Division B
Acceptable Solutions
Part 3 — Fire Protection, Occupant Safety and Accessibility
Section 3.2. Building Fire Safety
(See Appendix A.)3.2.1. General
3.2.1.1. Exceptions in Determining Building Height
A roof-top enclosure shall not be considered as a storey in calculating the building height if the roof-top enclosure is

Space under tiers of seats in a building of the arena type shall not be considered as adding to the building height provided the space is used only for dressing rooms, concession stands and similar purposes incidental
to the major occupancy of the building.
per cent
of the horizontal plane separating the mezzanine from the room or floor space in which it is located is open, and
an open
area without partitions or subdividing walls higher than 1 070 mm above the mezzanine floor. (See Appendix A)
per cent
of the floor area in which they are located, and
per cent
of the area of that suite
(see Appendix A)
. 
Except as permitted by Sentence (6), each level of mezzanine that is partly or wholly superimposed above the first level of mezzanine shall be considered as a storey in calculating the building height.
Platforms intended solely for periodic inspection and elevated maintenance catwalks need not be considered as floor assemblies or mezzanines for the purpose of calculating building height, provided
per cent
of the horizontal plane separating the mezzanine from the room or floor space in which the mezzanine is located provided the enclosed space does not obstruct visual communication between the open space above the mezzanine and the room in which it is located.
(See Figure A-3.2.1.1.(3)-D in Appendix A.)

A service space in which facilities are included to permit a person to enter and to undertake maintenance
and other operations pertaining to building services from within the service space need not be considered a storey if it conforms to Articles 3.2.5.14. and 3.3.1.24., and Sentences 3.2.4.19.(10), 3.2.7.3.(2), 3.3.1.3.(7), 3.4.2.4.(3) and 3.4.4.4.(9). (See Appendix A.)3.2.1.2. Storage Garage Considered as a Separate Building
A basement used primarily as a storage garage is permitted to be considered as a separate building for the purposes of Subsection 3.2.2.,
provided the floor and roof assemblies above the basement and the exterior walls of the basement above the adjoining ground level are constructed as fire separations of
noncombustible construction
having a fire-resistance rating not less than 2 h
and protected in conformance with Clause 3.1.10.2.(4)(a),
except as permitted by Sentence (2).
(See A-3.1.10.2.(4) in Appendix A.)
The exterior wall of a basement that is required to be a fire separation with a fire-resistance rating in accordance with Sentence (1) is permitted to be penetrated by openings that are not protected by closures provided
The floor or roof assembly projection referred to in Clause (2)(b) shall have a fire-resistance rating not less than 2 h and shall have no openings within the projection.
3.2.1.3. Roof Considered as a Wall
For the purposes of this Section any part of a roof that is pitched at an angle of 60° or more to the horizontal
and is adjacent to a space intended for occupancy within a building shall be considered as part of an exterior wall of the building. 3.2.1.4. Floor Assembly over Basement
Except as permitted by Sentences 3.2.2.47.(3), 3.2.2.48.(3), 3.2.2.49.(3), 3.2.2.50.(5), 3.2.2.51.(3), 3.2.2.52.(3) or 3.2.2.53.(3), a floor assembly immediately above a basement shall be constructed as a fire separation having a fire-resistance rating conforming to the requirements of Articles 3.2.2.20. to 3.2.2.88. for a floor assembly, but not less than 45 min.
All loadbearing walls, columns and arches supporting a floor assembly immediately above a basement shall have a fire-resistance rating not less than that required by Sentence (1) for the floor assembly. 3.2.1.5. Fire Containment in Basements
Deleted.
In a building in which an automatic sprinkler system is not required to be installed by Article 3.2.2.18., every basement shall
Deleted.

3.2.1.6. Mezzanines
The floor assembly of a mezzanine that is required to be considered as a storey in calculating the building height shall be constructed in conformance with the fire separation requirements for floor assemblies stated in Articles 3.2.2.20. to 3.2.2.88.3.2.1.7.
Fire Containment in Group C Combustible Buildings Greater Than Two Storeys

3.2.2. Building Size and Construction Relative to Occupancy
3.2.2.1. Application
Except as permitted by Article 3.2.2.3., a building shall be constructed in conformance with this Subsection to prevent fire spread and collapse caused by
the effects of fire. (See Subsection 3.1.3. for fire separations between major occupancies.) 3.2.2.2. Special and Unusual Structures
A structure that cannot be identified with the characteristics of a building in Articles 3.2.2.20. to 3.2.2.88. shall be protected against fire spread and collapse in conformance with good fire protection engineering
practice. (See Appendix A.) (See also A-3 and A-3.2.5.12.(1) in Appendix A.)3.2.2.3. Exceptions to Structural Fire Protection

3.2.2.4. Buildings with Multiple Major Occupancies
The requirements restricting fire spread and collapse for a building of a single major occupancy classification are provided in this Subsection according
to its building height and building area. 
3.2.2.5. Applicable Building Height and Area
In determining the fire safety requirements of a building in relation to each of the major occupancies contained therein, the building height and building area of the entire building shall be used. 3.2.2.6. Multiple Major Occupancies
Except as permitted by Articles 3.2.2.7. and 3.2.2.8., in a building containing more than one major occupancy, the requirements of this Subsection for the most
restricted major occupancy contained shall apply to the whole building. 3.2.2.7. Superimposed Major Occupancies
Except as permitted by Article 3.2.2.8. and as required by Sentence 3.2.2.18.(2), in a building in which one major occupancy is located entirely above another major occupancy, the requirements in this Subsection for each portion of the building containing a major occupancy shall apply to that portion as if the entire building was of that major occupancy. 
3.2.2.8. Exceptions for Major Occupancies
per cent
of the floor area of the storey in which they are located, these major occupancies need not be considered as major occupancies for the purposes of this Subsection, provided they are not
classified as Group F, Division 1 or 2 occupancies. 
3.2.2.9. Crawl Spaces
For the purposes of Articles 3.1.11.6., 3.2.1.4. and 3.2.1.5., a crawl space shall be considered as a basement if it is
A floor assembly immediately above a crawl space is not required to be constructed as a fire separation and is not required to have a fire-resistance rating provided the crawl space is not required to be considered
as a basement by Sentence (1). 3.2.2.10. Streets
Every building shall face a street located in conformance with the requirements of Articles 3.2.5.4. and 3.2.5.5. for access routes.
For the purposes of Subsections 3.2.2. and 3.2.5. an access route conforming to Subsection 3.2.5. is
permitted to be considered as a street.
per cent
of the building perimeter is located within 15 m of the street or streets. 
per cent
of the building perimeter is located within 15 m of the street or streets. 
Enclosed spaces, tunnels, bridges and similar structures, even though used for vehicular or pedestrian traffic, are not considered
as streets for the purpose of this Part. 3.2.2.11. Exterior Balconies
construction
required by Articles 3.2.2.20. to 3.2.2.88., as applicable to the occupancy classification of the building. 
3.2.2.12. Exterior Passageways
An elevated exterior passageway used as part of a means of egress shall conform to the requirements of Articles 3.2.2.20. to 3.2.2.88. for mezzanines. 3.2.2.13. Occupancy on Roof
A portion of a roof that supports an occupancy shall be constructed in conformance with the fire separation requirements of Articles 3.2.2.20. to 3.2.2.88. for floor assemblies, and not the fire-resistance rating for roof assemblies. 3.2.2.14. Roof-Top Enclosures

A roof-top enclosure for elevator machinery or for a service room, not more than one storey high, is not required to have a fire-resistance rating. 
A roof-top enclosure for a stairway need not have a fire-resistance rating nor be constructed as a fire separation. 3.2.2.15. Storeys below Ground
If a building is erected entirely below the adjoining finished ground level and does not extend more
than one storey below that ground level, the minimum precautions against fire spread and collapse shall be the
same as are required for basements under a building of 1 storey in building height having the same occupancy and building area.

Deleted.

3.2.2.16. Heavy Timber Roof Permitted

If Sentence (1) permits a roof assembly to be of heavy timber construction, structural members in the storey immediately below the roof assembly are permitted to be of heavy timber construction. 3.2.2.17. Arena-Type Building Roof Assembly
The requirements for a roof assembly to have a fire-resistance rating are permitted to be waived for a gymnasium, a swimming pool, an arena, or a rink if no
part of the roof assembly is less than 6 m above the
main floor or balcony and the roof carries no loads other than normal
roof loads, including permanent access walks, and ventilating, sound
and lighting equipment, except that the restriction concerning minimum
distance shall not apply to3.2.2.18. Automatic Sprinkler System Required
Except as required by Sentence (2) and (3),
an automatic sprinkler system conforming to the requirements of Articles 3.2.4.8., 3.2.4.9., 3.2.4.10. and 3.2.5.12. shall be installed throughout a building regulated by one or more of Articles 3.2.2.20., 3.2.2.21., 3.2.2.22., 3.2.2.23., 3.2.2.24., 3.2.2.26., 3.2.2.27., 3.2.2.29., 3.2.2.31., 3.2.2.33., 3.2.2.36., 3.2.2.37., 3.2.2.38., 3.2.2.39., 3.2.2.40., 3.2.2.41.,
3.2.2.42., 3.2.2.43., 3.2.2.44., 3.2.2.45., 3.2.2.46.,
3.2.2.47., 3.2.2.48., 3.2.2.50., 3.2.2.53., 3.2.2.54., 3.2.2.56., 3.2.2.57., 3.2.2.59., 3.2.2.61., 3.2.2.62., 3.2.2.63., 3.2.2.65., 3.2.2.67., 3.2.2.68., 3.2.2.69., 3.2.2.70., 3.2.2.72., 3.2.2.73., 3.2.2.75., 3.2.2.77., 3.2.2.78., 3.2.2.80., 3.2.2.82., 3.2.2.84. and 3.2.2.86.

