Division B
Acceptable Solutions
Part 3 — Fire Protection, Occupant Safety and Accessibility
Section 3.1. General
(See Appendix A.)3.1.1. Scope and Definitions
3.1.1.1. Scope
The scope of this Part shall be as described in Subsection 1.3.3. of Division A.
3.1.1.2. Defined Words
Words that appear in italics are defined in Article 1.4.1.2. of Division A. 3.1.1.3.
Use of Term Storage Tank

3.1.1.4. Fire Protection Information
Information to be submitted regarding major components of fire protection shall conform to the requirements of Subsection 2.2.3. of Division C.
3.1.2. Classification of Buildings or Parts of Buildings by Major Occupancy
(See Appendix A.)3.1.2.1. Classification of Buildings

A building intended for use by more than one major occupancy shall be classified according to all major occupancies for which it is used or intended to be used.
| Table 3.1.2.1. Major Occupancy Classification Forming part of Sentences 3.1.2.1.(1) and 3.1.2.2.(1) | ||
| Group | Division |
Description of Major Occupancies |
| A | 1 | Assembly occupancies intended for the production and viewing of the performing arts |
| A | 2 | Assembly occupancies not elsewhere classified in Group A |
| A | 3 | Assembly occupancies of the arena type |
| A | 4 | Assembly occupancies in which occupants are gathered in the open air |
| B | 1 | Detention occupancies![]() |
| B | 2 | Treatment occupancies![]() |
|
|
|
Care occupancies![]() |
| C | — | Residential occupancies |
| D | — | Business and personal services occupancies |
| E | — | Mercantile occupancies |
| F | 1 | High-hazard industrial occupancies |
| F | 2 | Medium-hazard industrial occupancies |
| F | 3 | Low-hazard industrial occupancies |
3.1.2.2. Occupancies of Same Classification
Any building is deemed to be occupied by a single major occupancy, notwithstanding its use for more than one major occupancy, provided that all occupancies are classified as belonging to the same Group classification or, where the Group
is divided into Divisions, as belonging to the same Division classification
described in Table 3.1.2.1.3.1.2.3. Arena-Type Buildings
An arena-type building intended for occasional use for trade shows and similar exhibition purposes shall
be classified as a Group A, Division 3 occupancy. (See Appendix A.)3.1.2.4. Police Stations
A police station with detention quarters is permitted to be classified as a Group B, Division 2 major occupancy provided the station is not more than 1 storey in building height and 600 m2 in building area. 3.1.2.5.
Care Facilities
Convalescent homes and children’s custodial homes permitted to be classified as residential occupancies
within the application of Part 3
, provided that occupants are ambulatory and live as a single housekeeping unit in a
suite
with sleeping accommodation for not more than 10 persons.
, a community care facility or a group residence,
is permitted to be classified as a residential occupancy, provided
occupants live as a single housekeeping unit in a dwelling unit
with sleeping accommodation for not more than 10 persons,
A child care facility shall be classified as either a Group C or Group A Division 2 major occupancy as determined by Table 3.1.2.5. provided| Table 3.1.2.5. Table 3.1.2.5. Major Occupancy Classification and Fire Safety Requirements for Child Care Facilities Forming part of Sentence 3.1.2.5.(3) |
|||||||
| Major Occupancy Determination | Fire Safety Requirements for Major Occupancy | ||||||
| Age of Children(6) (months) | Number of Children(6) | Major Occupancy Permitted | Sprinkler (suite or entire building) | Fire Alarm | Smoke and CO Detectors Alarms | Fire Separation from Remainder of Building | Emergency Lighting |
| ≥ 30 | ≤ 8 and more than 2 | C(1) | No | No | Yes | No | Yes(2) |
| < 30 | ≤ 8 and more than 2 | C(1) | Yes(5) | No | Yes(3) | No | Yes(2) |
| ≥ 30 | ≤ 8 and more than 2 | C(4) | Yes(5) | Yes | Yes(3) | 1 h | Yes |
| < 30 | ≤ 8 and more than 2 | C(4) | Yes(5) | Yes | Yes(3) | 2 h | Yes |
| ≥ 30 | > 8 | A2 | Yes | Yes | Yes(3) | 1 h | Yes |
| < 30 | > 8 | A2 | Yes | Yes | Yes(3) | 2 h | Yes![]() |
| Notes to Table 3.1.2.5.: | |
|
|
|
| (1) | Applies to one and two family dwellings or row houses |
| (2) | Emergency lighting to conform to Subsections 3.2.7. and 9.9.12. where applicable |
| (3) | Coverage to include all areas within the suite, except closets and kitchens |
| (4) | Applies to buildings other than one or two family dwellings or row houses |
| (5) | Suite only |
| (6) | Children means persons under the age of 13 years. |

3.1.2.6. Group A, Division 2, Low Occupant Load
, and 
3.1.2.7.
Storage of Combustible Fibres

3.1.2.8. Daycare Facilities for Children
(See Appendix A.)
3.1.2.9.
Retail Food Facility

3.1.3. Multiple Occupancy Requirements
3.1.3.1. Separation of Major Occupancies
Except as permitted by Sentences (2) and (3), major occupancies shall be separated from adjoining major occupancies by fire separations having fire-resistance ratings conforming to Table 3.1.3.1.
In a building not more than 3 storeys in building height, if not more than 2 dwelling units are contained together with a Group E major occupancy, the fire-resistance rating of the fire separation between the 2 major occupancies need not be more than 1 h.
In a building conforming to the requirements of Articles 3.2.8.2. to 3.2.8.9., the requirements of Sentence (1) for fire separations between major occupancies do not apply at the vertical plane around the perimeter of an opening through the horizontal fire separation. (see Appendix A.)| Table 3.1.3.1. Major Occupancy Fire Separations(1) Forming part of Sentence 3.1.3.1.(1) | |||||||||||||
|
Minimum Fire-Resistance Rating of Fire Separation, h |
|||||||||||||
|
Adjoining Major Occupancy | |||||||||||||
| A-1 | A-2 | A-3 | A-4 | B-1 | B-2 |
![]() | C (5)![]() | D | E | F-1 | F-2 | F-3 | |
| A-1 | — | 1 | 1 | 1 | 2 | 2 |
|
1 | 1 | 2 | 2 | 1 | |
| A-2 | 1 | — | 1 | 1 | 2 | 2 |
|
1 | 1 | 2 | 2 | 1 | |
| A-3 | 1 | 1 | — | 1 | 2 | 2 |
|
1 | 1 | 2 | 2 | 1 | |
| A-4 | 1 | 1 | 1 | — | 2 | 2 |
|
1 | 1 | 2 | 2 | 1 | |
| B-1 | 2 | 2 | 2 | 2 | — | 2 |
|
2 | 2 | 2 | 2 | 2 | |
| B-2 | 2 | 2 | 2 | 2 | 2 | — |
|
2 | 2 | 2 | 2 | 2 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C (5)![]() | 1 | 1 | 1 | 1 | 2 | 2 |
|
— | 1 |
2(3) |
2(4) |
1 | |
| D | 1 | 1 | 1 | 1 | 2 | 2 |
|
1 | — | — | 3 | — | — |
| E | 2 | 2 | 2 | 2 | 2 | 2 |
|
2(3) |
— | — | 3 | — | — |
| F-1 | 3 | 3 | — | 2 | 2 | ||||||||
| F-2 | 2 | 2 | 2 | 2 | 2 | 2 |
|
2(4) |
— | — | 2 | — | — |
| F-3 | 1 | 1 | 1 | 1 | 2 | 2 |
|
1 | — | — | 2 | — | —![]() |
| Notes to Table 3.1.3.1.: | |
|
|
|
| (1) | Section 3.3. contains requirements for the separation of occupancies and tenancies that are in addition to the requirements for the separation of major occupancies. |
| (2) | See Sentence 3.1.3.2.(1). |
| (3) | See Sentence 3.1.3.1.(2). |
| (4) | See Sentence 3.1.3.2.(2). |
| (5) | See Article 3.2.1.7.![]() |

