Division B
Acceptable Solutions
Part 9 — Housing and Small Buildings
Section 9.29. Interior Wall and Ceiling Finishes
9.29.1. General
9.29.1.1. Fire Protection and Sound Control
A wall or ceiling finish shall also conform to the appropriate requirements in Sections 9.10. and 9.11., in addition to the requirements
in this Section.
9.29.2. Waterproof Wall Finish
9.29.2.1. Where Required
Waterproof finish shall be provided to a height of not less than9.29.2.2. Materials
Waterproof finish shall consist of ceramic, plastic or metal tile, sheet vinyl, tempered hardboard, laminated thermosetting decorative
sheets or linoleum.
9.29.3. Wood Furring
9.29.3.1. Size and Spacing of Furring
Wood furring for the attachment of wall and ceiling finishes shall conform to Table 9.29.3.1.| Table 9.29.3.1. Size and Spacing of Furring Forming part of Sentence 9.29.3.1.(1) | |||
|
Maximum Spacing of Furring, mm (in.) |
Minimum Size of Furring, mm (in.) |
||
| Maximum Spacing of Furring Supports | |||
| Continuous Supports |
400 mm (in.) (o.c.) |
600 mm (in.) (o.c.) |
|
|
300 (12) |
19 x 38 (¾ x 1½) |
19 x 38 (¾ x 1½) |
19 x 64 (¾ x 2½) |
|
400 (16) |
19 x 38 (¾ x 1½) |
19 x 38 (¾ x 1½) |
19 x 64 (¾ x 2½) |
|
600 (24) |
19 x 38 (¾ x 1½) |
19 x 64 (¾ x 2½) |
19 x 89 (¾ x 3½) |
9.29.3.2. Fastening
9.29.4. Plastering
9.29.4.1. Application
Application of plaster wall and ceiling finishes, including installation of metal or gypsum lath, shall conform to CSA A82.30-M, “Interior Furring, Lathing and Gypsum Plastering.”9.29.5. Gypsum Board Finish (Taped Joints)
9.29.5.1. Application
The requirements for application of gypsum board in this Subsection apply to the single layer application of gypsum board to wood furring
or framing using nails or screws.
Gypsum board applications not described in this Subsection shall conform to CSA A82.31-M, “Gypsum Board Application.”9.29.5.2. Materials
Gypsum products shall conform to9.29.5.3. Maximum Spacing of Supports
Maximum spacing of supports for gypsum board applied as a single layer shall conform to Table 9.29.5.3.| Table 9.29.5.3. Spacing of Supports for Gypsum Board Forming part of Sentence 9.29.5.3.(1) | ||||
| Thickness, mm | Orientation of Board to Framing | Maximum Spacing of Supports, mm o.c. | ||
| Walls | Ceilings | |||
| Painted Finish | Water-Based Texture Finish | |||
| Gypsum board conforming to Sentence 9.29.5.2.(1) (except Sections 9 and 12 of ASTM C 1396/C 1396M | ||||
| 9.5 | parallel | — | — | — |
| perpendicular | 400 | 400 | — | |
| 12.7 | parallel | 600 | 400 | — |
| perpendicular | 600 | 600 | 400 | |
| 15.9 | parallel | 600 | 400 | — |
| perpendicular | 600 | 600 | 600 | |
|
Gypsum ceiling board conforming to Clause 9.29.5.2.(1)(c) (only Section 12 of ASTM C 1396/C 1396M |
||||
|
12.7 |
parallel |
600 |
400 |
— |
|
perpendicular |
600 |
600 |
600 |
|
9.29.5.4. Support of Insulation
9.29.5.5. Length of Fasteners
The length of fasteners for gypsum board shall conform to Table 9.29.5.5., except that lesser depths of penetration are permitted for assemblies required to have a fire-resistance rating provided it can be shown, on the basis of fire tests,
that such depths are adequate for the required rating.
| Table 9.29.5.5. Fastener Penetration into Wood Supports Forming part of Sentence 9.29.5.5.(1) | ||||
|
Required Fire-Resistance Rating of Assembly |
Minimum Penetration, mm (in.) |
|||
| Walls | Ceilings | |||
| Nails | Screws | Nails | Screws | |
| Not required |
20 |
15 |
20 |
15 |
|
45 min |
20 |
20 |
30 |
30 |
|
1 h |
20 |
20 |
45 |
45 |
|
1.5 h |
20 |
20 |
60 |
60 |
9.29.5.6. Nails
ASTM F1667, “Driven Fasteners: Nails, Spikes, and Staples,”
or 
9.29.5.7. Screws
Screws for fastening gypsum board to wood supports shall conform to ASTM C 1002, “Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs.”9.29.5.8. Spacing of Nails
For single-layer application on a ceiling, nails shall be spaced
Where the ceiling sheets are supported by the wall sheets around the perimeter of the ceiling, this support may be considered as equivalent
to nailing at this location.
Except as required by Sentence (4), for single-layer application on walls, nails shall be spaced
For single-layer application on walls, where gypsum board
provides required bracing in braced wall panels, lateral support for studs,
or fire protection, nails shall be spaced not more than 200 mm o.c. on9.29.5.9. Spacing of Screws
For single-layer application on a ceiling, screws shall be spaced not more than 300 mm o.c. on ceiling supports.
Where the ceiling sheets are supported by the wall sheets around the perimeter of the ceiling, this support may be considered as equivalent
to screwing at this location.
Except as required by Sentence (4), for single-layer application on walls, screws shall be spaced
Except as provided in Sentence (5), for single-layer application on walls, where gypsum board
provides required bracing in braced wall panels, lateral support for studs,
or fire protection, screws shall be spaced not more than 300 mm o.c. on
Where a fire-resistance rating is determined based on Table A-9.10.3.1.A in Appendix A, Sentence (4) need not apply for the purpose of fire protection.
9.29.5.10. Low Temperature Conditions
In cold weather, heat shall be provided to maintain a temperature not below 10°C for 48 h prior to taping
and finishing and maintained for not less than 48 h thereafter.
9.29.6. Plywood Finish
9.29.6.1. Thickness
Except as provided in Sentences (2) and (3), the minimum thickness of plywood interior finish shall conform to Table 9.29.6.1.| Table 9.29.6.1. Thickness of Plywood Interior Finish Forming part of Articles 9.29.6.1. and 9.29.6.2. | ||
| Maximum Spacing of Supports, mm o.c. |
Minimum Thickness, mm(1) | |
| On Supports with no Horizontal Blocking |
On Supports with Blocking at Vertical Intervals not Exceeding 1.2 m |
|
| 400 | 4.7 | 4.0 |
| 600 | 8.0 | 4.7 |
| Notes to Table 9.29.6.1.: | |
|
|
|
| (1) | Thickness limits shall apply to the net effective thickness (NET) of grooved, striated, textured and/or embossed panels and to the actual thickness of flat panels. |
A manufacturing tolerance of −0.4 mm may be applied to the thicknesses listed in Table 9.29.6.1.9.29.6.2. Grooved Plywood
Except as permitted in Sentence (2), where plywood for interior finish is grooved, the grooves shall not extend through the face ply and into the plies below the face
ply unless the groove is supported by framing or furring.
If the grain of the face ply is at right angles to the supporting members, the groove is permitted to extend into plies below the face
ply provided the thickness of the plywood exceeds the value shown
in Table 9.29.6.1. by an amount equal to not less than the depth of penetration of the grooves into the plies below the face
ply.
9.29.6.3. Nails and Staples