Except for buildings described in Sentence 1.3.3.6.(2) of Division A, all newly constructed buildings shall be provided with an automatic sprinkler system designed and installed in accordance with Article 3.2.5.12.
3.2.2.19. Buildings Containing Impeded Egress Zones
A building containing an impeded egress zone and conforming to the appropriate requirements of Articles 3.2.2.20. to 3.2.2.88. is not required to conform to the requirements of Articles 3.2.2.36. and 3.2.2.37. for a Group B, Division 1 major occupancy provided3.2.2.20. Group A, Division 1, Any Height, Any Area, Sprinklered
Except as permitted by Articles 3.2.2.21. and 3.2.2.22., a building classified as Group A, Division 1 shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.21. Group A, Division 1, One Storey, Limited Area, Sprinklered
per cent
of the area of the building as 2 storeys for the purpose of
The building referred to in Sentence (1) is permitted to be of heavy timber construction or noncombustible construction used singly or in combination, and3.2.2.22. Group A, Division 1, One Storey, Sprinklered
A building classified as Group A, Division 1 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly, or in combination, and3.2.2.23. Group A, Division 2, Any Height, Any Area, Sprinklered
Except as permitted by Articles 3.2.2.24. to 3.2.2.28., a building classified as Group A, Division 2 shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.24. Group A, Division 2, up to 6 Storeys, Any Area, Sprinklered
A building classified as Group A, Division 2, that is not limited by building area, is permitted to conform to Sentence (2) provided
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.25. Group A, Division 2, up to 2 Storeys
A building classified as Group A, Division 2 is permitted to conform to Sentence (2) provided| Table 3.2.2.25. Maximum Building Area, Group A, Division 2, up to 2 Storeys Forming part of Sentence 3.2.2.25.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 1 600 | 2 000 | 2 400 |
| 2 | 800 | 1 000 | 1 200 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.26. Group A, Division 2, up to 2 Storeys, Increased Area, Sprinklered
A building classified as Group A, Division 2 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.27. Group A, Division 2, up to 2 Storeys, Sprinklered
A building classified as Group A, Division 2 is permitted to be of combustible construction or noncombustible construction, used singly or in combination, provided3.2.2.28. Group A, Division 2, One Storey
A building classified as Group A, Division 2 is permitted to be of combustible construction or noncombustible construction, used singly or in combination, provided
In a building referred to in Sentence (1) without a basement, the building area limits of Sentence (1) are permitted to be doubled provided a fire separation with a fire-resistance rating not less than 1 h is used to separate the building into fire compartments, each one of which does not exceed the limits of Clause (1)(b). 3.2.2.29. Group A, Division 3, Any Height, Any Area, Sprinklered
Except as permitted by Articles 3.2.2.30. to 3.2.2.34., a building classified as Group A, Division 3 shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.30. Group A, Division 3, up to 2 Storeys
A building classified as Group A, Division 3 is permitted to conform to Sentence (2) provided| Table 3.2.2.30. Maximum Building Area, Group A, Division 3, up to 2 Storeys Forming part of Sentence 3.2.2.30.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 4 000 | 5 000 | 6 000 |
| 2 | 2 000 | 2 500 | 3 000 |
Except as permitted by Clauses (c) and (d), the building referred to in Sentence (1) shall be of noncombustible construction, and
If intended for occasional use for trade shows and similar exhibition purposes, a building referred to in Sentence (1) that is more than 1 500 m2 in building area shall be sprinklered throughout. 3.2.2.31. Group A, Division 3, up to 2 Storeys, Sprinklered
A building classified as Group A, Division 3 is permitted to conform to Sentence (2) provided
Except as permitted by Clause (c) and Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.32. Group A, Division 3, One Storey, Increased Area
A building classified as Group A, Division 3 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and
If intended for occasional use for trade shows and similar exhibition purposes, a building referred to in Sentence (1) that is more than 1 500 m2 in building area shall be sprinklered throughout. 3.2.2.33. Group A, Division 3, One Storey, Sprinklered
A building classified as Group A, Division 3 is permitted to be of combustible construction or noncombustible construction used singly or in combination provided3.2.2.34. Group A, Division 3, One Storey
A building classified as Group A, Division 3 is permitted to be of combustible construction or noncombustible construction used singly or in combination provided3.2.2.35. Group A, Division 4
Except as permitted by Sentences (2) and (3), a building classified as Group A, Division 4 shall be of noncombustible construction.
Roof assemblies and supporting arches and columns are permitted to be of heavy timber construction.
A building classified as Group A, Division 4 is permitted to be of combustible construction provided
Sprinklers shall be installed in all spaces below tiers of seats in a building classified as Group A, Division 4 if those spaces are used for occupancy. (See Appendix A.)3.2.2.36. Group B, Division 1, Any Height, Any Area, Sprinklered
Except as permitted by Article 3.2.2.37., a building classified as Group B, Division 1 shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.37. Group B, Division 1, up to 3 Storeys, Sprinklered
A building classified as Group B, Division 1 is permitted to conform to Sentence (2) provided
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.38. Group B, Division 2, Any Height, Any Area, Sprinklered
Except as permitted by Articles 3.2.2.39. to 3.2.2.41., a building classified as Group B, Division 2 shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.39. Group B, Division 2, up to 3 Storeys, Sprinklered
A building classified as Group B, Division 2 is permitted to conform to Sentence (2) provided
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.40. Group B, Division 2, up to 2 Storeys, Sprinklered
A building classified as Group B, Division 2 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.41. Group B, Division 2, One Storey, Sprinklered
A building classified as Group B, Division 2 is permitted to be of combustible construction or noncombustible construction, used singly or in combination, provided3.2.2.42.
Group B, Division 3, Any Height, Any Area, Sprinklered
Except as permitted by Articles 3.2.2.43. to 3.2.2.46., a building classified as Group B, Division 3 shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.43. Group B, Division 3, up to 3 Storeys (Noncombustible), Sprinklered
A building classified as Group B, Division 3 is permitted to conform to Sentence (2) provided
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.44. Group B, Division 3, up to 3 Storeys, Sprinklered
A building classified as Group B, Division 3 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction, used singly or in combination, and3.2.2.45. Group B, Division 3, up to 2 Storeys, Sprinklered
A building classified as Group B, Division 3 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction, used singly or in combination, and3.2.2.46. Group B, Division 3, One Storey, Sprinklered
A building classified as Group B, Division 3 is permitted to be of combustible construction or noncombustible construction, used singly or in combination, provided
3.2.2.47. Group C, Any Height, Any Area, Sprinklered
Except as permitted by Articles 3.2.2.48. to 3.2.2.53., a building classified as Group C shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and
In a building that contains dwelling units that have more than one storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations. 3.2.2.48. Group C, up to 6 Storeys, Sprinklered
A building classified as Group C is permitted to conform to Sentence (2) provided
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and
In a building that contains dwelling units that have more than one storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations. 3.2.2.49. Group C, up to 3 Storeys, Noncombustible Construction
A building classified as Group C is permitted to conform to Sentence (2) provided| Table 3.2.2.49. Maximum Building Area, Group C, up to 3 Storeys Forming part of Sentence 3.2.2.49.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | not limited | not limited | not limited |
| 2 | 6 000 | not limited | not limited |
| 3 | 4 000 | 5 000 | 6 000 |
The building referred to in Sentence (1) shall be of noncombustible construction, and
In a building that contains dwelling units that have more than one storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations. 3.2.2.50. Group C, up to 6 Storeys, Sprinklered
A building classified as Group C is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and
Except as required in Sentence (4), a building referred to in Subclause (1) (d)(v) or (d)(vi)
shall have an exterior wall assembly
CAN/ULC-S102, “Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies,”
or
Sentences 3.1.5.5.(3) and (4)
when subjected to testing in conformance with CAN/ULC-S134, “Fire Test of Exterior Wall Assemblies.”
The solutions described in Clauses 3.2.2.50.(3)(b) and (c) are not permitted where an exposing building face is required by Article 3.2.3.7. to have noncombustible cladding.

In a building that contains dwelling units that have more than one storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
In a building in which there is no dwelling unit above another dwelling unit, the fire-resistance rating for floor assemblies entirely within the dwelling unit is waived. 
3.2.2.51. Group C, up to 3 Storeys, Increased Area
A building classified as Group C is permitted to conform to Sentence (2) provided| Table 3.2.2.51. Maximum Building Area, Group C, up to 3 Storeys, Increased Area Forming part of Sentence 3.2.2.51.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 2 400 | 3 000 | 3 600 |
| 2 | 1 200 | 1 500 | 1 800 |
| 3 | 800 | 1 000 | 1 200 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and
In a building that contains dwelling units that have more than one storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
In a building in which there is no dwelling unit above another dwelling unit, the fire-resistance rating for floor assemblies entirely within the dwelling unit is waived. 3.2.2.52. Group C, up to 3 Storeys
A building classified as Group C is permitted to conform to Sentence (2) provided| Table 3.2.2.52. Maximum Building Area, Group C, up to 3 Storeys Forming part of Sentence 3.2.2.52.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 1 800 | 2 250 | 2 700 |
| 2 | 900 | 1 125 | 1 350 |
| 3 | 600 | 750 | 900 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and
In a building that contains dwelling units that have more than one storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 45 min but need not be constructed as fire separations.
In a building in which there is no dwelling unit above another dwelling unit, the fire-resistance rating for floor assemblies entirely within the dwelling unit is waived. 3.2.2.53. Group C, up to 3 Storeys, Sprinklered
A building classified as Group C is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and
In a building that contains dwelling units that have more than one storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 45 min but need not be constructed as fire separations.
In a building in which there is no dwelling unit above another dwelling unit, the fire-resistance rating for floor assemblies entirely within the dwelling unit is waived. 3.2.2.54. Group D, Any Height, Any Area, Sprinklered
Except as permitted by Articles 3.2.2.55. to 3.2.2.61., a building classified as Group D shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.55. Group D, up to 6 Storeys
A building classified as Group D is permitted to conform to Sentence (2) provided| Table 3.2.2.55. Maximum Building Area, Group D, up to 6 Storeys Forming part of Sentence 3.2.2.55.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | not limited | not limited | not limited |
| 2 | 7 200 | not limited | not limited |
| 3 | 4 800 | 6 000 | 7 200 |
| 4 | 3 600 | 4 500 | 5 400 |
| 5 | 2 880 | 3 600 | 4 320 |
| 6 | 2 400 | 3 000 | 3 600 |
The building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.56. Group D, up to 6 Storeys, Sprinklered
A building classified as Group D is permitted to conform to Sentence (2) provided
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.57. Group D, up to 4 Storeys, Sprinklered
A building classified as Group D is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.58. Group D, up to 3 Storeys
A building classified as Group D is permitted to conform to Sentence (2) provided| Table 3.2.2.58. Maximum Building Area, Group D, up to 3 Storeys Forming part of Sentence 3.2.2.58.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 4 800 | 6 000 | 7 200 |
| 2 | 2 400 | 3 000 | 3 600 |
| 3 | 1 600 | 2 000 | 2 400 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.59. Group D, up to 3 Storeys, Sprinklered
A building classified as Group D is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.60. Group D, up to 2 Storeys
A building classified as Group D is permitted to conform to Sentence (2) provided| Table 3.2.2.60. Maximum Building Area, Group D, up to 2 Storeys Forming part of Sentence 3.2.2.60.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 1 000 | 1 250 | 1 500 |
| 2 | 800 | 1 000 | 1 200 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.61. Group D, up to 2 Storeys, Sprinklered
A building classified as Group D is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.62. Group E, Any Height, Any Area, Sprinklered
Except as permitted by Articles 3.2.2.63. to 3.2.2.67., a building classified as Group E shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.63. Group E, up to 4 Storeys, Sprinklered
A building classified as Group E is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.64. Group E, up to 3 Storeys
A building classified as Group E is permitted to conform to Sentence (2) provided| Table 3.2.2.64. Maximum Building Area, Group E, up to 3 Storeys Forming part of Sentence 3.2.2.64.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 1 500 | 1 500 | 1 500 |
| 2 | 1 200 | 1 500 | 1 500 |
| 3 | 800 | 1 000 | 1 500 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.65. Group E, up to 3 Storeys, Sprinklered
A building classified as Group E is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.66. Group E, up to 2 Storeys
A building classified as Group E is permitted to conform to Sentence (2) provided| Table 3.2.2.66. Maximum Building Area, Group E, up to 2 Storeys Forming part of Sentence 3.2.2.66.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 1 000 | 1 250 | 1 500 |
| 2 | 600 | 750 | 900 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.67. Group E, up to 2 Storeys, Sprinklered
A building classified as Group E is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.68. Group F, Division 1, up to 4 Storeys, Sprinklered
Except as permitted by Articles 3.2.2.69. to 3.2.2.71., a building classified as Group F, Division 1 shall conform to Sentence (2) provided
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.69. Group F, Division 1, up to 3 Storeys, Sprinklered
A building classified as Group F, Division 1 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of heavy timber construction or noncombustible construction used singly or in combination, and3.2.2.70. Group F, Division 1, up to 2 Storeys, Sprinklered
A building classified as Group F, Division 1 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.71. Group F, Division 1, One Storey
A building classified as Group F, Division 1 is permitted to be of combustible construction or noncombustible construction used singly or in combination provided3.2.2.72. Group F, Division 2, Any Height, Any Area, Sprinklered
Except as permitted by Articles 3.2.2.73. to 3.2.2.77., a building classified as Group F, Division 2 shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.73. Group F, Division 2, up to 4 Storeys, Increased Area, Sprinklered
A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.74. Group F, Division 2, up to 3 Storeys
A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided| Table 3.2.2.74. Maximum Building Area, Group F, Division 2, up to 3 Storeys Forming part of Sentence 3.2.2.74.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 1 500 | 1 500 | 1 500 |
| 2 | 1 500 | 1 500 | 1 500 |
| 3 | 1 070 | 1 340 | 1 500 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.75. Group F, Division 2, up to 4 Storeys, Sprinklered
A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.76. Group F, Division 2, up to 2 Storeys
A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided| Table 3.2.2.76. Maximum Building Area, Group F, Division 2, up to 2 Storeys Forming part of Sentence 3.2.2.76.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 1 000 | 1 250 | 1 500 |
| 2 | 600 | 750 | 900 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.77. Group F, Division 2, up to 2 Storeys, Sprinklered
A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.78. Group F, Division 3, Any Height, Any Area, Sprinklered
Except as permitted by Articles 3.2.2.79. to 3.2.2.88., a building classified as Group F, Division 3 shall conform to Sentence (2).
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.79. Group F, Division 3, up to 6 Storeys
A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided| Table 3.2.2.79. Maximum Building Area, Group F, Division 3, up to 6 Storeys Forming part of Sentence 3.2.2.79.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | not limited | not limited | not limited |
| 2 | 7 200 | 9 000 | 10 800 |
| 3 | 4 800 | 6 000 | 7 200 |
| 4 | 3 600 | 4 500 | 5 400 |
| 5 | 2 880 | 3 600 | 4 320 |
| 6 | 2 400 | 3 000 | 3 600 |
The building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.80. Group F, Division 3, up to 6 Storeys, Sprinklered
A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided
Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and3.2.2.81. Group F, Division 3, up to 4 Storeys
A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided| Table 3.2.2.81. Maximum Building Area, Group F, Division 3, up to 4 Storeys Forming part of Sentence 3.2.2.81.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 4 800 | 6 000 | 7 200 |
| 2 | 2 400 | 3 000 | 3 600 |
| 3 | 1 600 | 2 000 | 2 400 |
| 4 | 1 200 | 1 500 | 1 800 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.82. Group F, Division 3, up to 4 Storeys, Sprinklered
A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.83. Group F, Division 3, up to 2 Storeys
A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided| Table 3.2.2.83. Maximum Building Area, Group F, Division 3, up to 2 Storeys Forming part of Sentence 3.2.2.83.(1) | |||
|
No. of Storeys |
Maximum Area, m2 |
||
|
Facing 1 Street |
Facing 2 Streets |
Facing 3 Streets | |
| 1 | 1 600 | 2 000 | 2 400 |
| 2 | 800 | 1 000 | 1 200 |
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.84. Group F, Division 3, up to 2 Storeys, Sprinklered
A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided
The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and3.2.2.85. Group F, Division 3, One Storey
A building classified as Group F, Division 3 is permitted to be of heavy timber construction or noncombustible construction used singly or in combination provided3.2.2.86. Group F, Division 3, One Storey, Sprinklered
A building classified as Group F, Division 3 is permitted to be of heavy timber construction or noncombustible construction used singly or in combination provided3.2.2.87. Group F, Division 3, One Storey, Any Area, Low Fire Load Occupancy
A building classified as Group F, Division 3 is permitted to conform to Sentence (2) provided it is3.2.2.88. Group F, Division 3, Storage Garages up to 22 m High
A building used as a storage garage with all storeys constructed as open-air storeys and having no other occupancy above it is permitted to have its floor, wall, ceiling and roof assemblies constructed without
a fire-resistance rating provided it is3.2.3. Spatial Separation and Exposure Protection
(See Appendix A.)
3.2.3.1. Limiting Distance and Area of Unprotected Openings
Except as permitted by Articles 3.2.3.10. to 3.2.3.12., the area of unprotected openings in an exposing building face for the applicable limiting distance shall be not more than the value determined in
accordance with
The area of the unprotected openings in an exposing building face shall be the aggregate area of unprotected openings expressed as a percentage of the area of the exposing building face in Table 3.2.3.1.B, Table 3.2.3.1.C, Table 3.2.3.1.D or Table 3.2.3.1.E. (See Sentence 3.2.3.2.(1).)
For the purpose of determining the type of construction and cladding and the fire-resistance rating of an exterior wall,
For the purpose of determining the actual percentage of unprotected openings permitted in an exterior wall, the location of the exposing building face is permitted to be taken at a vertical plane located so
that there are no unprotected openings between the vertical plane and the line to which the limiting distance is measured. (See Appendix A.)
Except for buildings that are sprinklered, where the limiting distance is 2 m or less, individual unprotected openings in an exposing building face shall be no greater than
| Table 3.2.3.1.A Maximum Concentrated Area of Unprotected Openings Forming part of Sentence 3.2.3.1.(5) | |
| Limiting Distance, m | Maximum Area of Individual Unprotected Openings, m2 |
| 1.2 | 0.35 |
| 1.5 | 0.78 |
| 2.0 | 1.88 |
The spacing between individual unprotected openings described in Sentence (5) that serve a single room or space described in Sentence (7) shall not be less than
For the purpose of Sentence (6), “single room or space” shall mean
per cent
or more of all fire department calls to the building, and 