3.1.3.2. Prohibition of Occupancy Combinations
No major occupancy of Group F, Division 1 shall be contained within a building with any occupancy classified as Group A, B or C.
Except as provided in Article 3.1.3.4. and Subsection 11.4.5.,
not more than one suite of residential occupancy shall be contained within a building classified as a Group F, Division 2 major occupancy. 
3.1.3.3.
Artist Live/Work - Class A Artist Studio
3.1.3.4. Artist Live/Work - Class B Artist Studio
3.1.3.5. Training School
3.1.3.6. Industrial Flex Space

3.1.4. Combustible Construction
3.1.4.1. Combustible Materials Permitted
A building permitted to be of combustible construction is permitted to be constructed of combustible materials, with or without noncombustible components.
The flame-spread rating on any exposed surface of foamed plastic insulation, and on any surface that
would be exposed by cutting through the insulation in any direction,
shall be not more than 500.
3.1.4.2. Protection of Foamed Plastics
Foamed plastics that form part of a wall or ceiling assembly in combustible construction shall be protected from adjacent spaces in the building, other than adjacent concealed spaces within attic or roof spaces, crawl spaces, and wall assemblies,3.1.4.3. Wires and Cables
Except as required by Sentence (2),
optical fibre cables and electrical wires and cables
with combustible insulation, jackets or sheathes that are
installed in a building permitted to be of combustible construction shall
(FT1 rating),
except as required by Subclause 3.6.4.3.(1)(a)(ii) or

Except as permitted in Sentence (3)
and Article 3.6.4.3.
, optical fibre cables and electrical wires and cables with combustible insulation, jackets or sheathes that are used for the transmission of voice, sound or data and are installed in a plenum in a building permitted to be of combustible construction shall exhibit a vertical char of not more than 1.5 m when tested in conformance with the Vertical Flame Test - Cables in Cable Trays in Clause 4.11.4 of CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables,” (FT4 rating).

Cables or wires within plenum spaces that are used for the transmission of signals in fire alarm, security,
radio, and television broadcasting, closed circuit television or community
television systems need not comply with the requirements of Sentence (2).
3.1.4.4.
Non-metallic Raceways
Totally enclosed non-metallic raceways used in a plenum in a building permitted to be of combustible construction shall meet the requirements of Clause 3.1.5.20.(1)(a).
3.1.4.5. Fire-Retardant-Treated Wood
If fire-retardant-treated wood is specified in this Part, the wood shall3.1.4.6. Heavy Timber Construction Alternative
If combustible construction is permitted and is not required to have a fire-resistance rating more than 45 min, heavy timber construction is permitted to be used. 3.1.4.7. Heavy Timber Construction
Wood elements in heavy timber construction shall be arranged in heavy solid masses and with essentially smooth flat surfaces to avoid thin sections and sharp projections.
Except as permitted by Sentences (3) to (6) and (12), the minimum dimensions of wood elements in heavy timber construction shall conform to Table 3.1.4.7.| Table 3.1.4.7. Heavy Timber Dimensions Forming part of Sentence 3.1.4.7.(2) | ||||
| Supported Assembly | Structural Element | Solid Sawn (width x depth), mm x mm |
Glued-Laminated (width x depth), mm x mm |
Round (diam), mm |
| Roofs only | Columns | 140 x 191 | 130 x 190 | 180 |
| Arches supported on the tops of walls or abutments | 89 x 140 | 80 x 152 | — | |
| Beams, girders and trusses | 89 x 140 | 80 x 152 | — | |
| Arches supported at or near the floor line | 140 x 140 | 130 x 152 | — | |
| Floors, floors plus roofs |
Columns | 191 x 191 | 175 x 190 | 200 |
| Beams, girders, trusses and arches | 140 x 241 or | 130 x 228 or | — | |
| 191 x 191 | 175 x 190 | |||
Where splice plates are used at splices of roof arches supported on the tops of walls or abutments, roof trusses, roof beams and roof
girders in heavy timber construction, they shall be not less than 64 mm thick.
Floors in heavy timber construction shall be of glued-laminated or solid sawn plank not less than
Floors in heavy timber construction shall be laid
Roofs in heavy timber construction shall be of tongued and grooved phenolic-bonded plywood not less than 28 mm thick, or glued-laminated or solid sawn plank
that is
Wood columns in heavy timber construction shall be continuous or superimposed throughout all storeys.
Superimposed wood columns in heavy timber construction shall be connected by
Where beams and girders in heavy timber construction enter masonry, wall plates, boxes of the self-releasing
type or hangers shall be used.
Wood girders and beams in heavy timber construction shall be closely fitted to columns, and adjoining
ends shall be connected by ties or caps to transfer horizontal loads
across the joints.
In heavy timber construction, intermediate wood beams used to support a floor shall be supported
on top of the girders or on metal hangers into which the ends of the
beams are closely fitted.
Roof arches supported on the top of walls or abutments, roof trusses, roof beams and roof girders in heavy timber construction are permitted to be not less than 64 mm
wide provided3.1.5. Noncombustible Construction
3.1.5.1. Noncombustible Materials
Except as permitted by Sentences (2) to (4) and Articles 3.1.5.2. to 3.1.5.21., 3.1.13.4. and 3.2.2.16., a building or part of a building required to be of noncombustible construction shall be constructed with noncombustible materials. (See also Subsection 3.1.13. for the requirements
regarding the flame-spread rating of interior finishes.)
Notwithstanding the definition of noncombustible materials stated in Article 1.4.1.2. of Division A, a material is permitted to be used in noncombustible construction provided that, when tested in accordance with ULC-S135, “Test Method for the Determination of Combustibility Parameters of Building Materials Using an Oxygen Consumption Calorimeter (Cone Calorimeter),” at a heat flux of 50
kW/m2,
If a material referred to in Sentence (2) consists of a number of discrete layers and testing reveals that the surface layer or layers protect the underlying layers such that
complete combustion of the underlying layers does not occur, the test
shall be repeated by removing the outer layers sequentially until
all layers have been exposed during testing, or until complete combustion
has occurred.
The acceptance criteria for a material tested in accordance with Sentence (3) shall be based on the cumulative emissions from all layers, which must not exceed the criteria
stated in Clauses (2)(a) and (b). 3.1.5.2. Minor Combustible Components
The following minor combustible components are permitted in a building required to be of noncombustible construction:3.1.5.3. Combustible Roofing Materials
Combustible roof covering that has an A, B, or C classification determined in conformance with Subsection 3.1.15. is permitted on a building required to be of noncombustible construction.
Combustible roof sheathing and roof sheathing supports installed above a concrete deck are permitted on a building required to be of noncombustible construction provided
fire blocks
in conformance with Article 3.1.11.5.,
Combustible cant strips, roof curbs, nailing strips and similar components used in the installation of
roofing are permitted on a building required to be of noncombustible construction.
Wood nailer facings to parapets, not more than 600 mm high, are permitted on a building required to be of noncombustible construction, if the facings and any roof membranes covering the facings are protected by sheet metal.
3.1.5.4. Combustible Glazing and Skylights
per cent
of the area of the ceiling of the room or space in which they are located, and
per cent
of the area of the ceiling of the room or space in which they are located, and
Combustible vertical glazing installed no higher than the second storey is permitted in a building required to be of noncombustible construction.
Except as permitted by Sentence (4), the combustible vertical glazing permitted by Sentence (2) shall have a flame-spread rating not more than 75.
per cent
of the wall area of the storey in which it is located, and
per cent
of the area of the wall face.

