0.5 m of the end of the foundation, and spaced not more than 1.7 m o.c.change end

contentHistory

4) Intent StatementAnchor bolts referred to in Sentences (2) change beginand (3)change end shall be
a) fastened to the sill plate with nuts and washers,
b) embedded not less than 100 mm in the foundation, and
c) so designed that they may be tightened without withdrawing them from the foundation.
5) Intent Statementchange beginWhere the seismic spectral response acceleration, Sa(0.2), is greater than 1.2 or the 1-in-50 hourly wind pressure is equal to or greater than 1.2 kPa, anchorage shall be designed according to Part 4.change end
9.23.6.2. Anchorage of Columns and Posts
1) Intent StatementExcept as provided in Sentences (2) and (3), exterior columns and posts shall be anchored to resist uplift and lateral movement.
2) Intent StatementExcept as provided in Sentence (3), where columns or posts support balconies, decks, verandas or other exterior platforms, and the distance from finished ground to the underside of the joists is not more than 600 mm,
a) the columns or posts shall be anchored to the foundation to resist uplift and lateral movement, or
b) the supported joists or beams shall be directly anchored to the ground to resist uplift.
3) Intent StatementAnchorage is not required for platforms described in Sentence (2) that
a) are not more than 1 storey in height,
b) are not more than 55 m2 in area,
c) do not support a roof, and
d) are not attached to another structure, unless it can be demonstrated that differential movement will not adversely affect the performance of the structure to which the platform is attached.
9.23.6.3. Anchorage of Smaller Buildings
1) Intent StatementBuildings not more than 4.3 m wide and not more than 1 storey in building height that are not anchored in accordance with Sentence 9.23.6.1.(1) shall be anchored in conformance with the requirements of CSA Z240.10.1, “Site Preparation, Foundation, and Anchorage of Manufactured Homes.”

9.23.7. Sill Plates

9.23.7.1. Size of Sill Plates
1) Intent StatementWhere sill plates provide bearing for the floor system, they shall be not less than 38 mm by 89 mm material.
9.23.7.2. Levelling and Sealing of Sill Plates
1) Intent StatementSill plates shall be
a) levelled by setting them on a full bed of mortar, or
b) laid directly on the foundation if the top of the foundation is level.
(See also Article 9.23.2.3.)
2) Intent StatementThe joint between the sill plate for exterior walls and the foundation shall be sealed in accordance with Subsection 9.25.3.

9.23.8. Beams to Support Floors

9.23.8.1. Bearing for Beams
1) Intent StatementBeams shall have even and level bearing and the bearing at end supports shall be not less than 89 mm long, except as stated in the notes to Tables A-8 to A-11
9.23.8.2. Priming of Steel Beams
1) Intent StatementExterior steel beams shall be shop primed.
9.23.8.3. Built-up Wood Beams
(See Appendix A.)
1) Intent StatementWhere a beam is made up of individual pieces of lumber that are nailed together, the individual members shall be 38 mm or greater in thickness and installed on edge.
2) Intent StatementExcept as permitted in Sentence (3), where individual members of a built-up beam are butted together to form a joint, the joint shall occur over a support.
3) Intent StatementWhere a beam is continuous over more than one span, individual members are permitted to be butted together to form a joint at or within 150 mm of the end quarter points of the clear spans, provided the quarter points are not those closest to the ends of the beam.
4) Intent StatementMembers joined at quarter points shall be continuous over adjacent supports.
5) Intent StatementJoints in individual members of a beam that are located at or near the end quarter points shall not occur in adjacent members at the same quarter point and shall not reduce the effective beam width by more than half.
6) Intent StatementNot more than one butt joint shall occur in any individual member of a built-up beam within any one span.
7) Intent StatementExcept as provided in Sentence (8), where 38 mm members are laid on edge to form a built-up beam, individual members shall be nailed together with a double row of nails not less than 89 mm in length, spaced not more than 450 mm apart in each row with the end nails located 100 mm to 150 mm from the end of each piece.
8) Intent StatementWhere 38 mm members in built-up wood beams are not nailed together as provided in Sentence (7), they shall be bolted together with not less than 12.7 mm diam bolts equipped with washers and spaced not more than 1.2 m o.c., with the end bolts located not more than 600 mm from the ends of the members.