If the surface temperature on the unexposed surface of a wall assembly exceeds the temperature limit of a standard fire test as permitted by Article 3.1.7.2., an allowance shall be made for the radiation from the hot unexposed wall surface by
adding an equivalent area of unprotected opening to the area of actual openings as follows:


Unless a closure used to protect an opening in an exposing building face has a protective performance equivalent to that required for the wall assembly in which it is located, an equivalent area of unprotected opening, determined in accordance with the procedures of Sentence (9) shall be added to the greater of| Table 3.2.3.1.B Unprotected Opening Limits for a Building or Fire Compartment that is not Sprinklered Throughout Forming part of Article 3.2.3.1. | |||||||||||||||||||||||||||
|
Area of Unprotected Opening for Groups A, C, D, and F, Division 3 Occupancies, % |
|||||||||||||||||||||||||||
|
Max. Area, m2 |
Ratio | ||||||||||||||||||||||||||
| 0 | 1.2 | 1.5 | 2.0 | 2.5 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 16 | 18 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | ||
| 10 | Less than 3 : 1 | 0 | 8 | 10 | 18 | 29 | 46 | 91 | 100 | ||||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 8 | 12 | 21 | 33 | 50 | 96 | 100 | |||||||||||||||||||
| over 10 : 1 | 0 | 11 | 18 | 32 | 48 | 68 | 100 | ||||||||||||||||||||
| 15 | Less than 3 : 1 | 0 | 7 | 9 | 14 | 22 | 33 | 63 | 100 | ||||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 8 | 10 | 17 | 25 | 37 | 67 | 100 | |||||||||||||||||||
| over 10 : 1 | 0 | 10 | 15 | 26 | 39 | 53 | 87 | 100 | |||||||||||||||||||
| 20 | Less than 3 : 1 | 0 | 7 | 9 | 12 | 18 | 26 | 49 | 81 | 100 | |||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 8 | 10 | 15 | 21 | 30 | 53 | 85 | 100 | ||||||||||||||||||
| over 10 : 1 | 0 | 9 | 14 | 23 | 33 | 45 | 72 | 100 | |||||||||||||||||||
| 25 | Less than 3 : 1 | 0 | 7 | 8 | 11 | 16 | 23 | 41 | 66 | 98 | 100 | ||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 8 | 9 | 13 | 19 | 26 | 45 | 70 | 100 | ||||||||||||||||||
| over 10 : 1 | 0 | 9 | 13 | 21 | 30 | 39 | 62 | 90 | 100 | ||||||||||||||||||
| 30 | Less than 3 : 1 | 0 | 7 | 8 | 11 | 15 | 20 | 35 | 56 | 83 | 100 | ||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 7 | 9 | 12 | 17 | 23 | 39 | 61 | 88 | 100 | |||||||||||||||||
| over 10 : 1 | 0 | 8 | 12 | 19 | 27 | 36 | 56 | 79 | 100 | ||||||||||||||||||
| 40 | Less than 3 : 1 | 0 | 7 | 8 | 10 | 13 | 17 | 28 | 44 | 64 | 89 | 100 | |||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 7 | 8 | 11 | 15 | 20 | 32 | 48 | 69 | 93 | 100 | ||||||||||||||||
| over 10 : 1 | 0 | 8 | 11 | 17 | 24 | 31 | 47 | 66 | 88 | 100 | |||||||||||||||||
| 50 | Less than 3 : 1 | 0 | 7 | 8 | 9 | 12 | 15 | 24 | 37 | 53 | 72 | 96 | 100 | ||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 7 | 8 | 10 | 14 | 18 | 28 | 41 | 57 | 77 | 100 | ||||||||||||||||
| over 10 : 1 | 0 | 8 | 10 | 15 | 21 | 28 | 41 | 57 | 76 | 97 | 100 | ||||||||||||||||
| 60 | Less than 3 : 1 | 0 | 7 | 8 | 9 | 11 | 14 | 21 | 32 | 45 | 62 | 81 | 100 | ||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 7 | 8 | 10 | 13 | 16 | 25 | 36 | 49 | 66 | 85 | 100 | |||||||||||||||
| over 10 : 1 | 0 | 8 | 10 | 14 | 20 | 25 | 38 | 51 | 67 | 85 | 100 | ||||||||||||||||
| 80 | Less than 3 : 1 | 0 | 7 | 7 | 8 | 10 | 12 | 18 | 26 | 36 | 48 | 62 | 79 | 98 | 100 | ||||||||||||
| 3 : 1 to 10 : 1 | 0 | 7 | 8 | 9 | 11 | 14 | 21 | 29 | 40 | 52 | 67 | 84 | 100 | ||||||||||||||
| over 10 : 1 | 0 | 8 | 9 | 13 | 17 | 22 | 32 | 44 | 56 | 70 | 86 | 100 | |||||||||||||||
| 100 | Less than 3 : 1 | 0 | 7 | 7 | 8 | 9 | 11 | 16 | 22 | 30 | 40 | 51 | 65 | 80 | 97 | 100 | |||||||||||
| 3 : 1 to 10 : 1 | 0 | 7 | 8 | 9 | 11 | 13 | 18 | 25 | 34 | 44 | 56 | 69 | 84 | 100 | |||||||||||||
| over 10 : 1 | 0 | 7 | 9 | 12 | 16 | 20 | 29 | 39 | 49 | 61 | 74 | 89 | 100 | ||||||||||||||
| 150 | Less than 3 : 1 | 0 | 7 | 7 | 8 | 9 | 10 | 13 | 17 | 22 | 29 | 37 | 46 | 56 | 67 | 79 | 93 | 100 | |||||||||
| 3 : 1 to 10 : 1 | 0 | 7 | 7 | 8 | 10 | 11 | 15 | 20 | 26 | 33 | 41 | 50 | 60 | 71 | 84 | 97 | 100 | ||||||||||
| over 10 : 1 | 0 | 7 | 8 | 11 | 13 | 17 | 24 | 31 | 39 | 48 | 57 | 68 | 79 | 91 | 100 | ||||||||||||
| 250 | Less than 3 : 1 | 0 | 7 | 7 | 7 | 8 | 9 | 10 | 13 | 16 | 20 | 25 | 30 | 36 | 43 | 51 | 59 | 68 | 87 | 100 | |||||||
| 3 : 1 to 10 : 1 | 0 | 7 | 7 | 8 | 9 | 10 | 12 | 15 | 19 | 24 | 28 | 34 | 40 | 47 | 55 | 63 | 72 | 92 | 100 | ||||||||
| over 10 : 1 | 0 | 7 | 8 | 9 | 11 | 14 | 19 | 24 | 30 | 36 | 43 | 50 | 57 | 65 | 73 | 82 | 92 | 100 | |||||||||
| 350 | Less than 3 : 1 | 0 | 7 | 7 | 7 | 8 | 8 | 9 | 11 | 14 | 16 | 20 | 24 | 28 | 33 | 38 | 44 | 50 | 64 | 81 | 99 | 100 | |||||
| 3 : 1 to 10 : 1 | 0 | 7 | 7 | 8 | 8 | 9 | 11 | 13 | 16 | 19 | 23 | 27 | 32 | 37 | 42 | 48 | 55 | 69 | 85 | 100 | |||||||
| over 10 : 1 | 0 | 7 | 8 | 9 | 10 | 12 | 16 | 21 | 25 | 30 | 36 | 41 | 47 | 53 | 59 | 66 | 73 | 88 | 100 | ||||||||
| 500 | Less than 3 : 1 | 0 | 7 | 7 | 7 | 7 | 8 | 9 | 10 | 12 | 14 | 16 | 19 | 22 | 25 | 29 | 33 | 37 | 47 | 59 | 71 | 100 | |||||
| 3 : 1 to 10 : 1 | 0 | 7 | 7 | 7 | 8 | 8 | 10 | 12 | 14 | 16 | 19 | 22 | 25 | 29 | 33 | 37 | 41 | 52 | 63 | 76 | 100 | ||||||
| over 10 : 1 | 0 | 7 | 7 | 8 | 9 | 11 | 14 | 18 | 22 | 25 | 30 | 34 | 38 | 43 | 48 | 53 | 58 | 70 | 82 | 96 | 100 | ||||||
| 1 000 | Less than 3 : 1 | 0 | 7 | 7 | 7 | 7 | 7 | 8 | 9 | 9 | 10 | 12 | 13 | 14 | 16 | 18 | 20 | 22 | 27 | 33 | 39 | 58 | 82 | 100 | |||
| 3 : 1 to 10 : 1 | 0 | 7 | 7 | 7 | 7 | 8 | 9 | 10 | 11 | 12 | 14 | 15 | 17 | 19 | 21 | 23 | 26 | 31 | 37 | 43 | 63 | 86 | 100 | ||||
| over 10 : 1 | 0 | 7 | 7 | 8 | 8 | 9 | 11 | 13 | 16 | 19 | 21 | 24 | 27 | 30 | 33 | 36 | 39 | 46 | 53 | 60 | 82 | 100 | |||||
| 2 000 | Less than 3 : 1 | 0 | 7 | 7 | 7 | 7 | 7 | 7 | 8 | 8 | 9 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 17 | 20 | 23 | 33 | 44 | 58 | 74 | 93 | 100 |
| 3 : 1 to 10 : 1 | 0 | 7 | 7 | 7 | 7 | 7 | 8 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 20 | 23 | 27 | 37 | 49 | 63 | 79 | 97 | 100 | |
| over 10 : 1 | 0 | 7 | 7 | 7 | 8 | 8 | 9 | 11 | 12 | 14 | 16 | 18 | 19 | 21 | 23 | 25 | 27 | 32 | 36 | 40 | 53 | 66 | 82 | 99 | 100 | ||
| Notes to Table 3.2.3.1.B: | |
|
|
|
| (1) | Apply whichever ratio is greater.
L= Length of exposing building face
H= Height of exposing building face
|
| Table 3.2.3.1.C Unprotected Opening Limits for a Building or Fire Compartment that is not Sprinklered Throughout Forming part of Article 3.2.3.1. | |||||||||||||||||||||||||||||||
|
Area of Unprotected Openings for Groups E and F, Division 1 and 2 Occupancies, % |
|||||||||||||||||||||||||||||||
|
Max. Area, m2 |
Ratio
| ||||||||||||||||||||||||||||||
| 0 | 1.2 | 1.5 | 2.0 | 2.5 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 16 | 18 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | ||
| 10 | Less than 3 : 1 | 0 | 4 | 5 | 9 | 15 | 23 | 46 | 77 | 100 | |||||||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 6 | 10 | 17 | 25 | 48 | 79 | 100 | ||||||||||||||||||||||
| over 10 : 1 | 0 | 5 | 9 | 16 | 24 | 34 | 58 | 91 | 100 | ||||||||||||||||||||||
| 15 | Less than 3 : 1 | 0 | 4 | 5 | 7 | 11 | 16 | 32 | 53 | 79 | 100 | ||||||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 5 | 8 | 13 | 18 | 34 | 55 | 82 | 100 | |||||||||||||||||||||
| over 10 : 1 | 0 | 5 | 8 | 13 | 19 | 26 | 43 | 66 | 93 | 100 | |||||||||||||||||||||
| 20 | Less than 3 : 1 | 0 | 4 | 4 | 6 | 9 | 13 | 25 | 40 | 61 | 85 | 100 | |||||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 5 | 7 | 11 | 15 | 27 | 43 | 63 | 87 | 100 | ||||||||||||||||||||
| over 10 : 1 | 0 | 5 | 7 | 11 | 17 | 22 | 36 | 53 | 74 | 99 | 100 | ||||||||||||||||||||
| 25 | Less than 3 : 1 | 0 | 4 | 4 | 6 | 8 | 11 | 20 | 33 | 49 | 69 | 92 | 100 | ||||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 5 | 7 | 9 | 13 | 22 | 35 | 51 | 71 | 94 | 100 | |||||||||||||||||||
| over 10 : 1 | 0 | 4 | 6 | 10 | 15 | 20 | 31 | 45 | 62 | 82 | 100 | ||||||||||||||||||||
| 30 | Less than 3 : 1 | 0 | 4 | 4 | 5 | 7 | 10 | 18 | 28 | 42 | 58 | 77 | 100 | ||||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 6 | 9 | 12 | 20 | 30 | 44 | 60 | 80 | 100 | |||||||||||||||||||
| over 10 : 1 | 0 | 4 | 6 | 10 | 14 | 18 | 28 | 40 | 54 | 71 | 91 | 100 | |||||||||||||||||||
| 40 | Less than 3 : 1 | 0 | 4 | 4 | 5 | 6 | 8 | 14 | 22 | 32 | 44 | 59 | 76 | 94 | 100 | ||||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 6 | 8 | 10 | 16 | 24 | 34 | 47 | 61 | 78 | 97 | 100 | |||||||||||||||||
| over 10 : 1 | 0 | 4 | 5 | 8 | 12 | 15 | 23 | 33 | 44 | 57 | 72 | 89 | 100 | ||||||||||||||||||
| 50 | Less than 3 : 1 | 0 | 4 | 4 | 5 | 6 | 7 | 12 | 18 | 26 | 36 | 48 | 61 | 76 | 93 | 100 | |||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 5 | 7 | 9 | 14 | 20 | 29 | 38 | 50 | 63 | 79 | 95 | 100 | ||||||||||||||||
| over 10 : 1 | 0 | 4 | 5 | 8 | 11 | 14 | 21 | 29 | 38 | 48 | 61 | 74 | 90 | 100 | |||||||||||||||||