3.1.5.5. Combustible
Cladding Systems
for Exterior Walls
Except
as required in Sentence (2)
, an exterior non-loadbearing wall assembly that includes a combustible cladding system is permitted to be used in a building required to be of noncombustible construction provided
Except as permitted by Articles 3.2.3.10. and 3.2.3.11., where the limiting distance in Tables 3.2.3.1.B to E permits an area of unprotected openings of not more than 10
per cent
of the exposing building face, the construction requirements of Table 3.2.3.7. shall be met.
Flaming on or in the wall assembly shall not spread more than 5 m above the opening during or following the test procedure referenced in Sentence (1). (See Appendix A.)
The heat flux during the flame exposure on a wall assembly shall be not more than 35 kW/m2 measured 3.5 m above the
opening during the test procedure referenced in Sentence (1). (See Appendix A.)
A wall assembly permitted by Sentence (1) that includes combustible cladding of fire-retardant-treated wood shall be tested for fire exposure after the cladding has been subjected to an accelerated weathering test
as specified in ASTM D 2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing.”

3.1.5.6. Nailing Elements
Wood nailing elements attached directly to or set into a continuous noncombustible backing for the attachment of interior finishes are permitted in a building required to be of noncombustible construction provided the concealed space created by the wood elements is not more than 50 mm thick.
3.1.5.7. Combustible Millwork
Combustible millwork, including interior trim, doors and door frames, show windows together with their
frames, aprons and backing, handrails, shelves, cabinets and counters,
is permitted in a building required to be of noncombustible construction. 3.1.5.8. Combustible Flooring Elements
Combustible stage flooring supported on noncombustible structural members is permitted in a building required to be of noncombustible construction.
created are divided into compartments by fire blocks
in conformance with Sentence 3.1.11.3.(2). 
The floor system for the raised platform referred to in Sentence (2) is permitted to include a combustible subfloor and combustible finished flooring.
Combustible finished flooring is permitted in a building required to be of noncombustible construction. 3.1.5.9. Combustible Stairs in Dwelling Units
Combustible stairs are permitted in a dwelling unit in a building required to be of noncombustible construction.
3.1.5.10. Combustible Interior Finishes
Combustible interior finishes, including paint, wallpaper, and other interior finishes not more than 1 mm thick, are permitted in a building required to be of noncombustible construction.
Combustible interior wall finishes, other than foamed plastics, are permitted in a building required to be of noncombustible construction provided they
per cent
of the ceiling area within each fire compartment is permitted to have a flame-spread rating not more than 150.

3.1.5.11. Gypsum Board
Gypsum board with a tightly adhering paper covering not more than 1 mm thick is permitted in a building required to be of noncombustible construction provided the flame-spread rating on the surface is not more than 25.
3.1.5.12. Combustible Insulation and its Protection
Combustible insulation, other than foamed plastics, is permitted in a building required to be of noncombustible construction provided that it has a flame-spread rating not more than 25 on any exposed surface, or any surface that would be exposed by cutting through the material in any direction, where
the insulation is not protected as described in Sentences (3) and (4).
Foamed plastic insulation having a flame-spread rating not more than 25 on any exposed surface, or any surface
that would be exposed by cutting through the material in any direction,
is permitted in a building required to be of noncombustible construction provided the insulation is protected from adjacent space in the building, other than adjacent concealed spaces within wall assemblies, by a thermal barrier consisting of
Combustible insulation having a flame-spread rating more than 25 but not more than 500 on an exposed surface, or any surface that would be exposed
by cutting through the material in any direction, is permitted in
the exterior walls of a building required to be of noncombustible construction, provided the insulation is protected from adjacent space in the building, other than adjacent concealed spaces within wall assemblies, by a thermal barrier as described in Sentence (2), except that in a building that is not sprinklered throughout and is more than 18 m high, measured between grade and the floor level of the top storey, the insulation shall be protected by a thermal barrier consisting of
Combustible insulation having a flame-spread rating more than 25 but not more than 500 on any exposed surface, or any surface that would be
exposed by cutting through the material in any direction, is permitted
in the interior walls, within ceilings and within roof assemblies
of a building required to be of noncombustible construction, provided the insulation is protected from adjacent space in the building, other than adjacent concealed spaces within wall assemblies, by a thermal barrier as described in Sentence (2), except that in a building that is not sprinklered throughout and is more than 18 m high, measured between grade and the floor level of the top storey, the insulation shall be protected by a thermal barrier consisting of
Combustible insulation, including foamed plastics, installed above roof decks, outside of foundation walls below ground level and beneath concrete slabs-on-ground is permitted to be used in a building required to be of noncombustible construction.
Thermosetting foamed plastic insulation having a flame-spread rating not more than 500 that forms part of a factory-assembled exterior wall panel that does not
incorporate an air space is permitted to be used in a building required to be of noncombustible construction provided
Except as provided in Sentence 3.1.5.12.(8),
a factory-assembled non-loadbearing interior or exterior wall or ceiling panel containing foamed plastic insulation having a flame-spread rating of not more than 500 is permitted to be used in a building required to be of noncombustible construction provided
3.1.5.13. Combustible Elements in Partitions
Except as permitted by Sentence (2), solid lumber partitions not less than 38 mm thick and wood framing in partitions located in a fire compartment not more than 600 m2 in area are permitted
to be used in a building required to be of noncombustible construction in a floor area that is not sprinklered throughout provided the partitions
Partitions installed in a building of noncombustible construction are permitted to contain wood framing provided
Solid lumber partitions not less than 38 mm thick and partitions that contain wood framing are permitted to be used in a building required to be of noncombustible construction provided3.1.5.14. Storage Lockers in Residential Buildings
Storage lockers in storage rooms are permitted to be constructed of wood in a building of residential occupancy required to be of noncombustible construction. 3.1.5.15. Combustible Ducts
Except as required by Sentence 3.6.4.3.(1), combustible ducts, including plenums and duct connectors, are permitted to be used in a building required to be of noncombustible construction provided these ducts and duct connectors are used only in horizontal runs.
Combustible duct linings, duct coverings, duct insulation, vibration isolation connectors, duct tape,
pipe insulation and pipe coverings are permitted to be used in a building required to be of noncombustible construction provided they conform to the appropriate requirements of Subsection 3.6.5.
In a building required to be of noncombustible construction, combustible ducts need not comply with the requirements of Sentences 3.6.5.1.(1) and (2) provided the ducts are3.1.5.16. Combustible Piping Materials
Except as permitted by Clause 3.1.5.2.(1)(d) and Sentences (2) and (3), combustible piping and tubing and associated adhesives are permitted to be used in a building required to be of noncombustible construction provided that, except when concealed in a wall or concrete floor slab, they
Combustible sprinkler piping is permitted to be used within a sprinklered floor area in a building required to be of noncombustible construction. (See also Article 3.2.5.13.)
Polypropylene pipes and fittings are permitted to be used for drain, waste and vent piping for the conveyance of highly corrosive
materials and for piping used to distribute distilled or dialyzed
water in laboratory and hospital facilities in a building required to be of noncombustible construction, provided
with a pressure differential of 50 Pa between the exposed and unexposed sides, with the higher pressure on the exposed side.
3.1.5.17. Combustible Plumbing Fixtures
Combustible plumbing fixtures, including wall and ceiling enclosures that form part of the plumbing fixture,
are permitted in a building required to be of noncombustible construction provided they are constructed of material having a flame-spread rating and smoke developed classification not more than that
permitted for the wall surface of the room or space in which they
are installed.
3.1.5.18. Wires and Cables
Except as permitted by
Sentences (2) and (3) and
Article 3.1.5.19., optical fibre cables and electrical wires and cables with combustible insulation, jackets or sheathes are permitted in a building required to be of noncombustible construction, provided
(FT4 rating),
Clause 3.1.5.20.(1)(b)
, or
Except as permitted in Sentences (3) and (4), optical fibre cables and electrical wires and cables with combustible insulation, jackets or sheathes that are used for the transmission of voice, sound or data and
are not located in totally enclosed noncombustible raceways are permitted to be installed in a plenum in a building required to be of noncombustible construction, provided the wires and cables exhibit a horizontal flame distance of not more than 1.5 m, an average optical
smoke density of not more than 0.15, and a peak optical smoke density of not more
than 0.5 when tested in conformance with CAN/ULC-S102.4, “Standard Method of Test for Fire and Smoke Characteristics of Electrical Wiring, Cables and Non-Metallic Raceways,” (FT6 rating).