9.23.9. Floor Joists

9.23.9.1. End Bearing for Joists
1) Intent StatementExcept when supported on ribbon boards, floor joists shall have not less than 38 mm length of end bearing.
2) Intent StatementRibbon boards referred to in Sentence (1) shall be not less than 19 mm by 89 mm lumber let into the studs.
9.23.9.2. Joists Supported by Beams
1) Intent StatementFloor joists may be supported on the tops of beams or may be framed into the sides of beams.
2) Intent StatementWhen framed into the side of a wood beam, joists referred to in Sentence (1) shall be supported on
a) joist hangers or other acceptable mechanical connectors, or
b) not less than 38 mm by 64 mm ledger strips nailed to the side of the beam, except that 38 mm by 38 mm ledger strips may be used provided each joist is nailed to the beam by not less than four 89 mm nails, in addition to the nailing for the ledger strip required in Table 9.23.3.4.
3) Intent StatementWhen framed into the side of a steel beam, joists referred to in Sentence (1) shall be supported on the bottom flange of the beam or on not less than 38 mm by 38 mm lumber bolted to the web with not less than 6.3 mm diam bolts spaced not more than 600 mm apart.
4) Intent StatementJoists referred to in Sentence (3) shall be spliced above the beam with not less than 38 mm by 38 mm lumber at least 600 mm long to support the flooring.
5) Intent StatementNot less than a 12 mm space shall be provided between the splice required in Sentence (4) and the beam to allow for shrinkage of the wood joists.
9.23.9.3. Restraint of Joist Bottoms
1) Intent StatementExcept as provided in Sentence 9.23.9.4.(1), bottoms of floor joists shall be restrained from twisting at each end by toe-nailing to the supports, end-nailing to the header joists or by providing continuous strapping, blocking between the joists or cross-bridging near the supports.
9.23.9.4. Strapping, Bridging, Furring and Ceilings in Tables A-1 and A-2
(See A-9.23.4.2.(2) in Appendix A.)
1) Intent StatementExcept as permitted by Sentence (5), where strapping is specified in Table A-1, it shall be
a) not less than 19 mm by 64 mm, nailed to the underside of floor joists,
b) located not more than 2 100 mm from each support or other rows of strapping, and
c) fastened at each end to a sill or header.
2) Intent StatementWhere bridging is specified in Table A-1, it shall consist of not less than 19 mm by 64 mm or 38 mm by 38 mm cross bridging located not more than 2 100 mm from each support or other rows of bridging.
3) Intent StatementWhere bridging and strapping are specified in Table A-1,
a) bridging shall
i) comply with Sentence (2), or
ii) consist of 38 mm solid blocking located not more than 2 100 mm from each support or other rows of bridging and securely fastened between the joists, and
b) except as provided in Sentence (5), strapping shall comply with Sentence (1) and be installed under the bridging.
4) Intent StatementBridging specified in Table A-2 shall consist of
a) bridging as described in Sentence (2), or
b) 38 mm solid blocking located not more than 2 100 mm from each support or other rows of bridging and securely fastened between the joists.
5) Intent StatementStrapping described in Sentence (1) and Clause (3)(b) is not required where
a) furring strips complying with Table 9.29.3.1. are fastened directly to the joists, or
b) a panel-type ceiling finish complying with Subsection 9.29.5., 9.29.6., 9.29.7., 9.29.8., or 9.29.9. is attached directly to the joists.
6) Intent StatementWhere a ceiling attached to wood furring is specified in Table A-2,
a) the ceiling finish shall consist of gypsum board, plywood or OSB not less than 12.7 mm thick, and
b) the furring shall be
i) 19 mm by 89 mm wood furring spaced at not more than 600 mm o.c., or
ii) 19 mm by 64 mm wood furring spaced at not more than 400 mm o.c.
9.23.9.5. Header Joists
1) Intent StatementHeader joists around floor openings shall be doubled when they exceed 1.2 m in length.
2) Intent StatementThe size of header joists exceeding 3.2 m in length shall be determined by calculations.
9.23.9.6. Trimmer Joists
1) Intent StatementTrimmer joists around floor openings shall be doubled when the length of the header joist exceeds 800 mm.
2) Intent StatementWhen the header joist exceeds 2 m in length the size of the trimmer joists shall be determined by calculations.
9.23.9.7. Support of Tail and Header Joists
1) Intent StatementWhen tail joists and header joists are supported by the floor framing, they shall be supported by suitable joist hangers or nailing in accordance with Table 9.23.3.4.
9.23.9.8. Support of Walls
1) Intent StatementNon-loadbearing walls parallel to the floor joists shall be supported by joists beneath the wall or on blocking between the joists.
2) Intent StatementBlocking referred to in Sentence (1) for the support of non-loadbearing walls shall be
a) not less than 38 mm by 89 mm lumber, and
b) change beginexcept as required for the fastening of walls constructed with required braced wall panels,change end spaced not more than 1.2 m apart.
3) Intent Statementchange beginExcept as provided in Sentence (6),change end non-loadbearing interior walls at right angles to the floor joists are not restricted as to location.
4) Intent StatementLoadbearing interior walls parallel to floor joists shall be supported by beams or walls of sufficient strength to safely transfer the specified live loads to the vertical supports.
5) Intent Statementchange beginUnless the joist size is designed to support such loads,change end loadbearing interior walls at right angles to floor joists shall be located
a) not more than 900 mm from the joist support where the wall does not support a floor, and
b) not more than 600 mm from the joist support where the wall supports one or more floors.
6) Intent Statementchange beginLoadbearing and non-loadbearing walls constructed with required braced wall panels shall be continuously supported by floor joists, blocking or rim joists to allow for the required fastening (see Table 9.23.3.4.).change end
9.23.9.9. Cantilevered Floor Joists
1) Intent StatementFloor joists supporting roof loads shall not be cantilevered more than 400 mm beyond their supports where 38 mm by 184 mm joists are used and not more than 600 mm beyond their supports where 38 mm by 235 mm or larger joists are used.
2) Intent StatementThe cantilevered portions referred to in Sentence (1) shall not support floor loads from other storeys unless calculations are provided to show that the design resistances of the cantilevered joists are not exceeded.
3) Intent StatementWhere cantilevered floor joists described in Sentences (1) and (2) are at right angles to the main floor joists, the tail joists in the cantilevered portion shall extend inward away from the cantilever support a distance equal to not less than 6 times the length of the cantilever, and shall be end nailed to an interior doubled header joist in conformance with Table 9.23.3.4.

9.23.10. Wall Studs

9.23.10.1. Stud Size and Spacing
1) Intent StatementThe size and spacing of studs shall conform to Table 9.23.10.1.
Table 9.23.10.1.
Size and Spacing of Studs
Forming part of Sentence 9.23.10.1.(1)
Type of Wall

Supported Loads (including dead loads)

Minimum Stud Size, mm Maximum Stud Spacing, mm Maximum Unsupported Height, m
Interior No load 38 x 38 400 2.4

38 x 89 flat(1)

400 3.6
Attic not accessible by a stairway 38 x 64 600 3.0

38 x 64 flat(1)

400 2.4
38 x 89 600 3.6

38 x 89 flat(1)

400 2.4

Attic accessible by a stairway plus one floor
Roof load plus one floor
Attic not accessible by stairway plus 2 floors

38 x 89 400 3.6

Roof load
Attic accessible by a stairway
Attic not accessible by a stairway plus one floor

38 x 64 400 2.4
38 x 89 600 3.6

Attic accessible by a stairway plus 2 floors
Roof load plus 2 floors

38 x 89 300 3.6
64 x 89 400 3.6
38 x 140 400 4.2

Attic accessible by a stairway plus 3 floors
Roof load plus 3 floors

38 x 140 300 4.2
Exterior Roof with or without attic storage 38 x 64 400 2.4
38 x 89 600 3.0
Roof with or without attic storage plus one floor 38 x 89 400 3.0
38 x 140 600 3.0
Roof with or without attic storage plus 2 floors 38 x 89 300 3.0
64 x 89 400 3.0
38 x 140 400 3.6
Roof with or without attic storage plus 3 floors 38 x 140 300 1.8
Notes to Table 9.23.10.1.:

