Division B
Acceptable Solutions
Part 9 — Housing and Small Buildings
Section 9.15. Footings and Foundations
9.15.1. Application
9.15.1.1. General
(See Appendix A and A-9.4.4.6. and 9.15.1.1. in Appendix A.)
75 kPa or
greater, and
Foundations for applications other than as described in Sentence (1) shall be designed in accordance with Section 9.4.9.15.1.2. Permafrost
Buildings erected on permafrost shall have foundations designed by a designer competent in this field in accordance with the appropriate requirements of Part 4. 9.15.1.3. Foundations for Deformation-Resistant Buildings
Where the superstructure of a detached building conforms to the requirements of the deformation resistance test in Z240.2.1, “Structural Requirements for Manufactured Homes,” the foundation shall be constructed in conformance with9.15.2. General
9.15.2.1. Concrete
Concrete shall conform to Section 9.3.9.15.2.2. Unit Masonry Construction
Concrete block shall conform to CAN/CSA-A165.1, “Concrete Block Masonry Units,” and shall have a compressive strength over the average net cross-sectional area of the block of not less than 15 MPa.
Mortar, grout, mortar joints, corbelling and protection for unit masonry shall conform to Section 9.20.
For concrete block foundation walls required to be reinforced,9.15.2.3. Pier-Type Foundations
Where pier-type foundations are used, the piers shall be designed to support the applied loads from the
superstructure.
Where piers are used as a foundation system in a building of 1 storey in building height, the piers shall be installed to support the principal framing members
and shall be spaced not more than 3.5 m apart along the
framing, unless the piers and their footings are designed for larger
spacings.
The height of piers described in Sentence (2) shall not exceed 3 times their least dimension at the base of the pier.
Where concrete block is used for piers described in Sentence (2), they shall be laid with cores placed vertically, and where the width of the building is 4.3 m or less, placed with their longest dimension at right angles to the longest dimension of the building. 9.15.2.4. Wood-Frame Foundations
9.15.3. Footings
9.15.3.1. Footings Required
Footings shall be provided under walls, pilasters, columns, piers, fireplaces and chimneys that bear on soil or rock, except that footings may be omitted under piers or monolithic concrete walls
if the safe loadbearing capacity of the soil or rock is not exceeded. 9.15.3.2. Support of Footings
Granular fill shall not contain pyritic material in a concentration that will damage the building to a degree that would adversely affect its stability or the performance of assemblies. (See also Article 9.4.4.4. and A-9.4.4.4.(1) in Appendix A.) 9.15.3.3. Application of Footing Width and Area Requirements

Except as provided in Sentence 9.15.3.4.(2), where the span of the supported joists exceeds 4.9 m, footings shall be designed in accordance with Section 4.2.
Where the specified live load exceeds 2.4 kPa, footings shall be designed in accordance with Section 4.2.9.15.3.4. Basic Footing Widths and Areas
Except as provided in Sentences (2) and (3) and in Articles 9.15.3.5. to 9.15.3.7., the minimum footing width or area shall comply with Table 9.15.3.4.
Where the supported joist span exceeds 4.9 m in buildings with light wood-frame walls, floors and roofs, footing widths shall be determined according to
Where a foundation rests on gravel, sand or silt in which the water table level is less than the width
of the footings below the bearing surface,Table 9.15.3.4. Minimum Footing SizesForming part of Sentence 9.15.3.4.(1) | |||
| No. of Floors Supported |
Minimum Width of Strip Footings, mm |
Minimum Footing Area for Columns Spaced 3 m o.c.,(1) m2 | |
|
Supporting Exterior Walls(2) |
Supporting Interior Walls(3) | ||
| 1 |
250 |
200 |
0.4 |
| 2 |
350 |
350 |
0.75 |
| 3 |
450 |
500 |
1.0 ![]() |
| Notes to Table 9.15.3.4.: | |
|
|
|
| (1) | See Sentence 9.15.3.7.(1). |
| (2) | See Sentence 9.15.3.5.(1). |
| (3) | See Sentence 9.15.3.6.(1). |

9.15.3.5. Adjustments to Footing Widths for Exterior Walls

9.15.3.6. Adjustments to Footing Widths for Interior Walls

Footings for interior non-loadbearing masonry walls shall be not less than 200 mm wide for walls up to 5.5 m high and the width shall be increased
by 100 mm for each additional 2.7 m of height.