Except as permitted in Sentence (4), where totally enclosed noncombustible raceways are used in a plenum, exposed components of wiring systems with combustible insulation, jackets or sheathes, including optical fibre cables and electrical wires and cables that are used for the transmission
of voice, sound or data, that are installed in a plenum or that extend from the plenum not more than 9 m in length including drop down to the floor level, are permitted provided they exhibit a vertical char of not more than
1.5 m when tested in conformance with the Vertical Flame Test – Cables
in Cabletrough in Clause 4.11.4 of CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables,” (FT4 rating).
Cables or wires within plenum spaces that are used for the transmission of signals in fire alarm, security,
radio, and television broadcasting, closed circuit television or community
television systems need not comply with the requirements of Sentences (2) and (3).
3.1.5.19. Combustible Travelling Cables for Elevators
Combustible travelling cables are permitted on elevating devices in a building required to be of noncombustible construction. 3.1.5.20. Non-metallic Raceways

Except as required in Sentence (2),
subject to the limits on the size of elements that penetrate fire separations as stated in Sentence 3.1.9.3.(2), within a fire compartment of a building required to be of noncombustible construction, totally enclosed non-metallic raceways not more
than 175 mm in outside diameter, or of an equivalent
rectangular area, are permitted to be used to enclose optical fibre
cables and electrical wires and cables, provided
where the wires and cables in the raceways meet or exceed the requirements of Clause 3.1.5.18.(1)(a), the non-metallic raceways meet the requirements for at least an FT4 rating in
where the wires and cables in the raceways do not meet or exceed the requirements of Clause 3.1.5.18.(1)(a), the non-metallic
raceways exhibit a vertical char of not more than 1.5 m when tested in conformance with
the Vertical Flame Test (FT4) – Conduit or Tubing on Cable Tray in
Clause 6.16 of CSA C22.2 No. 211.0, “General Requirements and Methods of Testing for Nonmetallic Conduit.”
Totally enclosed non-metallic raceways used in a plenum in a building required to be of noncombustible construction shall exhibit a horizontal flame distance of not more than 1.5 m, an average optical smoke density of not more than
0.15, and a peak optical smoke density of not more than 0.5 when tested in
conformance with
CAN/ULC-S102.4, “Standard Method of Test for Fire and Smoke Characteristics of Electrical Wiring, Cables and Non-Metallic Raceways,”
(FT6 rating).

3.1.5.21. Decorative Wood Cladding
CAN/ULC-S102, “Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies.”

3.1.6. Tents and Air-Supported Structures
(See Appendix A.)3.1.6.1. Means of Egress
3.1.6.2. Restrictions
An air-supported structure shall not be used for Groups B, C, or Group F, Division 1 major occupancies or for classrooms. 
3.1.6.3. Clearance to Other Structures
Except as permitted by Sentences (2), (3) and (4), every tent and air-supported structure shall conform to Subsection 3.2.3.
Tents and air-supported structures
Tents and air-supported structures not occupied by the public
Tents not more than 120 m2 in ground area, located on fair grounds or similar open spaces, need not be
separated from one another provided this does not create a hazard
to the public.
3.1.6.4. Clearance to Flammable Material
The ground enclosed by a tent or air-supported structure and not less than 3 m of ground outside
the structure shall be cleared of all flammable material or vegetation
that will spread fire.
3.1.6.5. Flame Resistance
Every tent and air-supported structure and all tarpaulins and decorative materials used in connection with these structures shall conform to CAN/ULC-S109, “Flame Tests of Flame-Resistant Fabrics and Films.”3.1.6.6. Emergency Air Supply
An air-supported structure used as a place of assembly for more than 200 persons shall have either3.1.6.7.
Electrical Systems
The electrical system and equipment in a tent or air-supported structure, including electrical fuses and switches, shall be inaccessible to the public.
Cables on the ground in areas used by the public in a tent or air-supported structure shall be placed in trenches or protected by covers to prevent damage from traffic.
3.1.7. Fire-Resistance Ratings
3.1.7.1. Determination of Ratings
Except as permitted by Sentence (2) and Article 3.1.7.2., the rating of a material, assembly of materials or a structural member that is required to have a fire-resistance rating, shall be determined on the basis of the results of tests conducted in conformance with CAN/ULC-S101, “Fire Endurance Tests of Building Construction and Materials.”
A material, assembly of materials or a structural member is permitted to be assigned a fire-resistance rating on the basis of Appendix D.
A ceiling assembly is permitted to be assigned a fire-resistance rating on the basis of Assembly Number Rl in Table A-9.10.3.1.B.
A ceiling membrane is permitted to be assigned a fire-resistance rating on the basis of Assembly Number Ml or M2 in Table A-9.10.3.1.B.
3.1.7.2. Exception for Exterior Walls
The limit on the rise of temperature on the unexposed surface of an assembly as required by the tests referred to in Sentence 3.1.7.1.(1) shall not apply to an exterior wall that has a limiting distance of 1.2 m or more, provided correction is made for radiation from the unexposed surface in accordance with Sentence 3.2.3.1.(9). 3.1.7.3. Exposure Conditions for Rating
Firewalls and interior vertical fire separations shall be rated for exposure to fire on each side.
Exterior walls shall be rated for exposure to fire from inside the building. 3.1.7.4. Minimum Fire-Resistance Rating
The use of materials or assemblies having a greater fire-resistance rating than required shall impose no obligation to exceed in whole or in part the minimum fire-resistance ratings required by this Part. 3.1.7.5. Rating of Supporting Construction