(1) See Article 9.23.10.3.
9.23.10.2. Bracing and Lateral Support
1) Intent StatementWhere loadbearing interior walls are not finished in accordance with change beginSection 9.29.change end, blocking or strapping shall be fastened to the studs at mid-height to prevent sideways buckling.
9.23.10.3. Orientation of Studs
1) Intent StatementExcept as permitted in Sentences (2) and (3), all studs shall be placed at right angles to the wall face.
2) Intent StatementStuds on the flat are permitted to be used in gable ends of roofs that contain only unfinished space or in non-loadbearing interior walls within the limits described in Article 9.23.10.1.
3) Intent StatementWall studs that support only a load from an attic not accessible by a stairway are permitted to be placed on the flat within the limits permitted in Article 9.23.10.1. provided
a) the studs are clad on not less than one side with plywood, OSB or waferboard sheathing fastened to the face of the studs with a structural adhesive, and
b) the portion of the roof supported by the studs does not exceed 2.1 m in width.
9.23.10.4. Continuity of Studs
1) Intent StatementWall studs shall be continuous for the full storey height except at openings and shall not be spliced except by fingerjoining with a structural adhesive. (See Appendix A.)
9.23.10.5. Support for Cladding, Sheathing and Finishing Materials
1) Intent StatementCorners and intersections shall be designed to provide adequate support for the vertical edges of interior finishes, sheathing and cladding materials, and in no instance shall exterior corners be framed with less than the equivalent of 2 studs.
2) Intent StatementWhere the vertical edges of interior finishes at wall intersections are supported at vertical intervals by blocking or furring, the vertical distance between such supports shall not exceed the maximum distance between supports specified in Section 9.29.
9.23.10.6. Studs at Sides of Openings
1) Intent StatementWhere the lintel spanning the opening is more than 3 m long, studs shall be tripled on each side of the opening so that
a) the two inner studs on each side extend from the bottom of the supported lintel to the top of the bottom wall plate, and
b) the outer stud on each side extends from the bottom of the top wall plate to the bottom wall plate.
2) Intent StatementExcept as provided in Sentence (3), where the lintel spanning the opening is not more than 3 m long, studs shall be doubled on each side of the opening so that
a) the inner studs on each side extend from the bottom of the supported lintel to the top of the bottom wall plate, and
b) the outer stud on each side extends from the bottom of the top wall plate to the bottom wall plate.
3) Intent StatementSingle studs are permitted to be used on either side of openings
a) in non-loadbearing interior walls not required to have fire-resistance ratings, provided the studs extend from the top wall plate to the bottom wall plate, or
b) in loadbearing or non-loadbearing interior or exterior walls, provided
i) the opening is less than and within the required stud spacing, and
ii) no 2 such openings of full stud-space width are located in adjacent stud spaces.
(See Appendix A.)

9.23.11. Wall Plates

9.23.11.1. Size of Wall Plates
1) Intent StatementExcept as provided in Sentence (2), wall plates shall be
a) not less than 38 mm thick, and
b) not less than the required width of the wall studs.
2) Intent StatementIn non-loadbearing walls and in loadbearing walls where the studs are located directly over framing members, the bottom wall plate is permitted to be 19 mm thick.
9.23.11.2. Bottom Wall Plates
1) Intent StatementA bottom wall plate shall be provided in all cases.
2) Intent StatementThe bottom plate in exterior walls shall not project more than one-third the plate width over the support.
9.23.11.3. Top Plates
1) Intent StatementExcept as permitted in Sentences (2) to (4), at least 2 top plates shall be provided in loadbearing walls.
2) Intent StatementA single top plate is permitted to be used in a section of a loadbearing wall containing a lintel provided the top plate forms a tie across the lintel.
3) Intent StatementA single top plate is permitted to be used in loadbearing walls where the concentrated loads from ceilings, floors and roofs are not more than 50 mm to one side of the supporting studs and in all non-loadbearing walls.
4) Intent StatementThe top plates need not be provided in a section of loadbearing wall containing a lintel provided the lintel is tied to the adjacent wall section with not less than
a) 75 mm by 150 mm by 0.91 mm thick galvanized steel, or
b) 19 mm by 89 mm by 300 mm wood splice nailed to each wall section with at least three 63 mm nails.
9.23.11.4. Joints in Top Plates
1) Intent StatementJoints in the top plates of loadbearing walls shall be staggered not less than one stud spacing.
2) Intent StatementThe top plates in loadbearing walls shall be lapped or otherwise tied at corners and intersecting walls in accordance with Sentence (4).
3) Intent StatementJoints in single top plates used with loadbearing walls shall be tied in accordance with Sentence (4).
4) Intent StatementTies referred to in Sentences (2) and (3) shall be the equivalent of not less than 75 mm by 150 mm by 0.91 mm thick galvanized steel nailed to each wall with at least three 63 mm nails.

9.23.12. Framing over Openings

9.23.12.1. Openings in Non-Loadbearing Walls
1) Intent StatementExcept as provided in Sentence (2), openings in non-loadbearing walls shall be framed with not less than 38 mm material the same width as the studs, securely nailed to adjacent studs.
2) Intent StatementOpenings for doors in non-loadbearing walls required to be fire separations with a fire-resistance rating shall be framed with the equivalent of at least two 38 mm thick members that are the same width as the wall plates.
9.23.12.2. Openings in Loadbearing Walls
1) Intent StatementOpenings in loadbearing walls greater than the required stud spacing shall be framed with lintels designed to carry the superimposed loads to adjacent studs. (See A-9.23.10.6.(3) in Appendix A.)
2) Intent StatementExcept as provided in Sentence 9.23.12.3.(2), where 2 or more members are used in lintels, they shall be fastened together with not less than 82 mm nails in a double row, with nails not more than 450 mm apart in each row.
3) Intent StatementLintel members are permitted to be separated by filler pieces.
9.23.12.3. Lintel Spans and Sizes
1) Intent Statement Spans and sizes of wood lintels shall conform to the spans shown in Tables A-12 to A-16
b) where the wall studs exceed 38 mm by 64 mm in size,
c) where the spans of supported joists do not exceed 4.9 m, and
d) where the spans of trusses do not exceed 9.8 m.
2) Intent StatementIn loadbearing exterior and interior walls of 38 mm by 64 mm framing members, lintels shall consist of
a) 64 mm thick members on edge, or
b) 38 mm thick and 19 mm thick members fastened together with a double row of nails not less than 63 mm long and spaced not more than 450 mm apart.
3) Intent Statement Lintels referred to in Sentence (2)
a) shall be not less than 50 mm greater in depth than those shown in Tables A-12 to A-16 for the maximum spans shown, and
b) shall not exceed 2.24 m in length.