| 60 | Less than 3 : 1 | 0 | 4 | 4 | 4 | 5 | 7 | 11 | 16 | 23 | 31 | 40 | 52 | 64 | 78 | 94 | 100 | ||||||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 5 | 6 | 8 | 12 | 18 | 25 | 33 | 43 | 54 | 66 | 81 | 96 | 100 | |||||||||||||||
| over 10 : 1 | 0 | 4 | 5 | 7 | 10 | 13 | 19 | 26 | 34 | 43 | 53 | 64 | 77 | 92 | 100 | ||||||||||||||||
| 80 | Less than 3 : 1 | 0 | 4 | 4 | 4 | 5 | 6 | 9 | 13 | 18 | 24 | 31 | 40 | 49 | 60 | 71 | 84 | 98 | 100 | ||||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 5 | 6 | 7 | 10 | 15 | 20 | 26 | 33 | 42 | 51 | 62 | 74 | 86 | 100 | ||||||||||||||
| over 10 : 1 | 0 | 4 | 5 | 6 | 9 | 11 | 16 | 22 | 28 | 35 | 43 | 52 | 62 | 73 | 85 | 98 | 100 | ||||||||||||||
| 100 | Less than 3 : 1 | 0 | 4 | 4 | 4 | 5 | 5 | 8 | 11 | 15 | 20 | 26 | 32 | 40 | 48 | 58 | 68 | 79 | 100 | ||||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 4 | 5 | 6 | 9 | 13 | 17 | 22 | 28 | 35 | 42 | 51 | 60 | 70 | 81 | 100 | |||||||||||||
| over 10 : 1 | 0 | 4 | 4 | 6 | 8 | 10 | 14 | 19 | 25 | 31 | 37 | 44 | 52 | 61 | 71 | 81 | 92 | 100 | |||||||||||||
| 150 | Less than 3 : 1 | 0 | 4 | 4 | 4 | 4 | 5 | 6 | 8 | 11 | 14 | 18 | 23 | 28 | 33 | 40 | 46 | 54 | 70 | 89 | 100 | ||||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 4 | 5 | 6 | 8 | 10 | 13 | 16 | 20 | 25 | 30 | 36 | 42 | 49 | 56 | 73 | 92 | 100 | |||||||||||
| over 10 : 1 | 0 | 4 | 4 | 5 | 7 | 8 | 12 | 16 | 20 | 24 | 29 | 34 | 39 | 46 | 52 | 59 | 67 | 84 | 100 | ||||||||||||
| 250 | Less than 3 : 1 | 0 | 4 | 4 | 4 | 4 | 4 | 5 | 7 | 8 | 10 | 12 | 15 | 18 | 22 | 25 | 29 | 34 | 44 | 55 | 68 | 100 | |||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 4 | 4 | 5 | 6 | 8 | 10 | 12 | 14 | 17 | 20 | 24 | 27 | 32 | 36 | 46 | 57 | 70 | 100 | ||||||||||
| over 10 : 1 | 0 | 4 | 4 | 5 | 6 | 7 | 9 | 12 | 15 | 18 | 21 | 25 | 28 | 32 | 37 | 41 | 46 | 56 | 68 | 81 | 100 | ||||||||||
| 350 | Less than 3 : 1 | 0 | 4 | 4 | 4 | 4 | 4 | 5 | 6 | 7 | 8 | 10 | 12 | 14 | 16 | 19 | 22 | 25 | 32 | 40 | 49 | 77 | 100 | ||||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 4 | 4 | 4 | 5 | 7 | 8 | 10 | 12 | 14 | 16 | 18 | 21 | 24 | 27 | 34 | 43 | 52 | 79 | 100 | |||||||||
| over 10 : 1 | 0 | 4 | 4 | 4 | 5 | 6 | 8 | 10 | 13 | 15 | 18 | 21 | 23 | 26 | 30 | 33 | 36 | 44 | 53 | 62 | 90 | 100 | |||||||||
| 500 | Less than 3 : 1 | 0 | 4 | 4 | 4 | 4 | 4 | 4 | 5 | 6 | 7 | 8 | 9 | 11 | 13 | 14 | 16 | 19 | 24 | 29 | 36 | 55 | 78 | 100 | |||||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 4 | 4 | 4 | 5 | 6 | 7 | 8 | 9 | 11 | 13 | 14 | 16 | 18 | 21 | 26 | 31 | 38 | 57 | 80 | 100 | ||||||||
| over 10 : 1 | 0 | 4 | 4 | 4 | 5 | 5 | 7 | 9 | 11 | 13 | 15 | 17 | 19 | 21 | 24 | 26 | 29 | 35 | 41 | 48 | 68 | 92 | 100 | ||||||||
| 1 000 | Less than 3 : 1 | 0 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 5 | 5 | 6 | 6 | 7 | 8 | 9 | 10 | 11 | 14 | 16 | 20 | 29 | 41 | 55 | 71 | 89 | 100 | ||||
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 4 | 4 | 4 | 4 | 5 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 15 | 18 | 22 | 31 | 43 | 57 | 73 | 91 | 100 | |||||
| over 10 : 1 | 0 | 4 | 4 | 4 | 4 | 5 | 6 | 7 | 8 | 9 | 11 | 12 | 13 | 15 | 16 | 18 | 20 | 23 | 26 | 30 | 41 | 53 | 68 | 84 | 100 | ||||||
| 2 000 | Less than 3 : 1 | 0 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 7 | 7 | 9 | 10 | 12 | 16 | 22 | 29 | 37 | 46 | 56 | 68 | 80 | 94 | 100 |
| 3 : 1 to 10 : 1 | 0 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 5 | 5 | 5 | 6 | 6 | 7 | 7 | 8 | 9 | 10 | 12 | 13 | 18 | 24 | 31 | 39 | 49 | 59 | 70 | 83 | 96 | 100 | |
| over 10 : 1 | 0 | 4 | 4 | 4 | 4 | 4 | 5 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 16 | 18 | 20 | 26 | 33 | 41 | 50 | 59 | 70 | 81 | 94 | 100 | ||
| Notes to Table 3.2.3.1.C: | |
|
|
|
| (1) | Apply whichever ratio is greater.
L= Length of exposing building face
H= Height of exposing building face
|
| Table 3.2.3.1.D Unprotected Opening Limits for a Building or Fire Compartment that is Sprinklered Throughout Forming part of Article 3.2.3.1. | ||||||||||||
|
Area of Unprotected Opening for Groups A, B, C, D and F, Division 3 Occupancies, % |
||||||||||||
|
Max. Area, m2 |
||||||||||||
| 0 | 1.2 | 1.5 | 2.0 | 2.5 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | |
| 10 | 0 | 16 | 24 | 42 | 66 | 100 | ||||||
| 15 | 0 | 16 | 20 | 34 | 50 | 74 | 100 | |||||
| 20 | 0 | 16 | 20 | 30 | 42 | 60 | 100 | |||||
| 25 | 0 | 16 | 18 | 26 | 38 | 52 | 90 | 100 | ||||
| 30 | 0 | 14 | 18 | 24 | 34 | 46 | 78 | 100 | ||||
| 40 | 0 | 14 | 16 | 22 | 30 | 40 | 64 | 96 | 100 | |||
| 50 | 0 | 14 | 16 | 20 | 28 | 36 | 56 | 82 | 100 | |||
| 60 | 0 | 14 | 16 | 20 | 26 | 32 | 50 | 72 | 98 | 100 | ||
| 80 | 0 | 14 | 16 | 18 | 22 | 28 | 42 | 58 | 80 | 100 | ||
| 100 | 0 | 14 | 16 | 18 | 22 | 26 | 36 | 50 | 68 | 88 | 100 | |
| 150 or more | 0 | 14 | 14 | 16 | 20 | 22 | 30 | 40 | 52 | 66 | 82 | 100 |
| Table 3.2.3.1.E Unprotected Opening Limits for a Building or Fire Compartment that is Sprinklered Throughout Forming part of Article 3.2.3.1. | ||||||||||||||||||
|
Area of Unprotected Opening for Groups E and F, Division 1 and 2 Occupancies, % |
||||||||||||||||||
|
Max. Area, m2 |
||||||||||||||||||
| 0 | 1.2 | 1.5 | 2.0 | 2.5 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | |
| 10 | 0 | 8 | 12 | 20 | 34 | 50 | 96 | 100 | ||||||||||
| 15 | 0 | 8 | 10 | 16 | 26 | 36 | 68 | 100 | ||||||||||
| 20 | 0 | 8 | 10 | 14 | 22 | 30 | 54 | 86 | 100 | |||||||||
| 25 | 0 | 8 | 10 | 14 | 18 | 26 | 44 | 70 | 100 | |||||||||
| 30 | 0 | 8 | 8 | 12 | 18 | 24 | 40 | 60 | 88 | 100 | ||||||||
| 40 | 0 | 8 | 8 | 12 | 16 | 20 | 32 | 48 | 68 | 94 | 100 | |||||||
| 50 | 0 | 8 | 8 | 10 | 14 | 18 | 28 | 40 | 58 | 76 | 100 | |||||||
| 60 | 0 | 8 | 8 | 10 | 12 | 16 | 24 | 36 | 50 | 66 | 86 | 100 | ||||||
| 80 | 0 | 8 | 8 | 10 | 12 | 14 | 20 | 30 | 40 | 52 | 66 | 84 | 100 | |||||
| 100 | 0 | 8 | 8 | 8 | 10 | 12 | 18 | 26 | 34 | 44 | 56 | 70 | 84 | 100 | ||||
| 150 | 0 | 8 | 8 | 8 | 10 | 12 | 16 | 20 | 26 | 32 | 40 | 50 | 60 | 72 | 84 | 98 | 100 | |
| 200 or more | 0 | 8 | 8 | 8 | 8 | 10 | 14 | 18 | 22 | 28 | 34 | 42 | 50 | 60 | 68 | 80 | 92 | 100 |
3.2.3.2. Area of Exposing Building Face
Except as permitted by Sentences (2) and (3), the area of an exposing building face shall be calculated as the total area of an exterior wall
facing in one direction on any side of a building measured from the finished ground level to the uppermost ceiling.
If a building is divided by fire separations into fire compartments, the area of exposing building face is permitted to be calculated for each fire compartment provided the fire separations have a fire-resistance rating not less than 45 min.
In a building that is sprinklered throughout and contains an interconnected floor space, the area of the exposing building face for the interconnected floor space is permitted to be determined by considering each storey as a separate fire compartment notwithstanding openings through the floor assemblies.
3.2.3.3. Wall Enclosing Attic or Roof Space
An exterior wall enclosing an attic or roof space and located above an exposing building face, shall be constructed in conformance with the
requirements for the exposing building face. 3.2.3.4. Party Wall
3.2.3.5. Wall with Limiting Distance Less Than 1.2 m
Openings in a wall that has a limiting distance less than 1.2 m shall be protected by closures whose fire-protection rating is in conformance with the fire-resistance rating required for the wall.
3.2.3.6. Combustible Projections
Except for a building containing one or 2 dwelling units only, combustible projections on the exterior of a wall that could expose an adjacent building to fire spread and are more than 1 m above ground level, including balconies, platforms, canopies and stairs, shall not be
permitted within
Where the exposing building face has a limiting distance of not more than 0.45 m, projecting roof soffits shall not be constructed
above the exposing building face. (See Appendix A.)
Where the exposing building face has a limiting distance of more than 0.45 m, the face of roof soffits above the exposing building face shall not project to less than 0.45 m from the property line. (See A-3.2.3.6.(2) in Appendix A.)
Where roof soffits project to less than 1.2 m from the centre line of a lane or public thoroughfare, or from an imaginary
line between two buildings or fire compartments on the same property, they shall
For buildings of combustible construction, materials installed to provide the required protection of soffits may be covered with a combustible or noncombustible finish material.
3.2.3.7. Construction of Exposing Building Face
Except as provided in Sentences (3) and (4), and Articles 3.2.3.10. and 3.2.3.11., the fire-resistance rating, construction and cladding for exposing building faces of buildings or fire compartments of Group A, B, C, D or Group F, Division 3 occupancy classification shall comply with Table 3.2.3.7.