Loadbearing walls, columns and arches supporting a service room or service space need not conform to Sentence (1).
If an assembly is required to be of noncombustible construction and have a fire-resistance rating, it shall be supported by noncombustible construction.
3.1.8. Fire Separations and Closures
3.1.8.1. General Requirements
Any wall, partition or floor assembly required to be a fire separation shall
Openings in a fire separation shall be protected with closures, shafts or other means in conformance with Articles 3.1.8.4. to 3.1.8.17. and Subsections 3.1.9. and 3.2.8. (See Appendix A.) 3.1.8.2. Combustible Construction Support
Combustible construction that abuts on or is supported by a noncombustible fire separation shall be constructed so that its collapse under fire conditions will not cause the collapse
of the fire separation. 3.1.8.3. Continuity of Fire Separations
Except as permitted by Sentence 3.6.4.2.(2), a horizontal service space or other concealed space located above a required vertical fire separation, including the walls of a vertical shaft, shall be divided at the fire separation by an equivalent fire separation within the service space.
The fire separation required by Sentence (1) shall terminate so that smoke-tight joints are provided where it abuts on or intersects
Except as required by Subsection 3.6.3. for a
shaft penetrating a roof assembly, a shaft, including an exit enclosure, that penetrates a fire separation, shall
The continuity of a fire separation shall be maintained where it abuts another fire separation, a floor, a ceiling, a roof, or an exterior wall assembly. (See Appendix A.)3.1.8.4. Determination of Ratings

Except as permitted by Sentence 3.1.8.10.(1), the fire-protection rating of a closure shall conform to Table 3.1.8.4. for the required fire-resistance rating of the fire separation. | Table 3.1.8.4. Fire-Protection Rating of Closures Forming part of Sentences 3.1.8.4.(2) and 3.1.9.1.(1) | |
|
Minimum Fire-Protection Rating of Closure | |
| 45 min | 45 min |
| 1 h | 45 min |
| 1.5 h | 1 h |
| 2 h | 1.5 h |
| 3 h | 2 h |
| 4 h | 3 h |
3.1.8.5. Installation of Closures
Except where fire dampers, window assemblies and glass block are used as closures, closures of the same fire-protection rating installed on opposite sides of the same opening are deemed to have a fire-protection rating equal to the sum of the fire-protection ratings of the closures. (See A-3.1.8.1.(2) in Appendix A.)
Except as otherwise specified in this Part, every door, window assembly or glass block used as a closure in a required fire separation shall be installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives.” (See A-3.1.8.1.(2) in Appendix A.)
If a door is installed such that it could damage the integrity of a fire separation if its swing is unrestricted, door stops shall be installed to prevent the damage.

Protective guarding devices shall be
3.1.8.6. Maximum Openings
The size of an opening in an interior fire separation required to be protected with a closure shall be not more than 11 m2, with no dimension more than 3.7 m, if a fire compartment on either side of the fire separation is not sprinklered.
The size of an opening in an interior fire separation required to be protected with a closure shall be not more than 22 m2, with no dimension more than 6 m, provided the fire compartments on both sides of the fire separation are sprinklered. 3.1.8.7. Fire Dampers
Except as permitted by Article 3.1.8.8., a duct that penetrates an assembly required to be a fire separation shall be equipped with a fire damper.
A fire damper required by Sentence (1) shall have a fire-protection rating conforming to Sentence 3.1.8.4.(2). 3.1.8.8. Fire Dampers Waived
Fire dampers need not be provided in noncombustible branch ducts that have a melting point above 760°C and that penetrate a
required fire separation provided the ducts
A duct penetrating a vertical fire separation not required to have a fire-resistance rating need not be equipped with a fire damper at the fire separation.
A noncombustible duct that penetrates a horizontal fire separation not required to have a fire-resistance rating need not be equipped with a fire damper at the fire separation.
A noncombustible duct that penetrates a fire separation that separates a vertical service space from the remainder of the building need not be equipped with a fire damper at the fire separation provided
A continuous noncombustible duct having a melting point above 760°C that penetrates a
vertical fire separation as required by Sentence 3.3.1.1.(1) between suites of other than residential, care, treatment or detention occupancy need not be equipped with a fire damper at the fire separation.
A duct that serves commercial cooking equipment and penetrates a required fire separation need not be equipped with a fire damper at the fire separation. (See also Article 6.2.2.7.) 3.1.8.9. Installation of Fire Dampers
A fire damper shall be arranged so as to close automatically upon the operation of a fusible link
conforming to ULC-S505, “Fusible Links for Fire Protection Service,” or other heat-actuated or smoke-actuated device.
A heat-actuated device referred to in Sentence (1) shall
A fire damper shall be installed in the plane of the fire separation so as to stay in place should the duct become dislodged during a fire.
A fire damper tested in the vertical or horizontal position shall be installed in the position in which
it was tested.
A tightly fitted access door shall be installed for each fire damper to provide access for the inspection of the damper and the resetting of the release device. (See Appendix A.)3.1.8.10. Twenty-Minute Closures
A door assembly having a fire-protection rating not less than 20 min is permitted to be
used as a closure in
The requirements for noncombustible sills and combustible floor coverings in NFPA 80, “Fire Doors and Other Opening Protectives,” do not apply to a
door described in Sentence (1).
A door described in Sentence (1) shall have clearances of not more than 6 mm at the bottom and
not more than 3 mm at the sides and top.
3.1.8.11. Self-closing Devices
Except as permitted by Sentence (2), every door in a fire separation, other than doors to freight elevators and dumbwaiters, shall be equipped
with a self-closing device designed to return the door to the closed
position after each use.
A self-closing device need not be provided on a door that is located between3.1.8.12. Hold-Open Devices
A hold-open device is permitted on a door in a required fire separation, other than an exit
stair
door in a building more than 3 storeys in building height, and on a door for a vestibule required by Article 3.3.5.7., provided the device is designed to release the door in conformance with Sentences (2), (3) and (4). 
CAN/ULC-S524, “Installation of Fire Alarm Systems,”
if used on
care occupancy
,
a treatment occupancy,
a detention occupancy, or