9.23.13. change beginBracing to Resist Lateral Loads Due to Wind and Earthquake

(See Appendix A.)
9.23.13.1. Requirements for Low to Moderate Wind and Seismic Forces
(See Appendix A.)
1) Intent StatementThis Article applies in locations where the seismic spectral response acceleration, Sa(0.2), is not more than 0.70 and the 1-in-50 hourly wind pressure is less than 0.80 kPa.
2) Bracing to resist lateral loads shall be designed and constructed as follows:
a) exterior walls shall be
i) clad with panel-type cladding in accordance with Section 9.27.,
ii) sheathed with plywood, OSB, waferboard, fibreboard, gypsum board or diagonal lumber sheathing complying with change beginSubsection 9.23.17.change end and fastened in accordance with Table 9.23.3.5.A, or
iii) finished on the interior with a panel-type material in accordance with the requirements of Section 9.29., or
b) in accordance with
ii) Part 4, or
iii) good engineering practice such as that provided in CWC 2009, “Engineering Guide for Wood Frame Construction.”

contentHistory

9.23.13.2. Requirements for High Wind and Seismic Forces
1) Intent StatementExcept as provided in Article 9.23.13.1., this Article applies in locations where
a) the seismic spectral response acceleration, Sa(0.2), is
i) not more than 1.10 and the lowest exterior frame wall supports not more than 1 floor in buildings of heavy construction which are defined as having tile roofs or concrete topping on floors, or
ii) not more than 1.20 and the lowest exterior frame wall supports not more than 2 floors in other types of construction, and
b) the 1-in-50 hourly wind pressure is less than 1.20 kPa.
2) Intent StatementBracing to resist lateral loads shall be designed and constructed in accordance with
b) Part 4, or
c) good engineering practice such as that provided in CWC 2009, “Engineering Guide for Wood Frame Construction.”
9.23.13.3. Requirements for Extreme Wind and Seismic Forces
1) Intent StatementExcept as provided in Articles 9.23.13.1. and 9.23.13.2., this Article applies in locations where
a) the seismic spectral response acceleration, Sa(0.2), is
i) greater than 1.10 for buildings with tile roofs or concrete topping on floors,
ii) greater than 1.20 for other types of construction,
iii) greater than 0.70 and the lowest exterior frame wall supports more than 2 floors in buildings of light construction, or
iv) greater than 0.70 and the lowest exterior frame wall supports more than 1 floor in buildings of heavy construction, or
b) the 1-in-50 hourly wind pressure is equal to or greater than 1.20 kPa.
2) Intent StatementBracing to resist lateral loads shall be designed and constructed in accordance with
a) Part 4, or
b) good engineering practice such as that provided in CWC 2009, “Engineering Guide for Wood Frame Construction.”
9.23.13.4. Braced Wall Bands
(See Appendix A.)
1) Intent StatementBraced wall bands shall
a) be full storey height,
b) be not more than 1.2 m wide,
c) lap at both ends with another braced wall band,
d) be aligned with braced wall bands on storeys above and below, and
e) conform to the spacing and dimensions given in Table 9.23.13.5.
2) Intent StatementThe perimeter of the building shall be located within braced wall bands.
3) Intent StatementFor split-level buildings, a braced wall band shall be located where there is a change in floor level greater than the depth of one floor joist.
9.23.13.5. Braced Wall Panels in Braced Wall Bands
1) Intent StatementExcept as provided in Sentences (2) to (5) and Article 9.23.13.7., braced wall panels shall
a) be located within braced wall bands,
b) extend, as applicable, from the top of the supporting footing, slab or subfloor to the underside of the floor, ceiling or roof framing above, and
c) conform to the spacing and dimensions given in Table 9.23.13.5.
Table 9.23.13.5.
Spacing and Dimensions of Braced Wall Bands and Braced Wall Panels
Forming part of Sentences 9.23.13.4.(1) and 9.23.13.5.(1)
Description Spacing and Dimensions of Braced Wall Bands and Braced Wall Panels(1)(2)(3)
Seismic and Wind Loads
0.70 < Sa(0.2) < 1.0 1.0 ≤ Sa(0.2) ≤ 1.2 or
0.80 ≤ HWP < 1.2 kPa
Maximum distance between centre lines of adjacent braced wall bands measured from the furthest points between centres of the bands 10.6 m 7.6 m
Maximum distance between required braced wall panels measured from the edges of the panels 6.4 m 6.4 m
Maximum distance from the end of a braced wall band to the edge of the closest required braced wall panel 2.4 m 2.4 m
Minimum length of individual braced wall panels:    
• panel located at the end of a braced wall band where the braced wall panel connects to an intersecting braced wall panel 600 mm
• panel not located at the end of a braced wall band or braced wall panel located at the end of a braced wall band where the braced wall panel does not connect to an intersecting braced wall panel 750 mm
Minimum total length of all braced wall panels in a braced wall band    
• supporting 3 floors, light construction 75% of length of braced wall band
• supporting 2 floors, heavy construction(4) 75% of length of braced wall band
• supporting 2 floors, light construction 40% of length of braced wall band
• supporting 1 floor, heavy construction(4) 40% of length of braced wall band
• supporting 1 floor, light construction 25% of length of braced wall band
• not supporting a floor 25% of length of braced wall band
Notes to Table 9.23.13.5.:

(1) See Appendix A.
(2) All constructions include support of a roof load in addition to the indicated number of floors.
(3) See Article 9.23.13.7. for alternative methods of compliance.
(4) See Sentence 9.23.13.3.(1) for overall limit on application to heavy construction.
2) Intent StatementIn basements or crawl spaces where the perimeter foundation walls extend from the footings to the underside of the supported floor, braced wall bands constructed with braced wall panels shall be spaced not more than
a) 15 m from the perimeter foundation walls,
b) 15 m from interior foundation walls, and
c) 15 m from adjacent braced wall bands constructed with braced wall panels.
(See Appendix A.)
3) Intent StatementPortions of the perimeter of a single open or enclosed space need not comply with Sentence (1), where
a) the roof of the space projects not more than
i) 3.5 m from the face of the framing of the nearest parallel braced wall band, and
ii) half the perpendicular plan dimension,
b) that portion of the perimeter structure does not support a floor, and
c) the roof of the space is
i) integral with the roof of the rest of the building with framing members not more than 400 mm o.c., or
ii) constructed with roof framing not more than 400 mm o.c. fastened to the wall framing (see Table 9.23.3.4. and Article 9.23.9.1. for balloon framing).
(See Appendix A.)
4) Intent StatementWalls in detached garages and in accessory buildings serving a single dwelling unit, and the front wall of attached garages serving a single dwelling unit need not comply with Sentence (1) where these walls do not support a floor.
5) Intent StatementBraced wall panels in the braced wall band at the front of an attached garage serving a single dwelling unit need not comply with Sentence (1), provided
a) the maximum spacing between the front of the garage and the back wall of the garage does not exceed 7.6 m,
b) there is not more than one floor above the garage,
c) not less than 50% of the length of the back wall of the garage is constructed of braced wall panels, and
d) not less than 25% of the length of the side walls is constructed of braced wall panels.
9.23.13.6. Materials in Braced Wall Panels
1) Required braced wall panels shall be
a) clad with panel-type cladding complying with Section 9.27. and Table 9.23.3.4.,
b) sheathed with plywood, OSB, waferboard or diagonal lumber sheathing complying with Subsection 9.23.17. and Table 9.23.13.6., and fastened in accordance with Article 9.23.3.5., or
c) finished on the interior with a panel-type material in accordance with the requirements of Section 9.29. and Table 9.23.13.6.