9.15.3.7. Adjustments to Footing Area for Columns
The footing area for column spacings other than shown in Table 9.15.3.4. shall be adjusted in proportion to the distance between columns.
9.15.3.8. Footing Thickness
Footing thickness shall be not less than the greater of9.15.3.9. Step Footings
Where step footings are used,9.15.4. Foundation Walls
9.15.4.1. Permanent Form Material
Insulating concrete form units shall be manufactured of polystyrene conforming to the performance requirements of CAN/ULC-S701, “Thermal Insulation, Polystyrene, Boards and Pipe Covering,” for Type 2, 3 or 4 polystyrene.
9.15.4.2. Foundation Wall Thickness and Required Lateral Support
Except as required in Sentence (2), the thickness of foundation walls made of unreinforced concrete block or solid concrete and subject to lateral
earth pressure shall conform to Table 9.15.4.2.A for walls not exceeding
3.0 m
in unsupported height.
| Table 9.15.4.2.A Thickness of Solid Concrete and Unreinforced Concrete Block Foundation Walls Forming part of Sentence 9.15.4.2.(1) | |||||
|
Type of Foundation Wall |
Minimum Wall Thickness, mm |
Maximum Height of Finished Ground Above Basement Floor or Crawl Space Ground Cover, m |
|||
|
Height of Foundation Wall Laterally Unsupported at the Top(1)(2) |
Height of Foundation Wall Laterally Supported at the Top(1)(2) | ||||
≤ 3.0 m![]() | ≤ 2.5 m![]() | > 2.5 m and ≤ 2.75 m ![]() | > 2.75 m and ≤ 3.0 m ![]() | ||
|
Solid concrete, 15 MPa min. strength |
150 | 0.8 | 1.5 | 1.5![]() | 1.4![]() |
| 200 | 1.2 | 2.15 | 2.15![]() | 2.1![]() | |
| 250 | 1.4 | 2.3 | 2.6![]() | 2.5![]() | |
| 300 | 1.5 | 2.3 | 2.6![]() | 2.85![]() | |
|
Solid concrete, 20 MPa min. strength |
150 | 0.8 | 1.8 | 1.6![]() | 1.6![]() |
| 200 | 1.2 | 2.3 | 2.3![]() | 2.2![]() | |
| 250 | 1.4 | 2.3 | 2.6![]() | 2.85![]() | |
| 300 | 1.5 | 2.3 | 2.6![]() | 2.85![]() | |
|
Unreinforced concrete block |
140 | 0.6 | 0.8 | — | — |
| 190 | 0.9 | 1.2![]() | (3) | (3)![]() | |
| 240 | 1.2 | 1.8 | (3)![]() | (3)![]() | |
| 290 | 1.4 | 2.2 | — | — | |
| Notes to Table 9.15.4.2.A: | |
|
|
|
| (1) | See Article 9.15.4.3.![]() |
| (2) | See Article 9.15.4.6.![]() |
| (3) | See Table 9.15.4.2.B![]() |
The thickness of concrete in flat insulating concrete form foundation walls shall be not less than the greater of
Foundation walls made of flat insulating concrete form units shall be laterally supported at the top and at
the bottom.