A hold-open device permitted by Sentence (1) shall be designed to release upon a signal from the building fire alarm system if a fire alarm system is provided, except that this requirement does not apply to
treatment occupancy
, or 3.1.8.13. Door Latches
Except as permitted by Article 3.3.3.5., a swing-type door in a fire separation shall be equipped with a positive latching mechanism designed to hold the door in the
closed position after each use.
3.1.8.14. Wired Glass and Glass Block
Except as permitted by Articles 3.1.8.16. and 3.1.8.17. for the separation of exits, an opening in a fire separation having a fire-resistance rating not more than 1 h is permitted to be protected
with fixed wired glass assemblies or glass blocks installed in conformance
with NFPA 80, “Fire Doors and Other Opening Protectives.”
Wired glass assemblies permitted by Sentence (1) and described in Appendix D are permitted to be used as closures in vertical fire separations without being tested in accordance with Sentence 3.1.8.4.(1).
Glass blocks permitted by Sentence (1) shall be installed in accordance with Subsection 4.3.2. and reinforced with steel reinforcement in each horizontal joint.
3.1.8.15. Temperature Rise Limit for Doors
Except as permitted by Article 3.1.8.17., the maximum temperature rise on the opaque portion of the unexposed side of a
door used as a closure in a fire separation in a location shown in Table 3.1.8.15., shall conform to the Table when tested in conformance with Sentence 3.1.8.4.(1). | Table 3.1.8.15. Restrictions on Temperature Rise and Glazing for Closures Forming part of Articles 3.1.8.15. and 3.1.8.16. | ||||
| Location |
Minimum Required Fire-Protection Rating of Door |
Maximum Temperature Rise on Opaque Portion of Unexposed Side of Door, °C |
Maximum Area of Wired Glass in Door, m2 |
Maximum Aggregate Area of Glass Block and Wired Glass Panels not in a Door, m2 |
|
Between a dead-end corridor and an adjacent occupancy where the corridor provides the only access to exit and is required to have a fire-resistance rating |
Less than 45 min | No limit | No limit | No limit |
| 45 min | 250 after 30 min | 0.0645 | 0.0645 | |
|
Between an exit enclosure and the adjacent floor area in a building not more than 3 storeys in building height |
All ratings | No limit | 0.8 | 0.8 |
|
Between an exit enclosure and the adjacent floor area (except as permitted above) |
45 min | 250 after 30 min | 0.0645 | 0.0645 |
| 1.5 h | 250 after 1 h | 0.0645 | 0.0645 | |
| 2 h | 250 after 1 h | 0.0645 | 0.0645 | |
|
In a firewall |
1.5 h | 250 after 30 min | 0.0645 | 0 |
| 3 h | 250 after 1 h | 0 | 0 | |
3.1.8.16. Area Limits for Wired Glass and Glass Block
Except as permitted by Article 3.1.8.17., the maximum area of wired glass in a door used in the locations shown in Table 3.1.8.15. shall conform to the Table. (See Appendix A.)
Except as permitted by Article 3.1.8.17., the maximum area of glass block and wired glass panels not in a door, used in
the locations shown in Table 3.1.8.15., shall conform to the Table.
3.1.8.17. Temperature Rise and Area Limits Waived
The temperature rise limits and glass area limits required by Articles 3.1.8.15. and 3.1.8.16. are waived for a closure between an exit enclosure and an enclosed vestibule or corridor, provided3.1.9.
Penetrations
in Fire Separations and Fire-Rated Assemblies
(See Appendix A.)3.1.9.1. Fire Stops
and (3), and permitted by Sentences (4) and (5), penetrations of
a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating shall be
tightly fitted (see Appendix A).


Penetrations
of a firewall or a horizontal fire separation that is required to have a fire-resistance rating in conformance with Article 3.2.1.2. shall be sealed at the penetration by a fire stop that, when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems,” has an FT rating not less than the fire-resistance rating for the fire separation. 
Penetrations of a fire separation in conformance with Sentence 3.6.4.2.(2) shall be sealed by a fire stop that, when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems,” has an FT rating not less than the fire-resistance rating for the fire separation of the assembly.
Sprinklers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the fire stop requirements of Sentences (1) to (3), provided the annular space created by the penetration of a fire sprinkler is covered by
a metal escutcheon plate in accordance with NFPA 13, “Installation of Sprinkler Systems.”
Unless specifically designed with a fire stop, fire dampers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the fire stop requirements of Sentences (1) to (3), provided the fire damper is installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives.”
3.1.9.2. Combustibility of Service Penetrations
Except as permitted by Articles 3.1.9.3. and 3.1.9.4., pipes, ducts, electrical outlet boxes, totally enclosed raceways or other similar service equipment
that penetrate an assembly required to have a fire-resistance rating shall be noncombustible, unless the assembly was tested incorporating that service equipment. (See Appendix A.) 3.1.9.3. Penetration by Wires, Cables and Outlet Boxes
Optical fibre cables and electrical wires and cables in totally enclosed noncombustible raceways are permitted to penetrate an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2.
Except as permitted by Sentence (3), totally enclosed non-metallic raceways conforming to Article 3.1.5.20., optical fibre cables, and electrical wires and cables, single or grouped, with combustible insulation, jackets or sheathes that conform to the requirements of Clause 3.1.5.18.(1)(a) and that are not installed in totally enclosed noncombustible raceways are permitted to penetrate an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2., provided the overall diameter of the single or grouped wires or cables, or the raceways is not more than 25
mm.
Single conductor metal sheathed cables with combustible jacketting that are more than 25 mm in overall diameter are permitted to penetrate a fire separation required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2., provided the cables are not grouped
and are spaced a minimum of 300 mm apart
.
Combustible totally enclosed raceways that are embedded in a concrete floor slab are permitted in an assembly
required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2., provided the concrete cover between the raceway and the bottom of the slab is not less than 50 mm.
Combustible outlet boxes are permitted in an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time
of testing as required by Article 3.1.9.2., provided the opening through the membrane into the box is not more than 0.016
m2.
Outlet boxes that penetrate opposite sides of a wall assembly shall be offset where necessary to maintain the integrity of the fire separation. 3.1.9.4. Combustible Piping Penetrations
Combustible sprinkler piping is permitted to penetrate a fire separation provided the fire compartments on each side of the fire separation are sprinklered.
Combustible water distribution piping is permitted to penetrate a fire separation that is required to have a fire-resistance rating without being incorporated in the assembly at the time
of testing as required by Article 3.1.9.2., provided the piping is
protected at the penetration with a fire stop in conformance with Sentence (4).
Except as permitted by Sentences (4) to (5), combustible piping shall not be used in a drain, waste and vent piping system if any part of
that system penetrates
Combustible drain, waste and vent piping is permitted to penetrate a fire separation required to have a fire-resistance rating or a membrane that forms part of an assembly required to have a fire-resistance rating, provided
fire stop
that has an F rating not less than the fire-resistance rating required for the fire separation when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems,” with a pressure differential of 50 Pa between the exposed and unexposed sides, with the higher pressure
on the exposed side, and
Combustible drain, waste and vent piping is permitted on one side of a vertical fire separation provided it is not located in a
vertical service space
. 
Combustible piping for central vacuum systems is permitted to penetrate a fire separation provided the installation conforms to the requirements that apply to combustible drain, waste and vent piping specified in Sentence (4).
3.1.9.5. Openings for Ducts through a Membrane Ceiling
A membrane ceiling forming part of an assembly assigned a fire-resistance rating on the basis of Appendix D
or Sentence 3.1.7.1.(4)
is permitted to be penetrated by openings leading into ducts within the ceiling space, provided
3.1.9.6. Plenums
3.1.10. Firewalls
3.1.10.1. Prevention of Firewall Collapse
Except as permitted by Sentence (2), the connections and supports for structural framing members that are connected to or supported on a firewall and have a fire-resistance rating less than that required for the firewall, shall be designed so that the failure of the framing systems during a fire
will not affect the integrity of the firewall during the fire.
Sentence (1) does not apply to a firewall consisting of two separate wall assemblies each tied to its respective building frame but not to each other, provided each wall assembly is
A firewall is permitted to be supported on the structural frame of a building of noncombustible construction provided the supporting frame has a fire-resistance rating not less than that required for the firewall.
Piping, ducts and totally enclosed noncombustible raceways shall be installed so that their collapse will not cause collapse of the firewall. 3.1.10.2. Rating of Firewalls
A firewall that separates a building or buildings with floor areas containing a Group E or a Group F, Division 1 or 2 major occupancy shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 4 h, except that where the upper portion of a firewall separates floor areas containing other than Group E or Group F, Division 1 or 2 major occupancies, the fire-resistance rating of the upper portion of the firewall is permitted to be not less than 2 h.
A firewall that separates a building or buildings with floor areas containing major occupancies other than Group E or Group F, Division 1 or 2 shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 2 h.
Except as permitted by Sentence (4), the required fire-resistance rating of a firewall, except for closures, shall be provided by masonry or concrete.
A firewall permitted to have a fire-resistance rating not more than 2 h need not be constructed of masonry or concrete, provided3.1.10.3. Continuity of Firewalls
A firewall shall extend from the ground continuously through, or adjacent to, all storeys of a building or buildings so separated, except that a firewall located above a basement storage garage conforming to Article 3.2.1.2. is permitted to commence at the floor assembly immediately above the storage garage. (See also Sentence 3.1.10.1.(3).)
A firewall is permitted to terminate on the underside of a reinforced concrete roof slab, provided3.1.10.4. Parapets
Except as permitted by Sentences (2) and 3.1.10.3.(2), a firewall shall extend above the roof surface to form a parapet not less than
A firewall that separates 2 buildings with roofs at different elevations need not extend above the upper roof surface to form a parapet, provided
the difference in elevation between the roofs is more than 3
m.
3.1.10.5. Maximum Openings
per cent
of the entire length of the firewall. 
3.1.10.6. Exposure Protection for Adjacent Walls
The requirements of Article 3.2.3.14. shall apply to the external walls of 2 buildings that meet at a firewall at an angle less than 135°. 3.1.10.7. Combustible Projections
Combustible material shall not extend across the end of a firewall but is permitted to extend across a roof above a firewall that is terminated in conformance with Sentence 3.1.10.3.(2).
If buildings are separated by a firewall, combustible projections on the exterior of one building, including balconies, platforms, canopies, eave projections and stairs, that extend outward beyond the end of the firewall, shall not be permitted within 2.4 m of combustible projections and window or door openings of the adjacent building. (See also Article 3.2.3.6.)3.1.11. Fire
Blocks
in Concealed Spaces
3.1.11.1. Separation of Concealed Spaces
Concealed spaces in interior wall, ceiling and crawl spaces shall be separated from concealed spaces in exterior walls and attic or roof spaces by
fire blocks
conforming to Article 3.1.11.7.3.1.11.2. Fire Blocks in Wall Assemblies
and Vertical Concealed Spaces