contentHistory

Table 9.23.13.6.
Minimum Thicknesses of Cladding, Sheathing or Interior Finish for Braced Wall Panels
Forming part of Sentence 9.23.13.6.(1)
Panel-Type Cladding, Sheathing or Interior Finish Minimum Thickness
With supports 400 mm o.c. With supports 600 mm o.c.
Gypsum board interior finish(1) 12.7 mm 15.9 mm
Sheathing complying with CAN/CSA-O325 W16 W24
OSB O-1 and O-2 grades and waferboard R-1 grade 9.5 mm 12.5 mm
Plywood 9.5 mm 12.5 mm
Diagonal lumber 17 mm 17 mm
Notes to Table 9.23.13.6.:

(1) See Sentences (5) and (6).
2) Intent StatementExcept as provided in Sentence (3), required interior braced wall panels shall be
a) sheathed or finished on both sides with a wood-based material, or
b) finished on both sides with gypsum board.
3) Intent StatementRequired interior braced wall panels of wood-based material may be sheathed on one side only, provided
a) the sheathing material is plywood, OSB or waferboard, and
b) the maximum spacing of fasteners along the edge is half of the maximum spacing shown in Table 9.23.3.5.B.
4) Intent StatementFor stacked braced wall bands, where the construction of any one braced wall panel is required to be of a wood-based material, a wood-based material shall be installed in all the required braced wall panels in that braced wall band.
5) Intent StatementGypsum board interior finish shall not be considered as an acceptable sheathing material to provide the required bracing in exterior walls. (See A-9.23.13.6.(5) and (6) in Appendix A.)
6) Intent StatementAt braced wall band spacing intervals of not more than 15 m, braced wall panels shall be constructed with OSB, plywood or diagonal lumber. (See A-9.23.13.6.(5) and (6) in Appendix A.)
9.23.13.7. Additional System Considerations
1) Intent StatementExcept as provided in Sentences (2) and (3), one exterior wall of the uppermost storey in each orthogonal direction may be set back from the exterior wall of the storey below, provided the adjacent interior braced wall band of the storey below the setback
a) is spaced not more than 10.6 m from the exterior wall of the storey below the setback wall,
b) consists of braced wall panels that are constructed of a wood-based material in conformance with Sentence 9.23.13.6.(2),
c) extends to the foundation, and
d) is not taken into consideration when providing braced wall panels constructed of a wood-based material at spacing intervals of not more than 15 m as per Sentence 9.23.13.6.(6).
2) Intent StatementWhere the exterior wall of the uppermost storey is set back from the exterior wall of the storey below, the roof and floor space supporting the setback wall shall be sheathed with a wood-based material between the exterior wall of the storey below the setback and the adjacent interior braced wall bands of the storey below the setback.
3) Intent StatementWhere the exterior wall of the uppermost storey is set back from the exterior wall of the storey below, the exterior walls perpendicular to the setback wall shall
a) have their top plate connected with nails that are spaced at no greater than half the spacing required in Table 9.23.3.4., and
b) be fastened with twice the number of nails specified in Sentences 9.23.11.3.(4) and 9.23.11.4.(4).
4) Intent StatementThe maximum distance between adjacent required braced wall panels in a braced wall band, measured from the edge of the panels, may be increased to 7.3 m provided that, throughout the height of the building, the length of any braced wall panel within the braced wall band is not less than 1.2 m.
5) Intent StatementThe maximum spacing between the centre lines of required braced wall bands given in Table 9.23.13.5. may be increased from 7.6 m to no more than 10.6 m, provided that the interior braced wall band whose spacing is being increased is replaced with an interior braced wall band that
a) consists of braced wall panels that are constructed of a wood-based material in conformance with Sentence 9.23.13.6.(2),
b) extends to the foundation, and
c) is not taken into consideration when providing braced wall panels constructed of a wood-based material at spacing intervals no greater than 15 m as per Sentence 9.23.13.6.(6).
6) Intent StatementFor each orthogonal direction of the building, the length of required braced wall panels of one exterior wall given in Table 9.23.13.5. may be reduced from 40% to no less than 25% of the length of the braced wall band, provided an additional parallel and adjacent interior braced wall band is constructed that
a) is spaced not more than 10.6 m from the exterior wall,
b) consists of braced wall panels that are constructed of a wood-based material in conformance with Sentence 9.23.13.6.(2) and whose lengths sum to no less than 25% of the length of the braced wall band,
c) extends to the foundation, and
d) is not taken into consideration when providing braced wall panels constructed of a wood-based material at spacing intervals no greater than 15 m as per Sentence 9.23.13.6.(6).
7) Where the length of required braced wall panels of an exterior wall is reduced as described in Sentence (6), the ratio of the length of braced wall panels in the respective upper braced wall bands to the length of braced wall panels in the reduced exterior braced wall band shall not exceed 2.change end