| Table 3.2.3.7. Minimum Construction Requirements for Exposing Building Faces Forming part of Sentences 3.2.3.7.(1) and (2) | ||||
| Occupancy Classification of Building or Fire Compartment | Maximum Area of Unprotected Openings Permitted, % of Exposing Building Face Area | Minimum Required Fire-Resistance Rating | Type of Construction Required | Type of Cladding Required |
| Group A, B, C, D, or Group F, Division 3 | 0 to 10 | 1 h | Noncombustible | Noncombustible |
| > 10 to 25 | 1 h | Combustible or Noncombustible | Noncombustible | |
| > 25 to 50 | 45 min | Combustible or Noncombustible | Noncombustible | |
| > 50 to < 100 | 45 min | Combustible or Noncombustible | Combustible or Noncombustible | |
| Group E, or Group F, Division 1 or 2 | 0 to 10 | 2 h | Noncombustible | Noncombustible |
| > 10 to 25 | 2 h | Combustible or Noncombustible | Noncombustible | |
| > 25 to 50 | 1 h | Combustible or Noncombustible | Noncombustible | |
| > 50 to < 100 | 1 h | Combustible or Noncombustible | Combustible or Noncombustible | |
per cent
of the exposing building face need not be noncombustible where the wall assembly complies with the requirements of Sentences 3.1.5.5.(1), (3) and (4) when tested in conformance with CAN/ULC-S134, “Fire Test of Exterior Wall Assemblies.”
per cent
but not more than 50
per cent
of the exposing building face need not be noncombustible where

Where Table 3.2.3.7. permits an area of unprotected openings of more than 10
per cent
but not more than 25
per cent
of the exposing building face,
the requirements for noncombustible cladding shall be waived for wall assemblies that comply with Article 3.1.5.5. (See Appendix A.) 

3.2.3.8. Protection of Exterior Building Face
and where the maximum permitted area of unprotected openings is greater than 10
per cent
of the exposing building face
, foamed plastic insulation used in an exterior wall of a building more than 3 storeys in building height shall be protected on its exterior surface by
The criteria for testing and the conditions of acceptance for a wall assembly to satisfy the requirements of Clause (1)(b) are that
The requirements of Sentence (1) are waived for wall assemblies that comply with the requirements of Article 3.1.5.5. (See A-3.2.3.7.(5) in Appendix A.)
3.2.3.9. Protection of Structural Members
Structural members, including beams, columns and arches, that are placed wholly or partly outside the exterior face of a building and are less than 3 m from the property line or the centre line of a public thoroughfare shall
be protected from exterior fire exposure by fire protection having
a fire-resistance rating not less than that required for their protection from interior fire exposure, as
stated in Articles 3.2.2.20. to 3.2.2.88., but not less than 1 h.
Structural members of heavy timber construction, including beams, columns and arches, that are placed wholly or partly outside the exterior face of a building and are 3 m or more from the property line or the centre line of a public thoroughfare need not be covered with noncombustible cladding. 3.2.3.10. Unlimited Unprotected Openings
Deleted
is permitted to have unlimited unprotected openings provided it has a limiting distance not less than 3 m. 
The exposing building face of a storey that faces a street and is at the same level as the street is permitted to have unlimited unprotected openings if the limiting distance is not less than 9 m.
3.2.3.11. Low Fire Load, One Storey Building
An exposing building face of a building of low-hazard industrial occupancy conforming to Article 3.2.2.87. is permitted to be of noncombustible construction without a fire-resistance rating provided3.2.3.12. Area Increase for Unprotected Openings
Except as required by Sentence 3.2.3.7.(6), the maximum area of unprotected openings in any exposing building face of an unsprinklered building is permitted to be doubled if the openings are glazed with3.2.3.13. Protection of Exit Facilities
Except as required by Sentence (3) and as permitted by Sentence 3.4.4.3.(1), if the plane of an exterior wall of an exit enclosure forms an angle less than 135° with the plane of an exterior
wall of the building it serves, and an opening in the exterior wall of the exit enclosure could be exposed to fire from an opening in the exterior wall of the building, the opening in either the exterior wall of the exit or the exterior wall of the building shall be protected in conformance with the requirements of Sentence (4) where the opening in the exterior wall of the building is within 3 m horizontally and
If any unenclosed exterior single means of egress
could be exposed to fire from an opening in the exterior wall of the building it serves, the opening in the exterior wall of the building shall be protected in conformance with the requirements of Sentence (4) where the opening in the exterior wall of the building is within 3 m horizontally and
Except as permitted by Sentence 3.4.4.3.(1), if an exterior exit door in one fire compartment is within 3 m horizontally of an opening in another fire compartment and the exterior walls of these fire compartments intersect at an exterior angle of less than 135°, the opening shall
be protected in conformance with the requirements of Sentence (4). 
A sprinkler water curtain for opening protection as permitted in Clause (4)(d) shall

3.2.3.14. Wall Exposed to Another Wall
Except as required by Sentences (3) and 3.2.3.13.(1) or as permitted by Sentence 3.2.3.19.(4), if an unprotected opening in an exterior wall of a fire compartment is exposed to an unprotected opening in the exterior wall of another fire compartment, and the planes of the 2 walls are parallel or at an angle less than 135°, measured from the exterior of the building, the unprotected openings in the 2 fire compartments shall be separated by a distance not less than Do where Do = 2D − ((θ /90) x D) but in no case less than 1 m, and
The exterior wall of each fire compartment referred to in Sentence (1) within the distance, Do, shall have a fire-resistance rating not less than that required for the interior vertical fire separation between the fire compartment and the remainder of the building. 
3.2.3.15. Wall Exposed to Adjoining Roof
Except as permitted by Sentence 3.2.3.19.(4), if a wall in a building is exposed to a fire hazard from an adjoining roof of a separate fire compartment that is not sprinklered in the same building, and the exposed wall contains windows within 3 storeys vertically and 5 m horizontally of the roof, the roof shall contain no skylights within 5 m of the exposed wall. 3.2.3.16. Protection of Soffits
Except as permitted by Sentences (3) and (4), where there is a common attic or roof space above more than 2 suites of residential occupancy or above more than 2 patients’ sleeping rooms, and the common attic or roof space projects beyond the exterior wall of the building, the soffit, and any opening in the soffit or other surface of the projection located within 2 500 mm of a window or door opening, shall be protected by
The soffit protection required by Sentence (1) shall extend the full width of the opening and to not less than 1 200 mm on either side of it, and shall apply
to all openings through the soffit within this limit.
If an eave overhang is completely separated from the remainder of the attic or roof space by the use of
fire blocks
, the requirements of Sentence (1) do not apply.

3.2.3.17. Canopy Protection for Vertically Separated Openings
Except as permitted by Sentences (2) and (3), if a storey classified as a Group E or Group F, Division 1 or 2 major occupancy is required to be separated from the storey above by a fire separation,
Except as permitted by Sentence (3), the canopy required by Sentence (1) is permitted to be omitted if the exterior wall of the upper storey is recessed not less than 1 m behind the exterior wall containing the opening in the lower storey.
The requirements of Sentences (1) and (2) are permitted to be waived if the building is sprinklered throughout. 3.2.3.18. Covered Vehicular Passageway
A covered vehicular passageway designed as a receiving or shipping area shall be separated from every building or part of a building adjoining it by a fire separation having a fire-resistance rating not less than 1.5 h. 3.2.3.19. Walkway between Buildings
Except as required by Sentence 3.2.3.20.(2), if buildings are connected by a walkway, each building shall be separated from the walkway by a fire separation with a fire-resistance rating not less than 45 min.
Except as permitted by Sentence (3), a walkway connected to a building required to be of noncombustible construction shall also be of noncombustible construction.
per cent
of the area of any enclosing perimeter walls is open to the outdoors, and

A walkway of noncombustible construction used only as a pedestrian thoroughfare need not conform to the requirements of Articles 3.2.3.14. and 3.2.3.15.3.2.3.20. Underground Walkway

Buildings connected by an underground walkway shall be separated from the walkway by a fire separation with a fire-resistance rating not less than 1 h.
An underground walkway shall be of noncombustible construction suitable for an underground location.
In an underground walkway3.2.3.21. Storage and Process Equipment Located Outdoors
Fire By-law
. 
3.2.3.22.
Installation of Service Lines Under Buildings
When a building is erected over existing buried flammable gas mains, such service lines shall be encased in
gas-tight conduits in conformance with CSA Z662, “Oil and Gas Pipeline Systems.”
3.2.4. Fire Alarm and Detection Systems
(See Appendix A.)3.2.4.1. Determination of Requirement for a Fire Alarm System
Except as permitted in
Sentences (2), (3), (5), (6) and (7)
, a fire alarm system shall be installed in buildings in which an automatic sprinkler system is required by this Part.