The thickness and reinforcing of foundation walls made of reinforced concrete block and subject to lateral earth pressure shall conform to Table 9.15.4.2.B and Sentences (5) to (8), where
the walls are laterally supported at the top,
Table 9.15.4.2.B Reinforced Concrete Block Foundation Walls Laterally Supported at the Top(1)Forming part of Sentence 9.15.4.2.(4) | ||||||
| Maximum Height of Finished Ground Above Basement Floor or Crawl Space Ground Cover, m(2) | Size and Spacing of Continuous Vertical Reinforcement, m at mm o.c. | |||||
| 190 mm Minimum Wall Thickness | 240 mm Minimum Wall Thickness | |||||
| Foundation Wall Height | Foundation Wall Height | |||||
| ≤ 2.5 m | ≤ 2.75 m | ≤ 3.0 m | ≤ 2.5 m | ≤ 2.75 m | ≤ 3.0 m | |
| 0.8 | (3) | (3) | (3) | (3) | (3) | (3) |
| 1 | (3) | 1-15M at 1 800 | 1-15M at 1 800 | (3) | (3) | (3) |
| 1.2 | (3) | 1-15M at 1 600 | 1-15M at 1 600 | (3) | 1-20M at 2 000 | 1-20M at 2 000 |
| 1.4 | 1-15M at 1 600 | 1-15M at 1 600 | 1-15M at 1 600 | (3) | 1-20M at 1 800 | 1-20M at 1 800 |
| 1.6 | 1-15M at 1 400 | 1-15M at 1 400 | 1-15M at 1 400 | (3) | 1-20M at 1 600 | 1-20M at 1 600 |
| 1.8 | 1-15M at 1 400 | 1-15M at 1 400 | 1-15M at 1 200 | (3) | 1-20M at 1 600 | 1-20M at 1 600 |
| 2 | 1-15M at 1 200 | 1-15M at 1 000 | 2-15M at 1 200 | 1-20M at 1 600 | 1-20M at 1 600 | 1-20M at 1 600 |
| or | ||||||
| 1-20M at 1 200 | ||||||
| 2.2 | 2-15M at 1 200 | 2-15M at 1 000 | 2-15M at 1 000 | 1-20M at 1 400 | 1-20M at 1 400 | 1-20M at 1 400 |
| 2.4 | 2-15M at 1 000 | 2-15M at 1 000 | 2-15M at 800 | 1-20M at 1 400 | 1-20M at 1 400 | 1-20M at 1 200 |
| 2.6 | n/a | 2-15M at 800 | 2-15M at 800 | n/a | 1-20M at 1 000 | 1-20M at 1 000 |
| or | or | |||||
| 1-25M at 1 000 | 1-25M at 1 000 | |||||
| 2.8 | n/a | n/a | 1-20M at 600 | n/a | n/a | 1-20M at 800 |
| or | ||||||
| 2-15M at 1 000 | ||||||
| 3 | n/a | n/a | 1-20M at 400 | n/a | n/a | 2-15M at 800 |
| or | ||||||
| 1-25M at 600 | ![]() | |||||
| Notes to Table 9.15.4.2.B: | |
|
|
|
| (1) | See Article 9.15.4.3. |
| (2) | See Article 9.15.4.6. |
| (3) | No reinforcement required. |
For concrete block walls required to be reinforced, continuous vertical reinforcement shall
For concrete block walls required to be reinforced, a continuous horizontal bond beam containing not less than one 15M bar shall be
installed
In concrete block walls required to be reinforced, all vertical bar reinforcement shall be installed along the centre line of the
wall.
In concrete block walls required to be reinforced, ladder- or truss-type lateral reinforcement not less than 3.8 mm in diameter (no. 9 ASWG) shall be installed in the bed joint of
every second masonry course.
9.15.4.3. Foundation Walls Considered to be Laterally Supported at the Top
Foundation walls shall be considered to be laterally supported at the top if
per cent
of the length of the wall. 
For the purposes of Sentence (3), the combined width of the openings shall be considered as a single
opening if the average width is greater than the width of solid wall
between them.
Flat insulating concrete form foundation walls shall be considered to be laterally supported at the top if the floor joists are installed according to Article 9.20.17.5.9.15.4.4. Foundation Walls Considered to be Laterally Supported at the Bottom
Flat insulating concrete form foundation walls shall be considered to be laterally supported at the bottom where the foundation wall9.15.4.5. Reinforcement for Flat Insulating Concrete Form Foundation Walls
Horizontal reinforcement in flat insulating concrete form foundation walls shall
Vertical reinforcement in flat insulating concrete form foundation walls shall be
Cold joints in flat insulating concrete form foundation walls shall be reinforced with no less than one 15M bar spaced at not more than 600 mm o.c. and embedded 300 mm on both sides of the joint.