contentHistory

9.23.14. Roof and Ceiling Framing

9.23.14.1. Continuity of Rafters and Joists
1) Intent StatementRoof rafters and joists and ceiling joists shall be continuous or shall be spliced over vertical supports that extend to suitable bearing.
9.23.14.2. Framing around Openings
1) Intent StatementRoof and ceiling framing members shall be doubled on each side of openings greater than 2 rafter or joist spacings wide.
9.23.14.3. End Bearing Length
1) Intent StatementThe length of end bearing of joists and rafters shall be not less than 38 mm.
9.23.14.4. Location and Attachment of Rafters
1) Intent StatementRafters shall be located directly opposite each other and tied together at the peak, or may be offset by their own thickness if nailed to a ridge board not less than 17.5 mm thick.
2) Intent StatementExcept as permitted in Sentence (3), framing members shall be connected by gusset plates or nailing at the peak in conformance with Table 9.23.3.4.
3) Intent StatementWhere the roof framing on opposite sides of the peak is assembled separately, such as in the case of factory-built houses, the roof framing on opposite sides is permitted to be fastened together with galvanized-steel strips not less than 200 mm by 75 mm by 0.41 mm thick spaced not more than 1.2 m apart and nailed at each end to the framing by at least two 63 mm nails.
9.23.14.5. Shaping of Rafters
1) Intent StatementRafters shall be shaped at supports to provide even bearing surfaces and supported directly above the exterior walls.
9.23.14.6. Hip and Valley Rafters
1) Intent StatementHip and valley rafters shall be not less than 50 mm greater in depth than the common rafters and not less than 38 mm thick, actual dimension.
9.23.14.7. Intermediate Support for Rafters and Joists
1) Intent StatementCeiling joists and collar ties of not less than 38 mm by 89 mm lumber are permitted to be assumed to provide intermediate support to reduce the span for rafters and joists where the roof slope is 1 in 3 or greater.
2) Intent StatementCollar ties referred to in Sentence (1) more than 2.4 m long shall be laterally supported near their centres by not less than 19 mm by 89 mm continuous members at right angles to the collar ties.
3) Intent StatementDwarf walls and struts are permitted to be used to provide intermediate support to reduce the span for rafters and joists.
4) Intent StatementWhen struts are used to provide intermediate support they shall be not less than 38 mm by 89 mm material extending from each rafter to a loadbearing wall at an angle of not less than 45° to the horizontal.
5) Intent StatementWhen dwarf walls are used for rafter support, they shall be framed in the same manner as loadbearing walls and securely fastened top and bottom to the roof and ceiling framing to prevent over-all movement.
6) Intent StatementSolid blocking shall be installed between floor joists beneath dwarf walls referred to in Sentence (5) that enclose finished rooms.
9.23.14.8. Ridge Support
1) Intent StatementExcept as provided in Sentence (4), roof rafters and joists shall be supported at the ridge of the roof by
a) a loadbearing wall extending from the ridge to suitable bearing, or
b) a ridge beam supported by not less than 89 mm length of bearing.
2) Intent StatementExcept as provided in Sentence (3), the ridge beam referred to in Sentence (1) shall conform to the sizes and spans shown in Table A-12, provided
a) the supported rafter or joist length does not exceed 4.9 m, and
b) the roof does not support any concentrated loads.
3) Intent StatementThe ridge beam referred to in Sentence (1) need not comply with Sentence (2) where
a) the beam is of not less than 38 mm by 140 mm material, and
b) the beam is supported at intervals not exceeding 1.2 m by not less than 38 mm by 89 mm members extending vertically from the ridge to suitable bearing.
4) Intent StatementWhen the roof slope is 1 in 3 or more, ridge support need not be provided when the lower ends of the rafters are adequately tied to prevent outward movement.
5) Intent StatementTies required in Sentence (4) are permitted to consist of tie rods or ceiling joists forming a continuous tie for opposing rafters and nailed in accordance with Table 9.23.14.8.
Table 9.23.14.8.
Rafter-to-Joist Nailing (Unsupported Ridge)
Forming part of Sentences 9.23.14.8.(5) and (6)
Roof Slope Rafter Spacing, mm

Minimum Number of Nails not less than 76 mm Long

Rafter Tied to every Joist

Rafter Tied to Joist every 1.2 m

Building Width up to 8 m

Building Width up to 9.8 m

Building Width up to 8 m

Building Width up to 9.8 m

Roof Snow Load, kPa Roof Snow Load, kPa Roof Snow Load, kPa Roof Snow Load, kPa
1.0 or less 1.5 2.0 or more 1.0 or less 1.5 2.0 or more 1.0 or less 1.5 2.0 or more 1.0 or less 1.5 2.0 or more
1 in 3 400 4 5 6 5 7 8 11
600 6 8 9 8 11
1 in 2.4 400 4 4 5 5 6 7 7 10 9
600 5 7 8 7 9 11 7 10
1 in 2 400 4 4 4 4 4 5 6 8 9 8
600 4 5 6 5 7 8 6 8 9 8
1 in 1.71 400 4 4 4 4 4 4 5 7 8 7 9 11
600 4 4 5 5 6 7 5 7 8 7 9 11
1 in 1.33 400 4 4 4 4 4 4 4 5 6 5 6 7
600 4 4 4 4 4 5 4 5 6 5 6 7
1 in 1 400 4 4 4 4 4 4 4 4 4 4 4 5
600 4 4 4 4 4 4 4 4 4 4 4 5
6) Intent StatementCeiling joists referred to in Sentence (5) shall be fastened together with at least one more nail per joist splice than required for the rafter to joist connection shown in Table 9.23.14.8.
7) Intent StatementMembers referred to in Sentence (6) are permitted to be fastened together either directly or through a gusset plate.
9.23.14.9. Restraint of Joist Bottoms
1) Intent StatementRoof joists supporting a finished ceiling, other than plywood, OSB or waferboard, shall be restrained from twisting along the bottom edges by means of furring, blocking, cross bridging or strapping conforming to Article 9.23.9.3.
9.23.14.10. Ceiling Joists Supporting Roof Load
1) Intent StatementExcept as permitted in Sentence (2), ceiling joists supporting part of the roof load from the rafters shall be not less than 25 mm greater in depth than required for ceiling joists not supporting part of the roof load.
2) Intent StatementWhen the roof slope is 1 in 4 or less, the ceiling joist sizes referred to in Sentence (1) shall be determined from the span tables for roof joists.
9.23.14.11. Roof Trusses
1) Intent StatementRoof trusses which are not designed in accordance with Part 4 shall
a) be capable of supporting a total ceiling load (dead load plus live load ) of 0.35 kPa plus two and two-thirds times the specified live roof load for 24 h, and
b) not exceed the deflections shown in Table 9.23.14.11. when loaded with the ceiling load plus one and one-third times the specified roof snow load for 1 h.
Table 9.23.14.11.
Maximum Roof Truss Deflections
Forming part of Sentence 9.23.14.11.(1)
Truss Span Type of Ceiling Maximum Deflection

4.3 m or less

Plaster or gypsum board 1/360 of the span
Other than plaster or gypsum board 1/180 of the span