Buildings in which a sprinkler system is installed in accordance with NFPA 13D, “Installation of Sprinkler Systems in One- and Two-Family Dwellings and
Manufactured Homes,” need not comply with Sentence (1). 
Buildings that contain fewer than 9 sprinklers conforming to Sentence 3.2.5.12.(4) need not comply with Sentence (1).
a school, college, child care facility, including a daycare facility for children, with an occupant load more than 40,

Deleted
has direct access to an exterior exit facility leading to ground level, a fire alarm system is not required if
Deleted
provided each suite has direct access to an exterior exit facility leading to ground level.

A fire alarm system is not required in a storage garage conforming to Article 3.2.2.88. that is contained in a building that is not sprinklered provided there are no other occupancies in the building. 3.2.4.2. Continuity of Fire Alarm System

Except as permitted by Sentence (6),
if there are openings through a firewall, other than those for piping, tubing, wiring and totally enclosed noncombustible raceways, the requirements in this Subsection shall apply to the floor areas on both sides of the firewall as if they were in the same building.
Except as permitted by Sentence (4), if a building contains more than one major occupancy and a fire alarm system is required, a single system shall serve all occupancies.
Except as permitted by Sentence (4), if a fire alarm system is required in any portion of a building, it shall be installed throughout the building.
Except as required by Sentence (5), the requirements in this Subsection are permitted to be applied to each portion of a building not more than 3 storeys in building height, in which a vertical fire separation having a fire-resistance rating not less than 1 h separates the portion from the remainder
of the building as if it were a separate building, provided there are no openings through the fire separation, other than those for piping, tubing, wiring and totally enclosed noncombustible raceways.
The permission in Sentence (4) to consider separated portions of a building as separate buildings does not apply to service rooms and storage rooms. 
Buildings interconnected by walkways permitted in Articles 3.2.3.19. and 3.2.3.20. or by vestibules provided in conformance with Article 3.2.6.3. shall be treated as separate buildings for the purpose of fire alarm installation required by this Subsection.
3.2.4.3. Types of Fire Alarm Systems
A fire alarm system shall be
Group B, Division 3 occupancy where the
building is 3 storeys or less in building height, and 3.2.4.4. Description of Fire Alarm Systems
A single stage fire alarm system shall, upon the operation of any manual station, waterflow detecting device, or fire detector, cause an alarm signal to sound on all audible signal devices in the system. (See Appendix A.)
A 2-stage fire alarm system shall
A 2-stage fire alarm system is permitted to be zone coded so that, upon the operation of any manual station, waterflow detecting
device, or fire detector,
If a second manual station, waterflow detecting device, or fire detector is operated in a fire alarm system with zone coding as permitted by Sentence (3), in a zone other than that for which the first alert signal was sounded, the coded alert signal for the first zone shall be completed before the coded alert signal for the second zone is repeated not less than 4 times.
3.2.4.5. Installation and Verification of Fire Alarm Systems


3.2.4.6.
Commissioning of Life Safety and Fire Protection Systems
By-law
or the
Fire By-law
, the commissioning of these integrated systems must be performed as a whole to ensure the proper
operation and inter-relationship between the systems. (See Appendix A.)

3.2.4.7. Silencing of Alarm Signals
A fire alarm system shall be designed so that when an alarm signal is actuated, it cannot be silenced automatically before a period of time has elapsed that is not less
than
Except as permitted by Sentence 3.2.4.19.(7) and Sentences 3.2.4.22.(3) and (4), a fire alarm system shall not incorporate manual silencing switches other than those installed inside the fire
alarm control unit. (See Appendix A.)
A manual silencing switch, accessible only to authorized personnel, shall be installed inside of the annunciator described in Sentence 3.2.4.9.(1). (See Appendix A.)
3.2.4.8. Signals to Fire Department
A single stage fire alarm system installed in a building of assembly occupancy that has an occupant load more than 300 shall be designed to notify the fire department, in conformance
with Sentence (4), that an alarm signal has been initiated.
A fire alarm system that includes waterflow-indicating devices shall be designed to notify the fire department in conformance with Sentence (4) when an alarm is initiated.
A 2-stage fire alarm system shall be designed to notify the fire department, in conformance with Sentence (4), that an alert signal has been initiated.
Notification of the fire department, as required by Sentences (1), (2) and (3), shall be provided in conformance with CAN/ULC-S561, “Installation and Services for Fire Signal Receiving Centres and Systems.” (See Appendix A.)
Where a single stage fire alarm system is installed in a building that is not sprinklered throughout and Sentence (1) does not apply, a legible notice that is not easily removed shall be affixed
to the wall near each manual station stating
Helicopter landing areas on roofs shall be provided with telephone extensions or means to notify the fire department.
3.2.4.9. Annunciator and Zone Indication
Except as permitted by Sentences (3) to (5), an annunciator shall be installed in close proximity to a building entrance that faces a street or an access route for fire department vehicles that complies with Sentence 3.2.5.5.(1).
Sentences (6), (8), (9) and (10)
, the annunciator required by Sentence (1) shall have separate zone indication of the actuation of the alarm initiating devices
, smoke detectors, heat detectors, manual stations and waterflow detecting devices,
in each
fire extinguishing system required by NFPA 96, “Ventilation Control and Fire Protection of Commercial Cooking Operations,”


An annunciator need not be provided for a fire alarm system if not more than one zone indicator is required by Sentence (2).
If an annunciator is not installed as part of a fire alarm system in conformance with Sentence (1), a visual and audible trouble signal device shall be provided inside the main
entrance of the building. 
The area limits of Clause (2)(a) are waived for an interior undivided open space used as an arena, a rink, or a swimming pool provided that other spaces in the building that are separated from the open space are individually zoned in accordance with the requirements of Sentence (2).
A fire alarm control unit installed in close proximity to a building entrance that faces a street or an access route for fire department vehicles that complies with Sentence 3.2.5.5.(1) is deemed to satisfy the requirement for an annunciator, provided all indicators required for
an annunciator or trouble signal device are included on the control
unit.
If a fire alarm system is required in row housing or in residential buildings where the egress of the dwelling units conforms to Sentence 3.3.4.4.(3) and the building is no more than 4 storeys in building height, the building shall be provided with
3.2.4.10. Electrical Supervision
If a fire alarm system in a building is required to have an annunciator by Sentence 3.2.4.9.(1), except for hose valves, all valves controlling water supplies in a standpipe system shall be equipped with
an electrically supervised switch for transmitting a trouble signal to the
annunciator in the event of movement of the valve handle.

trouble
signal on the building fire alarm system annunciator for each of the following:

A fire pump shall be electrically supervised as stipulated in NFPA 20, “Installation of Stationary Pumps for Fire Protection.”
A trouble signal indicating the nature of the trouble in accordance with Sentence (3) shall be transmitted to a Fire Signal Receiving Centre conforming to CAN/ULC-S561, “Installation and Services for Fire Signal Receiving Centres and Systems” as provided for in Sentence 3.2.4.8.(4).

3.2.4.11. Fire Detectors
Except as permitted by Sentence (3), if a fire alarm system is required in a building that is not sprinklered, fire detectors shall be installed in the following spaces:
Fire detectors required by Sentence (2) need not be provided within floor areas that are sprinklered.
Fire detectors required by Sentence (2) shall be installed in elevator hoistways and dumbwaiter shafts where a sprinkler system is not installed within the hoistway or shaft.

3.2.4.12. Smoke Detectors
except as permitted in Sentence (2),
each sleeping room and each corridor serving as part of a means of egress from sleeping rooms in portions of a building classified as a Group B major occupancy,
other than those serving only a Group A, Division 4 occupancy or an open storage garage
,
elevator machine rooms
, and 


Smoke detectors need not be installed in sleeping rooms and in corridors serving the sleeping rooms within
a suite of care occupancy where smoke alarms are installed in accordance with Article 3.2.4.21.
Smoke detectors required in the sleeping rooms of a care,
treatment
or detention occupancy shall, upon actuation, provide an audible and visible signal to staff serving those rooms
so that the room or location containing the actuated smoke detector can be easily identified. (See Appendix A.) 
Smoke detectors required in Clause (1)(g) shall, upon actuation, recall the elevators served by the elevator machine room in which the smoke detector is installed.
Except as permitted in Sentences (6) and (7), smoke detectors installed in buildings required to be equipped with a fire alarm system shall be located near the entrance to walkways described in Articles 3.2.3.19. and 3.2.3.20. or vestibules provided in conformance with Article 3.2.6.3.
Smoke detectors installed at the entrance to the walkways in conformance with Article 3.1.8.12. shall be deemed to meet the requirements of Sentence (5).
Smoke detectors required by Sentence (5) may be replaced with fire detectors in Group F occupancies where the smoke detectors may be subjected to false alarms due to the activities within the building.
3.2.4.13. Prevention of Smoke Circulation
If a fire alarm system is installed, an air-handling system shall be designed to prevent the circulation of smoke upon a signal
from a duct-type smoke detector if the air-handling system3.2.4.14. Vacuum Cleaning System Shutdown
A central vacuum cleaning system in a building equipped with a fire alarm system shall be designed to shut down upon actuation of the fire alarm system.
3.2.4.15. Elevator Emergency Return
Deleted.

Deleted.

3.2.4.16. System Monitoring

Waterflow-detecting devices required by Sentence (1) shall be connected to the fire alarm system so that, upon its actuation, an alert signal or an alarm signal is initiated.
The actuation of each waterflow detecting device required by Sentence (1) shall be indicated separately on the fire alarm system annunciator.
3.2.4.17. Manual Stations
, and 

In a building that is sprinklered throughout, a manual station is not required at an exterior egress doorway from a suite that does not lead to an interior shared means of egress in a hotel or motel not more than 3 storeys in building height, provided each suite is served by an exterior exit facility leading directly to ground level.
In a building that is sprinklered throughout, a manual station is not required at an exterior egress doorway from a dwelling unit that does not lead to an interior shared means of egress in a building not more than 3 storeys in building height containing only dwelling units, provided each dwelling unit is served by an exterior exit facility leading directly to ground level.
In a building referred to in Sentences (2) or (3), manual stations shall be installed near doorways leading from shared interior corridors to the exterior.

Where a fire alarm system is installed, a manually operated fire alarm station shall be installed on the roof at each exit from a helicopter landing area.
3.2.4.18. Alert and Alarm Signals
In a 2-stage fire alarm system described in Sentence 3.2.4.4.(2), the same audible signal devices are permitted to be used to sound the alert signals and the alarm signals.
If audible signal devices with voice reproduction capabilities are intended for paging and similar voice message use, other than
during a fire emergency, they shall be installed so that alert signals and alarm signals take priority over all other signals.
Audible signal devices forming part of a fire alarm or voice communication system shall not be used for playing music or background
noise.
3.2.4.19. Audibility of Alarm Systems
(See Appendix A.)
Audible signal devices forming part of a fire alarm system shall be installed in a building so that
alert signals are clearly audible in continuously staffed locations, and where there
are no continuously staffed locations, throughout the floor area.
The sound pattern of an alarm signal shall conform to the temporal pattern defined in Clause 4.2 of ISO 8201, “Acoustics – Audible emergency evacuation signal.” (See Appendix A.)
The sound patterns of alert signals shall be significantly different from the temporal patterns of alarm signals. (See Appendix A.)
The fire alarm signal sound pressure level shall be not more than 110 dBA in any normally
occupied area. (See Appendix A.)
The sound pressure level in a sleeping room from a fire alarm audible signal device shall be not less than 75 dBA in
a building of residential
or care occupancy
when any intervening doors between the device and the sleeping room are closed. (See Appendix A.)
Except as required by Sentence (5), the sound pressure level from a fire alarm system’s audible signal device within a floor area shall be not less than 10 dBA above the ambient noise level without being less than 65 dBA.
Except as permitted by Sentence (11), audible signal devices located within a dwelling unit shall include a means for them to be manually silenced for a period of not more than 10 min, after
which time the devices shall restore themselves to normal operation.
(See Appendix A.)
or care occupancy
shall be connected to the fire alarm system
or short circuit
at one device will not impair the operation of other audible signal devices on that same circuit that serve the
other dwelling units or suites of residential
or care occupancy
, or
or care occupancy
. 
Deleted.