fire blocks
conforming to Article 3.1.11.7. shall be provided to block off concealed spaces within a wall assembly
and concealed vertical spaces forming part of wood-frame buildings up to 6 storeys in building height:

Fire blocks
conforming to Sentence (1) are not required, provided
or concealed vertical space
is filled with insulation,
or concealed vertical space
are noncombustible,
within the
wall
space
or concealed vertical space
, including insulation but not including wiring, piping or similar services,
have a flame-spread rating not more than 25 on any exposed surface, or on any surface that would be exposed by cutting through the
material in any direction, and
fire blocks
are installed so that the vertical distance between them is not more than 10 m, or

3.1.11.3. Fire
Blocks
between Nailing and Supporting Elements
In a building required to be of noncombustible construction, a concealed space in which there is an exposed ceiling finish with a flame-spread rating more than 25 shall be provided with
fire blocks
conforming to Article 3.1.11.7. between wood nailing elements so that the maximum area of the concealed space is not more than 2 m2.
In a building required to be of noncombustible construction,
fire blocks
conforming to Article 3.1.11.7. shall be provided in the concealed spaces created by the wood members permitted by Sentence 3.1.5.8.(2) so that the maximum area of a concealed space is not more than 10 m2. 3.1.11.4. Fire
Blocks
between Vertical and Horizontal Spaces
Fire blocks
conforming to Article 3.1.11.7. shall be provided
3.1.11.5. Fire
Blocks
in Horizontal Concealed Spaces


3.1.11.6. Fire
Blocks
in Crawl Spaces

3.1.11.7. Fire
Block
Materials
Except as permitted by Sentences (2) to (4) and (7), materials used to separate concealed spaces into compartments shall remain in place and prevent the passage of flames for not less
than 15 min when subjected to the standard fire exposure
in CAN/ULC-S101, “Fire Endurance Tests of Building Construction and Materials.”
Gypsum board not less than 12.7 mm thick and sheet steel not less than 0.38 mm thick need not be tested
in conformance with Sentence (1), provided all joints have continuous support.
In a building required to be of noncombustible construction, wood nailing elements described in Article 3.1.5.6. need not be tested in conformance with Sentence (1).
In a building permitted to be of combustible construction, in a combustible roof system permitted by Sentence 3.1.5.3.(2), and in a raised platform permitted by Sentence 3.1.5.8.(2), materials used to separate concealed spaces into compartments are permitted to be
a fire stop
shall be used to seal the penetration.
(See Appendix A.)

In buildings permitted to be of combustible construction, semi-rigid fibre insulation board produced from glass, rock or slag is permitted to
be used to block the vertical space in a double stud wall assembly
formed at the intersection of the floor assembly and the walls, provided
the width of the vertical space does not exceed 25 mm and the insulation board3.1.12. Flame-Spread Rating and Smoke Developed Classification
3.1.12.1. Determination of Ratings
CAN/ULC-S102, “Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies.”

The flame-spread rating and smoke developed classification of a material or assembly shall be determined
on the basis of not less than three tests conducted in conformance
with CAN/ULC-S102.2, “Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies,” if the material
or assembly
A material, assembly, or structural member is permitted to be assigned a flame-spread rating and smoke developed classification on the basis of Appendix D. 3.1.13. Interior Finish
3.1.13.1. Interior Finishes, Furnishings and Decorative Materials
Fire By-law
. 
Interior finish material shall include any material that forms part of the interior surface of a floor, wall, partition or ceiling, including3.1.13.2. Flame-Spread Rating
Except as otherwise required or permitted by this Subsection, the flame-spread rating of interior wall and ceiling finishes, including glazing and skylights, shall
be not more than 150 and shall conform to Table 3.1.13.2.| Table 3.1.13.2. Flame-Spread Ratings Forming part of Sentence 3.1.13.2.(1) | ||
|
Occupancy, Location or Element |
Maximum Flame-Spread Rating for Walls and Ceilings |
|
|
Not Sprinklered | ||
| Group A, Division 1 occupancies, including doors, skylights, glazing and light diffusers and lenses | 150 | 75 |
|
Group B occupancies |
150 | 75 |
| 25 | 25 | |
| Lobbies described in Sentence 3.4.4.2.(2) | 25 | 25 |
| Covered vehicular passageways, except for roof assemblies of heavy timber construction in the passageways | 25 | 25 |
| 25 | 25 | |
| Notes to Table 3.1.13.2.: | |
|
|
|
| (1) | See Articles 3.1.13.8. and 3.1.13.10. |
Except as permitted by Sentence (3), doors, other than those in Group A, Division 1 occupancies, need not conform to Sentence (1) provided they have a flame-spread rating not more than 200. (See Appendix A.)
per cent
of the total wall area and 10
per cent
of the total ceiling area of a wall or ceiling finish that is required by Sentence (1) to have a flame-spread rating less than 150 is permitted to have a flame-spread rating not more than 150, except that up to 25
per cent
of the total wall area of lobbies described in Sentence 3.4.4.2.(2) is permitted to have a flame-spread rating not more than 150. 
Except in the case of Group A, Division 1 occupancies, combustible doors, skylights, glazing and light diffusers and lenses shall not be considered
in the calculation of wall and ceiling areas described in Sentence (4). 3.1.13.3. Bathrooms in Residential Suites
The flame-spread rating of interior wall and ceiling finishes for a bathroom within a suite of residential occupancy shall be not more than 200. 3.1.13.4. Light Diffusers and Lenses