Reinforcing around openings in flat insulating concrete form foundation walls shall comply with Article 9.20.17.3. or 9.20.17.4.| Table 9.15.4.5.A Vertical Reinforcement for 140 mm Flat Insulating Concrete Form Foundation Walls Forming part of Sentence 9.15.4.5.(2) | |||
|
Max. Height of Finished Ground Above Finished Basement Floor, m |
Minimum Vertical Reinforcement | ||
|
Maximum Unsupported Basement Wall Height |
|||
| 2.44 m | 2.75 m | 3.0 m | |
| 1.35 | 10M at 400 mm o.c. | 10M at 400 mm o.c. | 10M at 400 mm o.c. |
| 1.6 | 10M at 400 mm o.c. | 10M at 380 mm o.c. | 10M at 380 mm o.c. |
| 2 | 10M at 380 mm o.c. | 10M at 380 mm o.c. | 10M at 380 mm o.c. |
| 2.2 | 10M at 250 mm o.c. | 10M at 250 mm o.c. | 10M at 250 mm o.c. |
| 2.35 | n/a | 10M at 250 mm o.c. | 10M at 250 mm o.c. |
| 2.6 | n/a | 10M at 250 mm o.c. | 10M at 250 mm o.c. |
| 3 | n/a | n/a | 15M at 250 mm o.c. |
| Table 9.15.4.5.B Vertical Reinforcement for 190 mm Flat Insulating Concrete Form Foundation Walls Forming part of Sentence 9.15.4.5.(2) | |||
|
Max. Height of Finished Ground Above Finished Basement Floor, m |
Minimum Vertical Reinforcement | ||
|
Maximum Unsupported Basement Wall Height |
|||
| 2.44 m | 2.75 m | 3.0 m | |
| 2.2 | None required | 10M at 400 mm o.c. | 10M at 400 mm o.c. |
| 2.35 | n/a | 10M at 300 mm o.c. | 10M at 300 mm o.c. |
| 2.6 | n/a | 10M at 300 mm o.c. | 15M at 400 mm o.c. |
| 3.0 | n/a | n/a | 15M at 400 mm o.c. |
| Table 9.15.4.5.C Vertical Reinforcement for 240 mm Flat Insulating Concrete Form Foundation Walls Forming part of Sentence 9.15.4.5.(2) | |||
|
Max. Height of Finished Ground Above Finished Basement Floor, m |
Minimum Vertical Reinforcement | ||
|
Maximum Unsupported Basement Wall Height |
|||
| 2.44 m | 2.75 m | 3.0 m | |
| 2.2 | None required | None required | None required |
| 2.6 | n/a | 15M at 400 mm o.c. | 15M at 400 mm o.c. |
| 3.0 | n/a | n/a | 15M at 400 mm o.c. |
9.15.4.6. Extension above Ground Level
Exterior foundation walls shall extend not less than 150 mm above finished ground level.
9.15.4.7. Reduction in Thickness
Where the top of a foundation wall is reduced in thickness to permit the installation of floor joists,
the reduced section shall be not more than 350 mm high
and not less than 90 mm thick.
Where the top of a foundation wall is reduced in thickness to permit the installation of a masonry exterior
facing, the reduced section shall be
The space between wall and facing described in Sentence (2) shall be filled with mortar. 9.15.4.8. Corbelling
Corbelling of masonry foundation walls supporting cavity walls shall conform to Article 9.20.12.2.9.15.4.9. Crack Control Joints
Crack control joints shall be provided in foundation walls more than 25 m long at intervals of not more than 15 m.
Joints required in Sentence (1) shall be designed to resist moisture penetration and shall be keyed to prevent
relative displacement of the wall portions adjacent to the joint.
9.15.4.10. Interior Masonry Walls
Interior masonry foundation walls not subject to lateral earth pressure shall conform to Section 9.20.9.15.5. Support of Joists and Beams on Masonry Foundation Walls
9.15.5.1. Support of Floor Joists
Except as permitted in Sentence (2), foundation walls of hollow masonry units supporting floor joists shall be capped with not less than 50 mm of solid masonry or concrete, or have the top course
filled with mortar or concrete.
Capping required in Sentence (1) need not be provided9.15.5.2. Support of Beams
Not less than 190 mm depth of solid masonry shall be provided beneath beams supported on masonry.
Where the beam referred to in Sentence (1) is supported below the top of the foundation walls, the ends of such beams shall be protected from the weather.
9.15.5.3. Pilasters
Pilasters shall be provided under beams that frame into unit masonry foundation walls 140 mm or less in thickness.
Pilasters required in Sentence (1) shall be not less than 90 mm by 290 mm and shall be bonded or tied into the wall.
The top 200 mm of pilasters required in Sentence (1) shall be solid. 9.15.6. Parging and Finishing of Masonry Foundation Walls
9.15.6.1. Foundation Walls below Ground
Concrete block foundation walls shall be parged on the exterior face below ground level as required
in Section 9.13.9.15.6.2. Foundation Walls above Ground
Exterior surfaces of concrete block foundation walls above ground level shall have tooled joints, or shall be parged or otherwise suitably finished.