Audible signal devices shall be installed in a service space referred to in Sentence 3.2.1.1.(8) and shall be connected to the fire alarm system.
Audible signal devices within dwelling units that are wired on separate signal circuits need not include
a means for silencing as required by Sentence (7) provided the fire alarm system includes a provision for an automatic signal silence within dwelling units, where
If a 2-stage fire alarm system has been installed with an automatic signal silence as described in Sentence (11), the system shall be designed so that any silenced audible signal devices serving dwelling units are reactuated whenever an alarm signal is required to be transmitted as part of the second stage. (See A-3.2.4.19.(7) in Appendix A.)3.2.4.20. Visual Signals

Visual signal devices shall be installed in addition to audible signal devices
Visual signal devices required by
Sentence (1)
shall be installed so that the signal from at least one device is visible throughout the floor area or portion thereof in which they are installed. (See Appendix A.)
Sentence (2)
shall consist of strobe lights
conforming to ULC-S526 “Standard for Visible Signal Devices for Fire Alarm Systems” that are designed to operate as part of the building fire alarm system
Deleted.
Deleted.
Deleted.

Deleted.

strobe lights that conform to ULC - S526 “Standard for Visible Signal Devices for Fire Alarm Systems” shall be connected to and activated by smoke alarms required by Sentence (1) and Article 9.10.19.1., in locations described in Articles 3.8.2.27. to 3.8.2.31.,
installed in each
and
cover plates required by Sentence 3.8.2.27.(3)
shall
be
designed and wired specifically to allow strobe lights to operate as required by
installed in each

20 per cent of the dwelling units in the building
are in use. 3.2.4.21. Smoke Alarms
Except as required by Sentence (4) and permitted by Sentence (7),
smoke alarms conforming to
CAN/ULC-S531, “Standard for Smoke-Alarms,”
shall be installed in each dwelling unit and, except for
care, treatment or detention occupancies
required to have a fire alarm system, in each sleeping room not within a dwelling unit
or suite of care occupancy
. 
At least one smoke alarm shall be installed on each storey of a dwelling unit
or suite of care occupancy
.
On any storey of a dwelling unit containing sleeping rooms, a smoke alarm shall be installed
in each sleeping room, and

Where a care occupancy has individual suites for residents, a smoke alarm shall be installed
A smoke alarm shall be installed on or near the ceiling.

Except as permitted in Sentence (7), smoke alarms referred in Sentence (1) shall
in case the regular power supply to the smoke alarm is interrupted, be provided with a battery as an alternative power source that can continue to provide
power to the smoke alarm for a period of no less than 7 days in the normal condition, followed by 4 minutes of alarm.
A suite of residential occupancy is permitted to be equipped with smoke detectors in lieu of smoke alarms, provided the smoke detectors


If more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be wired so that the actuation of one smoke alarm will cause all smoke alarms within the dwelling unit to sound.
A smoke alarm required by Sentence (1) shall be installed in conformance with CAN/ULC-S553, “Installation of Smoke-Alarms.”
Except as permitted in Sentence (12), a
manually operated silencing device shall be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that it will silence the signal emitted by the smoke alarm for a period of not more than 10 min, after which the smoke alarm will reset and again sound the alarm if the level of smoke in the vicinity is sufficient to reactuate the smoke alarm.
Suites of residential occupancy equipped with smoke detectors installed to CAN/ULC-S524, “Installation of Fire Alarm Systems,” as part of the fire alarm system in lieu of smoke alarms as permitted by Sentence (7), need not incorporate the manually operated device required in Sentence (11). (See A-3.2.4.21.(7) in Appendix A.)

The sound patterns of smoke alarms shall
be a combination temporal pattern and voice relay.
3.2.4.22. Voice Communication Systems
A voice communication system required by Subsection 3.2.6.
and Sentences (7) to (10)
shall consist of
from each floor area
, and 
The voice communication system described in Clause (1)(b) shall be capable of broadcasting prerecorded, synthesized, or live messages with voice intelligibility
meeting or exceeding the equivalent of a common intelligibility scale
score of 0.70. (See Appendix A.)
The voice communication system referred to in Sentence (1) shall include a means to silence the alarm signal in a single stage fire alarm system while voice instructions are being transmitted, but only after the alarm signal has initially sounded for not less than 30 s.
The voice communication system referred to in Sentence (1) shall include a means to silence the alert signal and the alarm signal in a 2-stage fire alarm system while voice instructions are being transmitted, but only after the alert signal has initially sounded for not less than
alert or
alarm signal in a
Deleted
fire alarm system can be selectively transmitted to any zone or zones while maintaining an alert signal or selectively transmitting voice instructions to any other zone or zones in the building. 
The 2-way communication system referred to in Clause (1)(a) shall be installed so that emergency telephones are located in each floor area near exit stair shafts. 
Except for Group B, Division 1 and Group F, Division 1 major occupancies, where a fire alarm system is required under Subsection 3.2.4., a voice communication
system shall be installed in buildings where a 2-stage fire alarm system is installed and whose occupant load exceeds 1 000.
A voice communication system required by Sentence (7) shall consist of loudspeakers that are
Where the facility is not equipped with staff trained to provide instructions over the loudspeakers, a pre-recorded message shall be
provided.


3.2.5. Provisions for Firefighting
(See A-3 in Appendix A.)3.2.5.1. Access to Above-grade Storeys
Except for storeys below the first storey, direct access for firefighting shall be provided from the outdoors to every storey that is not sprinklered throughout and whose floor level is less than 25 m above grade, by at least one unobstructed window or access panel for each 15 m of wall in each wall required
to face a street by Subsection 3.2.2.
An opening for access required by Sentence (1) shall
Access panels above the first storey shall be readily openable from both inside and outside, or the opening shall be glazed with plain glass.
Where locking devices to prevent access to floor areas are installed on exit doors
3.2.5.2. Access to Basements
Direct access from at least one street shall be provided from the outdoors in a building that is not sprinklered to each basement having a horizontal dimension more than 25 m.
The access required by Sentence (1) is permitted to be provided by3.2.5.3. Roof Access
On a building more than 3 storeys in building height where the slope of the roof is less than 1 in 4, all main roof areas shall be provided with direct access from the floor areas immediately below, either by3.2.5.4. Access Routes
Every building shall be provided with fire department access route(s)

3.2.5.5. Location of Access Routes
and Paths of Travel
(See Appendix A.)
Except as provided by Sentences (2) and (3), access routes required by Article 3.2.5.4. shall be located so that every access opening required by Articles 3.2.5.1. and 3.2.5.2. is no less than 3 m and no more than 15 m from the closest portion of the access route, measured horizontally to the face of
the building. (See Appendix A)

Paths of travel for firefighters shall not be more than



3.2.5.6.
Design of Access Routes and Paths of Travel


The unobstructed path of travel for firefighters from the curb to the main entrance or suite entrance door as required in Sentences 3.2.5.5.(1) to (3) and every access opening as required in Articles 3.2.5.1. and 3.2.5.2. shall be

3.2.5.7. Water Supply
Every building shall be provided with an adequate water supply for firefighting. (See Appendix A.)
that
are sprinklered throughout with a sprinkler system conforming to
Article 3.2.5.12.
or have a standpipe system conforming to Article 3.2.5.9. to 3.2.5.11. need not comply with Sentence 3.2.5.7.(1). 
3.2.5.8. Standpipe Systems
Except as permitted by Sentence 3.2.5.9.(4), a standpipe system shall be installed in a building that is| Table 3.2.5.8. Building Limits without Standpipe Systems Forming part of Sentence 3.2.5.8.(1) | |||
|
Occupancy Classification |
Building Area, m2 | ||
|
1 storey |
2 storeys |
3 storeys | |
| Group A | 2 500 | 2 000 | 1 500 |
| Group C | 2 000 | 1 500 | 1 000 |
| Group D | 4 000 | 3 000 | 2 000 |
| Group F, Division 2 | 1 500 | 1 500 | 1 000 |
| Group F, Division 3 | 3 000 | 2 000 | 1 000 |
3.2.5.9. Standpipe System Design
to (8)
and Articles 3.2.5.10. and 3.2.5.11. and Sentence 3.2.4.10.(2), the design, construction, installation and testing of a standpipe system shall conform to NFPA 14, “Installation of Standpipe and Hose Systems.” 
A dry standpipe that is not connected to a water supply shall not be considered as fulfilling the requirements of this Article.
A standpipe need not be installed in a storage garage conforming to Article 3.2.2.88. provided the building is not more than 15 m high. 
If a standpipe system is required by Sentence 3.2.5.8.(1) and an exit stair shaft is not provided in the building, a standpipe system may be omitted if

A standpipe system may be omitted from dwelling units where
3.2.5.10. Hose Connections
Hose connections shall be located in exits, in accordance with NFPA 14, “Installation of Standpipe and Hose Systems.”
Hose connections are not required within a floor area.
Hose connections shall be provided with sufficient clearance to permit the use of a standard fire department hose key.
Except as permitted by Sentence (5), 64 mm diam hose connections shall be installed in a standpipe system.

3.2.5.11. Hose Stations
Hose stations for 38 mm diam hose shall be installed for a standpipe system in a building that is not sprinklered throughout.
Hose stations for a 38 mm diam hose shall be installed for a standpipe system within every floor area that is not sprinklered throughout. (See Appendix A.)
Hose stations shall be located in the floor area within 5 m of exits and at other locations to provide coverage of the entire floor area.
A hose station located on one side of a horizontal exit shall be considered to serve only the floor area on that side of the horizontal exit.
A hose cabinet shall be located so that its door, when fully opened, will not obstruct the required width of a means of egress. 
Where a building or part thereof is used as a distillery and the building is sprinklered in conformance with Article 3.2.5.12., small hose (38 mm) stations are permitted to be supplied from interior sprinkler piping.
Where a hose station is provided in grain handling and storage facilities in which combustible dusts are produced in quantities or concentrations that create an explosion or fire hazard, fog and fine spray nozzles shall be used instead of
nozzles that discharge a solid stream of water to prevent combustible dusts from being raised into suspension.
3.2.5.12. Automatic Sprinkler Systems

Instead of the requirements of Sentence (1), NFPA 13R, “Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies”, is permitted to be used for the design, construction and installation of an automatic sprinkler system installed
Group C major occupancy containing no other major occupancies, that


Instead of the requirements of Sentence (1), NFPA 13D, “Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes,” is permitted to be used for the design, construction, installation and testing of an automatic sprinkler system installed

If a building contains fewer than 9 sprinklers, the water supply for these sprinklers is permitted to
be supplied from the domestic water system for the building provided the required flow for the sprinklers can be met by the domestic system.



Notwithstanding Sentences (1) and (2) and except as permitted by Sentence (10), automatic sprinkler protection shall be provided for all unenclosed balconies, exterior
decks, porches and patios of buildings sprinklered to NFPA 13R or NFPA 13 if
Notwithstanding the requirements of the standards referenced by Sentence (3) regarding the installation of automatic sprinkler systems, sprinklers shall be provided in any storage garage attached to a building of residential occupancy where a fire separation is not provided between the storage garage and adjacent floor areas.
3.2.5.13. Combustible Sprinkler Piping
Combustible sprinkler piping shall be used only for wet systems in residential occupancies and other light-hazard occupancies. (See Appendix A.)
Combustible sprinkler piping shall meet the requirements of ULC/ORD-C199P, “Combustible Piping for Sprinkler Systems.”
Except as permitted by Sentence (5), combustible sprinkler piping may be located above a ceiling provided that the distance between the edge
of any ceiling opening that is not protected in conformance with Sentence (3) and the nearest sprinkler is not more than 300 mm.
Where combustible sprinkler piping has been tested in conformance with ULC/ORD-C199P, “Combustible Piping for Sprinkler Systems,” and has been shown to meet the requirements therein without additional protection, conformance to Sentences (3) and (4) is not required. 3.2.5.14. Sprinklered Service Space


The waterflow detecting devices required by Sentence (2) shall be connected to the fire alarm system, to3.2.5.15. Fire Department Connections
(see Appendix A)
horizontally within 5 m of the principal entrance of a building, have unobstructed access and be visible from the street.

horizontally within 5 m of the principal entrance of a building, have unobstructed access and be visible from the street.