3.1.13.5. Skylights
Individual combustible skylights in a corridor that is required to be separated from the remainder
of the building by a fire separation shall be not more than 1 m2 in area and not less than 1.2 m apart. 3.1.13.6. Corridors
Except as permitted by Sentences (2) and (3), the flame-spread rating shall be not more than 75 for the interior wall finish of
The flame-spread rating limit specified in Sentence (1) does not apply to corridors referred to in Sentence (1) provided the flame-spread rating is not more than
The flame-spread rating limits specified in Sentences (1) and (2) for corridors referred to in Sentence (1) does not apply to a corridor in which the flame-spread rating is not more than 150 provided the building is sprinklered throughout.
The flame-spread rating limits specified in Sentences (1), (2) and (3) apply to occupancies in the corridor as well as to the corridor itself.
Except in a building that is sprinklered throughout, the interior ceiling finish of corridors and occupancies referred to in Sentences (1) and (4) shall have a flame-spread rating not more than 25. 3.1.13.7. High Buildings
Except as permitted by Sentences (2) to (4), the interior wall, ceiling and floor finishes in a building regulated by the provisions of Subsection 3.2.6. shall conform to the flame-spread rating requirements in Articles 3.1.13.2.
and 3.1.13.11.
and to the flame-spread rating and smoke developed classification values in Table 3.1.13.7.| Table 3.1.13.7. Flame-Spread Rating and Smoke Developed Classification in High Buildings Forming part of Sentence 3.1.13.7.(1) | ||||||
| Location or Element |
Maximum Flame-Spread Rating | Maximum Smoke Developed Classification | ||||
| Wall Surface |
Ceiling Surface(1) | Floor Surface | Wall Surface |
Ceiling Surface(1) | Floor Surface | |
| Exit stairways, vestibules to exit stairs and lobbies described in Sentence 3.4.4.2.(2) | 25 | 25 | 25 | 50 | 50 | 50 |
|
Corridors not within suites |
300 | 100 | 50 | 500 | ||
Elevator cars![]() | 75![]() | 75![]() | 300![]() | 450![]() | 450![]() | 450![]() |
Elevator vestibules![]() | 25 | 25 | 300 | 100 | 100 | 300 |
| 25 | 25 | 25 | 50 | 50 | 50 | |
| Other locations and elements | No Limit | 300 | 50 | No Limit | ||
| Notes to Table 3.1.13.7.: | |
|
|
|
| (1) | See Article 3.1.13.4. for lighting elements. |
| (2) | Other requirements of this Part apply. |
Except for a building of Group B major occupancy and elevator cars, the flame-spread rating and smoke developed classification of interior wall, floor and ceiling finishes need not conform to the
values in Table 3.1.13.7., provided the building is sprinklered.
per cent
of the area of the wall or ceiling on which they occur.

per cent
of the area of the wall in which they are located.

3.1.13.8. Noncombustible Construction
In a building required to be of noncombustible construction,3.1.13.9. Underground Walkways
Except for paint, the interior wall and ceiling finishes of an underground walkway shall be of noncombustible materials. 3.1.13.10. Exterior Exit Passageway
per cent
of the total wall area and for up to 10
per cent
of the total ceiling area.

3.1.13.11.
Elevator Cars
The wall and ceiling surfaces of elevator cars shall have a flame-spread rating not more than 75.
The wall, ceiling and floor surfaces of elevator cars shall have a smoke developed classification not more than 450.
3.1.14. Roof Assemblies
3.1.14.1. Fire-Retardant-Treated Wood Roof Systems
If a fire-retardant-treated wood roof system is used to comply with the requirements of Subsection 3.2.2., the roof deck assembly shall meet the conditions
of acceptance of CAN/ULC-S126, “Test for Fire Spread Under Roof-Deck Assemblies.”
Supports for the roof deck assembly referred to in Sentence (1) shall consist of3.1.14.2. Metal Roof Deck Assemblies
Except as permitted by Sentence (2), a metal roof deck assembly shall meet the conditions of acceptance of CAN/ULC-S126, “Test for Fire Spread Under Roof-Deck Assemblies,” if
The requirements of Sentence (1) are waived provided3.1.14.3.
Overhead Skylight Glazing
3.1.14.4. Green Roof Assemblies

3.1.15. Roof Covering
3.1.15.1. Roof Covering Classification
A roof covering classification shall be determined in conformance with CAN/ULC-S107, “Fire Tests of Roof Coverings.”
3.1.15.2. Roof Coverings
Except as permitted by Sentence (2), every roof covering shall have a Class A, B or C classification as determined in accordance with Article 3.1.15.1.
A roof covering is not required to have a Class A, B or C classification for3.1.16. Fabrics
3.1.16.1. Fabric Canopies and Marquees

3.1.17. Occupant Load
3.1.17.1. Occupant Load Determination
The occupant load of a floor area or part of a floor area shall be based on
If a floor area or part thereof has been designed for an occupant load other than that determined from Table 3.1.17.1., a permanent sign indicating that occupant load shall be posted in a conspicuous location.
| Table 3.1.17.1. Occupant Load Forming part of Article 3.1.17.1. | |
|
Type of Use of Floor Area or Part Thereof |
Area per person, m2 |
| Assembly uses | |
| space with fixed seats | |
| space with non-fixed seats | 0.75 |
| stages for theatrical performances | 0.75 |
| space with non-fixed seats and tables | 0.95 |
| standing space | 0.40 |
| stadia and grandstands | 0.60 |
| bowling alleys, pool and billiard rooms | 9.30 |
| classrooms | 1.85 |
| school shops and vocational rooms | 9.30 |
| reading or writing rooms or lounges | 1.85 |
| dining, beverage and cafeteria space | 1.20 |
| laboratories in schools | 4.60 |
|
![]() | 1.40(4) |
|
Exercise rooms with equipment |
4.60(4) |
suites![]() | |
care, treatment and sleeping room areas |
10.00 |
| detention quarters | 11.60 |
| Residential uses | |
| dwelling units | |
| dormitories | 4.60 |
| Business and personal services uses | |
| personal services shops | 4.60 |
| offices | 9.30 |
| Mercantile uses | |
| basements and first storeys | 3.70 |
| second storeys having a principal entrance from a pedestrian thoroughfare or a parking area | 3.70 |
| other storeys | 5.60 |
| Industrial uses | |
| manufacturing or process rooms | 4.60 |
| storage garages | 46.00 |
| storage spaces (warehouse) | 28.00 |
| aircraft hangars | 46.00 |
| Other uses | |
| cleaning and repair goods | 4.60 |
| kitchens | 9.30 |
| storage | 46.00 |
| public corridors intended for occupancies in addition to pedestrian travel |
3.70(3) |
| Notes to Table 3.1.17.1.: | |
|
|
|
| (1) | See Clause 3.1.17.1.(1)(a). |
| (2) | See Clause 3.1.17.1.(1)(b) (apply values for dwelling units to suites of care occupancy ).![]() |
| (3) | See A-3.3. in Appendix A. |
| (4) | See A-3.1.17.1. in Appendix A.![]() |

For the purposes of this Article, mezzanines, tiers and balconies shall be regarded as part of the floor area.
If a room or group of rooms is intended for different occupancies at different times, the value to be used from Table 3.1.17.1. shall be the value which gives the greatest number of persons for the occupancies concerned. 