Over 4.3 m

Plaster or gypsum board 1/360 of the span
Other than plaster or gypsum board 1/240 of the span
2) Intent StatementThe joint connections used in trusses described in Sentence (1) shall be designed in conformance with the requirements in Subsection 4.3.1. (See Appendix A.)
3) Intent StatementWhere the length of compression web members in roof trusses described in Sentence (1) exceeds 1.83 m, such web members shall be provided with continuous bracing to prevent buckling.
4) Intent StatementBracing required in Sentence (3) shall consist of not less than 19 mm by 89 mm lumber nailed at right angles to the web members near their centres with at least two 63 mm nails for each member.
5) Intent StatementWhere the ability of a truss design to satisfy the requirements of Sentence (1) is demonstrated by testing, it shall consist of a full scale load test carried out in conformance with CSA S307-M, “Load Test Procedure for Wood Roof Trusses for Houses and Small Buildings.”
6) Intent StatementWhere the ability of a truss design to satisfy the requirements of Sentence (1) is demonstrated by analysis, it shall be carried out in accordance with good engineering practice such as that described in TPIC 2007, “Truss Design Procedures and Specifications for Light Metal Plate Connected Wood Trusses.”

9.23.15. Subflooring

9.23.15.1. Subflooring Required
1) Intent StatementSubflooring shall be provided beneath finish flooring where the finish flooring does not have adequate strength to support the specified live loads (see Subsection 9.30.3.).
9.23.15.2. Material Standards
1) Intent StatementExcept as provided in Sentence (2), wood-based panels for subfloors shall conform to
c) CSA O153-M, “Poplar Plywood,”
2) Intent StatementParticleboard subflooring may be used only where a building is constructed in a factory so that the subfloor will not be exposed to the weather.
3) Intent Statement Subflooring described in Sentence (2) shall conform to grade D-2 or D-3 in ANSI A208.1, “Particleboard.”
4) Intent StatementSubflooring described in Sentence (2) shall have its upper surface and all edges treated to restrict water absorption, where the subfloor is used in bathrooms, kitchens, laundry rooms or other areas subject to periodic wetting. (See Appendix A.)
9.23.15.3. Edge Support
1) Intent StatementWhere the edges of panel-type subflooring are required to be supported (see Sentence 9.30.2.1.(2)), such support shall consist of tongue-and-groove panel edges or not less than 38 mm by 38 mm blocking securely nailed between framing members.
9.23.15.4. Direction of Installation
1) Intent StatementPlywood subflooring shall be installed with the surface grain at right angles to the joists and with joints parallel to floor joists staggered.
2) Intent StatementOSB subflooring conforming to CAN/CSA-O325, “Construction Sheathing,” or to O-1 and O-2 grades in CSA O437.0, “OSB and Waferboard,” and waferboard subflooring conforming to R-1 grade in CSA O437.0 shall be installed so that the direction of face orientation is at right angles to the joists and the joints parallel to the floor joists are staggered. (See Appendix A.)
9.23.15.5. Subfloor Thickness or Rating
1) Intent StatementExcept as provided in Sentences (2) and (3), subfloors shall conform to either Table 9.23.15.5.A or Table 9.23.15.5.B
Table 9.23.15.5.A
Thickness of Subflooring
Forming part of Sentences 9.23.15.5.(1) and 9.23.16.7.(1)

Maximum Spacing of Supports, mm (in.)

Minimum Thickness, mm (in.)

Plywood and OSB, O-2 Grade OSB, O-1 Grade, and Waferboard, R-1 Grade Particleboard Lumber

400 (16)

15.5 (⅝)

15.9 (⅝)

15.9 (⅝)

17.0 (11/16)

500 (20)

15.5 (⅝)

15.9 (⅝)

19.0 (¾)

19.0 (¾)

600 (24)

18.5 (¾)

19.0 (¾)

25.4 (1)

19.0 (¾)

Table 9.23.15.5.B
Rating for Subfloor when Applying CAN/CSA-O325
Forming part of Sentences 9.23.15.5.(1) and 9.23.16.7.(1)
Maximum Spacing of Supports, mm Panel Mark
Subfloor Used with Panel-Type Underlay
400 1F16 2F16
500 1F20 2F20
600 1F24 2F24
2) Intent StatementWhere the finished flooring consists of not less than 19 mm matched wood strip flooring laid at right angles to joists spaced not more than 600 mm o.c., subflooring shall be permitted to consist of not less than
a) 12.5 mm thick plywood,
b) 12.5 mm thick OSB conforming to O-2 grade,
c) 12.7 mm thick OSB conforming to O-1 grade,
d) 12.7 mm thick waferboard conforming to R-1 grade, or
e) OSB conforming to 2R32/2F16 grade.
3) Intent StatementExcept where the flooring consists of ceramic tiles applied with adhesive, where a separate panel-type underlay or concrete topping is applied to a subfloor on joists spaced not more than 400 mm o.c., the subfloor is permitted to consist of not less than
a) 12.5 mm thick plywood,
b) 12.5 mm thick OSB conforming to O-2 grade,
c) 12.7 mm thick OSB conforming to O-1 grade,
d) 12.7 mm thick waferboard conforming to R-1 grade, or
e) OSB conforming to 2R32/2F16 grade.
9.23.15.6. Annular Grooved Nails
1) Intent StatementWhen resilient flooring is applied directly to an OSB, waferboard, particleboard or plywood subfloor, the subfloor shall be fastened to the supports with annular grooved nails.
9.23.15.7. Lumber Subflooring
1) Intent StatementLumber subflooring shall be laid at an angle of not less than 45° to the joists.
2) Intent StatementLumber subflooring shall be fully supported at the ends on solid bearing.
3) Intent StatementLumber for subflooring shall be of uniform thickness and not more than 184 mm wide.