3.2.5.16. Portable Fire Extinguishers
Fire By-law
. 
In a Group B, Division 1 major occupancy, portable fire extinguishers are permitted to be located in secure areas, or in lockable cabinets provided3.2.5.17. Protection from Freezing
Equipment forming part of a fire protection system shall be protected from freezing if3.2.5.18. Fire Pumps
If a fire pump is installed, it shall be installed in accordance with the requirements of NFPA 20, “Installation of Stationary Pumps for Fire Protection.” (See Appendix A.)3.2.5.19.
Location of Building Safety Facilities for Firefighters

3.2.6. Additional Requirements for High Buildings
(See Appendix B.)3.2.6.1. Application
This Subsection applies to a building

3.2.6.2. Limits to Smoke Movement
A building to which this Subsection applies shall be designed in accordance with Sentences (2) to (5) and Article 3.2.6.3. to limit the danger to occupants and firefighters from exposure to smoke in a building fire.
per cent
by volume of contaminated air from the fire floor, assuming an outdoor temperature equal to the January design
temperature on a 2.5
per cent
basis determined in accordance with Subsection 1.1.3. (See Appendix B.) 
Each stairway that serves storeys above the lowest exit level shall have a vent to the outdoors, at or near the bottom of the stair shaft, that
Measures shall be taken to limit movement of smoke from a fire in a floor area below the lowest exit storey into upper storeys. (See Appendix B.)
Except for exhaust fans in kitchens, washrooms and bathrooms in dwelling units, and except for fans used for smoke venting as required by Article 3.2.6.6., air moving fans in a system that serves more than 2 storeys shall be designed and installed so that in the event of a fire these fans can be stopped by means of a manually operated
switch at the central alarm and control facility.
3.2.6.3. Connected Buildings
If a building described in Article 3.2.6.1. is connected to any other building, measures shall be taken to limit movement of contaminated air from one building into another during a fire. (See Appendix B.)3.2.6.4. Emergency Operation of Elevators
Automatic and manual
emergency recall shall be provided for all elevators serving storeys above the first storey. 
Key-operated switches for emergency recall required by Sentence (1) shall be provided in a conspicuous location at
Keys to operate the switches required by Sentences (2) and (3) shall be
The automatic emergency recall provided in accordance with Sentence (1) shall be activated by
3.2.6.5. Elevator for Use by Firefighters
At least one elevator shall be provided for use by firefighters in conformance with Sentences (2) to (6).
The elevator referred to in Sentence (1) shall have a useable platform area not less than 2.2 m2 and shall be capable of carrying a load of 900 kg to the top floor that it serves from a landing on the storey containing the entrance for firefighter access referred to in Articles 3.2.5.4. and 3.2.5.5. within 1 min.
Each elevator for use by firefighters shall
Except as permitted by Sentence (5), an elevator referred to in Sentence (1) shall be capable of providing transportation from the storey containing the entrance for firefighter access referred to in Articles 3.2.5.4. and 3.2.5.5. to every floor that is above grade in the building and that is normally served by the elevator system.
If it is necessary to change elevators to reach any floor referred to in Sentence (4), the system shall be designed so that not more than one change of elevator is required
when travelling to any floor in the building from the storey containing the entrance for firefighter access referred to in Articles 3.2.5.4. and 3.2.5.5.
Deleted.

3.2.6.6. Venting to Aid Firefighting
Means of venting each floor area to the outdoors shall be provided by windows, wall panels, smoke shafts,
or the building exhaust system. (See Appendix B.)
Fixed glass windows shall not be used for the venting required by Sentence (1) if the breaking of the windows could endanger pedestrians below.
Openable windows used for the venting required by Sentence (1) shall be permanently marked so that they are easily identifiable.
Elevator hoistways shall not be designed for the venting required by Sentence (1). 3.2.6.7. Central Alarm and Control Facility
A central alarm and control facility shall be provided on the storey containing the entrance for firefighter access referred to in Articles 3.2.5.4. and 3.2.5.5. in a location that
and standpipe
system supervisory signals and trouble signals,

3.2.6.8. Voice Communication System
A voice communication system or systems conforming to Article 3.2.4.22. shall be provided in all buildings conforming to Article 3.2.6.1.

3.2.6.9. Testing
The systems for control of smoke movement and mechanical venting required by Articles 3.2.6.2. and 3.2.6.6. shall be tested to ensure satisfactory operation. (See Appendix B.)3.2.7. Lighting and Emergency Power Systems
3.2.7.1. Minimum Lighting Requirements
An exit, a public corridor, or a corridor providing access to exit for the public or serving patients’ sleeping rooms or classrooms shall be equipped to provide illumination to an average level not less than 50 lx at floor or tread level and at angles and intersections at changes of level where
there are stairs or ramps.
Rooms and spaces used by the public shall be illuminated as described in Article 9.34.2.7.
Lighting outlets in a building of residential occupancy shall be provided in conformance with Subsection 9.34.2.3.2.7.2. Recessed Lighting Fixtures
A recessed lighting fixture shall not be located in an insulated ceiling unless the fixture is designed for this type of installation.
3.2.7.3. Emergency Lighting
corridors serving sleeping rooms in a care occupancy, except corridors serving sleeping rooms within individual suites of care occupancy,
floor areas or parts thereof
where persons are cared for that are within daycare facilities, including child care facilities,
and

Emergency lighting to provide an average level of illumination of not less than 10 lx at floor or catwalk level shall
be included in a service space referred to in Sentence 3.2.1.1.(8).
The minimum value of the illumination required by Sentences (1) and (2) shall be not less than 1 lx.
In addition to the requirements of Sentences (1) to (3), the installation of battery-operated emergency lighting in
buildings or part thereof where treatment is provided
shall conform to the appropriate requirements of CSA Z32, “Electrical Safety and Essential Electrical Systems in Health Care Facilities.”
3.2.7.4. Emergency Power for Lighting
An emergency power supply shall be
If self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141, “Emergency Lighting Equipment.”3.2.7.5. Emergency Power Supply Installation
Except as required by Articles 3.2.7.6. and 3.2.7.7., an emergency electrical power supply system shall be installed in conformance with CAN/CSA-C282, “Emergency Electrical Power Supply for Buildings.” (See Sentence 3.2.7.8.(1) for emergency electrical power supply for voice communication systems.)3.2.7.6. Emergency Power for
Treatment Occupancies
Except as required by Article 3.2.7.7., an emergency electrical power supply system for emergency equipment required by
this Part for
treatment occupancies
shall be installed in conformance with CSA Z32, “Electrical Safety and Essential Electrical Systems in Health Care Facilities.” (See Appendix A.) 3.2.7.7. Fuel Supply Shut-off Valves
If a liquid or gas fuel-fired engine or turbine for an emergency electric power supply is dependent on a fuel supply from outside the building, the fuel supply shall be provided with a suitably-identified separate shut-off valve outside the building. 3.2.7.8. Emergency Power for Fire Alarm Systems
Fire alarm systems, including those incorporating a voice communication system, shall be provided with an emergency power supply conforming
to Sentences (2), (3) and (4).
The emergency power supply required by Sentence (1) shall be supplied from
The emergency power supply required by Sentence (1) shall be capable of providing
The emergency power supply required by Sentence (1) shall be designed so that, in the event of a failure of the normal power source, there is an immediate automatic transfer
to emergency power with no loss of information.
3.2.7.9. Emergency Power for Building Services
18 m
high measured between grade and the floor level of the top storey and every elevator for firefighters in conformance with Sentence (2),
fans required by Clause 3.2.8.5.(1)(c) and Article 3.2.8.8. in buildings within the scope of Subsection 3.2.6.

Except as permitted by Sentence (3), the emergency power supply for elevators required by Clause (1)(a) shall be capable of operating all elevators for firefighters plus one additional elevator simultaneously.
Sentence (2) does not apply if the time to recall all elevators under emergency power supply is not more
than 5 min, each from its most remote storey to3.2.7.10.
Protection of Electrical Conductors
Electrical conductors in buildings required to conform to Subsection 3.2.6. or Sentence 3.2.7.9.(1), shall be protected against exposure to fire, for a period of no less than 1 h, from the source of the emergency power supply to the branch circuits serving equipment, if the electrical conductors serve
Except as otherwise required by Sentence (3) and permitted by this Article, electrical conductors that are used in conjunction with systems identified in Sentence (1) shall
Electrical conductors identified in Clause (1)(c) shall
The service spaces referred to in Clauses (2)(b) and (3)(b) shall not contain any combustible materials other than the conductors being protected.
Except as stated in Sentences (7) and (9), the electrical conductors referred to in Sentence (1) are those that extend from the source of emergency power to
If a fire alarm transponder or annunciator in one fire compartment is connected to a central processing unit or another transponder or annunciator located in a
different fire compartment, the electrical conductors connecting them shall be protected in accordance with Sentence (2).
Fire alarm system branch circuits within a storey that connect transponders and individual devices need not conform to Sentence (2). (See Appendix A.)
Except as permitted in Sentence (9), if a distribution panel supplies power to emergency lighting, the power supply conductors leading up to the distribution panel shall
be protected in accordance with Sentence (2).
Conductors leading from a distribution panel referred to in Sentence (8) to emergency lighting units in the same storey need not conform to Sentence (2).
3.2.8. Mezzanines and Openings through Floor Assemblies
3.2.8.1. Application
Except as permitted by Article 3.2.8.2. and Sentence 3.3.4.2.(3), the portions of a floor area or a mezzanine that do not terminate at an exterior wall, a firewall or a vertical shaft shall
The penetration of a floor assembly by an exit or a vertical service space shall conform to the requirements of Sections 3.4., 3.5. and 3.6.
A floor area containing sleeping rooms in a building of Group B, Division 2 major occupancy shall not be constructed as part of an interconnected floor space. 3.2.8.2. Exceptions to Special Protection
A mezzanine need not terminate at a vertical fire separation nor be protected in conformance with the requirements of Articles 3.2.8.3. to 3.2.8.9. provided the mezzanine
Except for floors referred to in Sentence 3.1.10.3.(1) and Article 3.2.1.2., openings through a horizontal fire separation for vehicular ramps in a storage garage are not required to be protected with closures and need not conform to this Subsection.
If a closure in an opening in a fire separation would disrupt the nature of a manufacturing process, such as a continuous flow of material from storey to storey, the closure for the opening is permitted to be omitted provided precautions are taken to offset the resulting hazard. (See Appendix A.)
An interconnected floor space in a Group B, Division 1 occupancy need not conform to the requirements of Articles 3.2.8.3. to 3.2.8.9. provided the interconnected floor space does not interconnect more than 2 adjacent storeys.
Except as permitted by Sentence (6), openings for escalators and inclined moving walks need not conform to the requirements in Articles 3.2.8.3. to 3.2.8.9. provided
An interconnected floor space need not conform to the requirements of Articles 3.2.8.3. to 3.2.8.9. provided3.2.8.3. Construction Requirements
A building constructed in conformance with Articles 3.2.8.4. to 3.2.8.9. shall be of noncombustible construction, except that heavy timber construction is permitted if Subsection 3.2.2. permits the building to be constructed of combustible construction. 3.2.8.4. Sprinklers
3.2.8.5. Vestibules
contain more than 1
per cent
by volume of contaminated air from the fire floor, assuming an outdoor temperature
equal to the January design temperature on a 2.5
per cent
basis determined in accordance with Subsection 1.1.3. (see Appendix A).

If an elevator hoistway opens into an interconnected floor space and into storeys above the interconnected floor space, either the elevator doors opening into the interconnected floor space or the elevator doors opening into the storeys above the interconnected floor space shall be protected by vestibules conforming to Sentence (1). 3.2.8.6. Protected Floor Space
A protected floor space used to satisfy the requirements of Clause 3.4.3.2.(6)(b) shall3.2.8.7. Draft Stops
A draft stop shall be provided at each floor level within an interconnected floor space, immediately adjacent to and surrounding the opening, and shall be not less than 500
mm deep measured from ceiling level down to the underside of
the draft stop.
3.2.8.8. Mechanical Exhaust System
A mechanical exhaust system shall be provided to remove air from an interconnected floor space at a rate of 4 air changes per hour. (See Appendix A.)
The mechanical exhaust system required by Sentence (1) shall be actuated by a switch located on the storey containing the entrance for firefighter access referred to in Articles 3.2.5.4. and 3.2.5.5. near the annunciator for the fire alarm system.
3.2.8.9. Combustible Content Limits
An interconnected floor space shall be designed so that the combustible contents, excluding interior finishes, in those parts of a floor area in which the ceiling is more than 8 m above the floor, are limited to not more than 16 g of combustible material for each cubic metre of volume of the interconnected floor space. 