9.23.16. Roof Sheathing

9.23.16.1. Required Roof Sheathing
1) Intent Statementchange beginExcept where the 1-in-50 hourly wind pressure is less than 0.8 kPa and the seismic spectral response acceleration, Sa(0.2), is less than or equal to 0.70,change end continuous lumber or panel-type roof sheathing shall be installed to support the roofing.
9.23.16.2. Material Standards
1) Intent StatementWood-based panels used for roof sheathing shall conform to the requirements of
c) CSA O153-M, “Poplar Plywood,”
9.23.16.3. Direction of Installation
1) Intent StatementPlywood roof sheathing shall be installed with the surface grain at right angles to the roof framing.
2) Intent StatementOSB roof sheathing conforming to CAN/CSA-O325, “Construction Sheathing,” or to O-1 and O-2 grades as specified in CSA O437.0, “OSB and Waferboard,” shall be installed with the direction of face orientation at right angles to the roof framing members. (See A-9.23.15.4.(2) in Appendix A.)
9.23.16.4. Joints in Panel-Type Sheathing
1) Intent StatementPanel-type sheathing board shall be applied so that joints perpendicular to the roof ridge are staggered where
a) the sheathing is applied with the surface grain parallel to the roof ridge, and
b) the thickness of the sheathing is such that the edges are required to be supported.
2) Intent StatementA gap of not less than 2 mm shall be left between sheets of plywood, OSB or waferboard.
9.23.16.5. Lumber Roof Sheathing
1) Intent StatementLumber roof sheathing shall not be more than 286 mm wide and shall be applied so that all ends are supported with end joints staggered.
2) change beginLumber roof sheathing shall be installed diagonally, where
a) the seismic spectral response acceleration, Sa(0.2), is greater than 0.70 but not greater than 1.2, change beginorchange end
b) the 1-in-50 hourly wind pressure is equal to or greater than 0.80 kPa but less than 1.20 kPa.

contentHistory

3) Intent StatementLumber roof sheathing shall be designed according to Part 4, where
a) the seismic spectral response acceleration, Sa(0.2), is greater than 1.2, or
b) the 1-in-50 hourly wind pressure is equal to or greater than 1.20 kPa.change end
9.23.16.6. Edge Support
1) Intent StatementWhere panel-type roof sheathing requires edge support, the support shall consist of metal H clips or not less than 38 mm by 38 mm blocking securely nailed between framing members.
9.23.16.7. Thickness or Rating
1) Intent StatementThe thickness or rating of roof sheathing on a flat roof used as a walking deck shall conform to either Table 9.23.15.5.A or Table 9.23.15.5.B for subfloors.
2) Intent StatementThe thickness or rating of roof sheathing on a roof not used as a walking deck shall conform to either Table 9.23.16.7.A or Table 9.23.16.7.B
3) Asphalt-coated or asphalt-impregnated fibreboard not less than 11.1 mm thick conforming to change beginCAN/ULC-S706, “Wood Fibre Insulating Boards for Buildings,”change end is permitted to be used as a roof sheathing over supports spaced not more than 400 mm o.c. provided the roofing consists of
a) a continuous sheet of galvanized steel not less than 0.33 mm in thickness, or
b) a continuous sheet of aluminum not less than 0.61 mm in thickness.

contentHistory

4) Intent StatementAll edges of sheathing described in Sentence (3) shall be supported by blocking or framing.
Table 9.23.16.7.A
Thickness of Roof Sheathing
Forming part of Sentence 9.23.16.7.(2)

Maximum Spacing of Supports, mm

Minimum Thickness, mm

Plywood, and OSB, O-2 Grade OSB, O-1 Grade, and Waferboard, R-1 Grade Lumber
Edges Supported Edges Unsupported Edges Supported Edges Unsupported

300

7.5

7.5

9.5

9.5

17.0

400

7.5

9.5

9.5

11.1

17.0

600

9.5

12.5

11.1

12.7

19.0

contentHistory

Table 9.23.16.7.B
Rating for Roof Sheathing When Applying CAN/CSA-O325
Forming part of Sentence 9.23.16.7.(2)

Maximum Spacing of Supports, mm (in.)

Panel Mark
Edges Supported Edges Unsupported

400 (16)

2R16 1R16

500 (20)

2R20 1R20

600 (24)

2R24 1R24

9.23.17. Wall Sheathing

9.23.17.1. Required Sheathing
1) Intent StatementExterior walls and gable ends shall be sheathed when the exterior cladding requires intermediate fastening between supports or if the exterior cladding requires solid backing.
9.23.17.2. Thickness, Rating and Material Standards
1) Intent StatementWhere wall sheathing is required change beginfor the purpose of complying with this Section,change end it shall conform to either Table 9.23.17.2.A or B. change begin(See also Article 9.25.5.1.)change end
Table 9.23.17.2.A
Wall Sheathing Thickness and Specifications
Forming part of Sentence 9.23.17.2.(1)
Type of Sheathing

Minimum Thickness, mm(1)

Material Standards

With Supports
400 mm o.c.

With Supports
600 mm o.c.

Fibreboard (insulating) 9.5 11.1

CAN/ULC-S706

Gypsum sheathing 9.5 12.7

CAN/CSA-A82.27-M
ASTM C 1177/C 1177M
ASTM C 1396/C 1396M

Lumber 17.0 17.0

See Table 9.3.2.1.

Mineral Fibre, Rigid Board, Type 2 25 25

CAN/ULC-S702

OSB, O-2 Grade 6.0 7.5

CSA O437.0

OSB, O-1 Grade, and Waferboard, R-1 Grade 6.35 7.9

CSA O437.0

Phenolic, faced 25 25

CAN/CGSB-51.25-M

Plywood (exterior type) 6.0 7.5

CSA O121
CSA O151
CSA O153-M

Polystyrene, Types 1 and 2 38 38

CAN/ULC-S701

Polystyrene, Types 3 and 4 25 25

CAN/ULC-S701

Polyurethane and Polyisocyanurate Type 1, faced

38 38

CAN/ULC-S704

Polyurethane and Polyisocyanurate Types 2 and 3, faced

25 25

CAN/ULC-S704

Notes to Table 9.23.17.2.A:

(1) See also Sentences 9.27.5.1.(2) to (4).
Table 9.23.17.2.B
Rating for Wall Sheathing when Applying CAN/CSA-O325
Forming part of Sentence 9.23.17.2.(1)
Maximum Spacing of Supports, mm Panel Mark
400 W16
500 W20
600 W24
9.23.17.3. Attachment of Cladding to Sheathing
1) Intent StatementGypsum sheathing, rigid insulation and fibreboard shall not be used for the attachment of cladding materials.
9.23.17.4. Lumber Sheathing
1) Intent StatementLumber wall sheathing shall be applied so that all ends are supported.
2) Intent StatementWhere lumber wall sheathing is required to provide bracing according to Article 9.23.10.2., it shall be applied with end joints staggered.
9.23.17.5. Joints in Panel-Type Sheathing
1) Intent StatementA gap of not less than 2 mm shall be left between sheets of plywood, OSB, waferboard or fibreboard.
9.23.17.6. Mansard Style Roofs
1) Intent StatementWhere the bottom portions of mansard style roofs are vented, the vertical framing members behind the sloping portions shall be considered on the same basis as exterior wall studs and shall conform to Articles 9.27.3.2. to 9.27.3.6.