Except as provided in Sentence (2)
, nails for attaching plywood finishes shall not be less than 38 mm casing or finishing nails
spaced not more than 150 mm o.c. along edge supports
and 300 mm o.c. along intermediate supports, except that
staples providing equivalent lateral resistance may also be used.

Where plywood finish provides required bracing in braced wall panels, the plywood shall be fastened in accordance with the fastening requirements for sheathing
stated in Sentence 9.23.3.5.(2).
9.29.6.4. Edge Support
9.29.7. Hardboard Finish
9.29.7.1. Material Standard
Hardboard shall conform to CAN/CGSB-11.3-M, “Hardboard.”9.29.7.2. Thickness
Hardboard shall be not less than9.29.7.3. Nails
Nails for fastening hardboard shall be casing or finishing nails not less than 38 mm long, spaced not more than 150 mm o.c. along edge supports and 300 mm o.c.
along intermediate supports.
9.29.7.4. Edge Support
All hardboard edges shall be supported by furring, blocking or framing where the backing is not continuous.
9.29.8. Insulating Fibreboard Finish
9.29.8.1. Material Standard
CAN/ULC-S706, “Wood Fibre Insulating Boards for Buildings.”

9.29.8.2. Thickness
Insulating fibreboard sheets shall be not less than 11.1 mm thick on supports not more than 400 mm o.c.
Insulating fibreboard tile shall be not less than 12.7 mm thick on supports spaced not more than 400 mm o.c. 9.29.8.3. Nails
Nails for fastening fibreboard sheets shall be not less than 2.6 mm shank diameter casing or finishing nails of sufficient length to penetrate not less than 20 mm into the supports.
Nails shall be spaced not more than 100 mm o.c. along edge supports and 200 mm o.c. along intermediate
supports.
9.29.8.4. Edge Support
9.29.9. Particleboard, OSB or Waferboard Finish
9.29.9.1. Material Standard
Particleboard finish shall conform to ANSI A208.1, “Particleboard.”9.29.9.2. Minimum Thickness
Except as provided in Sentences (2) and (3), the minimum thickness of O-2 grade OSB used as an interior finish shall conform to that shown for plywood in Table 9.29.6.1.
Thicknesses listed in Table 9.29.6.1. shall permit a manufacturing tolerance of − 0.4 mm.
OSB conforming to O-1 grade, waferboard conforming to R-1 grade and particleboard shall be
OSB conforming to CAN/CSA-O325, “Construction Sheathing,” shall meet the minimum panel mark of9.29.9.3. Nails

Except as provided in Sentence (2),
nails for fastening particleboard, OSB or waferboard shall be not less than 38 mm casing or
finishing nails spaced not more than 150 mm o.c. along
edge supports and 300 mm o.c. along intermediate supports.

Where OSB or waferboard provides required bracing in braced wall panels, the OSB or waferboard shall be fastened in accordance with the fastening requirements for
sheathing stated in Sentence 9.23.3.5.(2).
9.29.9.4. Edge Support
9.29.10. Wall Tile Finish
9.29.10.1. Tile Application
9.29.10.2. Mortar Base
When ceramic tile is applied to a mortar base the cementitious material shall consist of one part Portland cement to not more than
one-quarter part lime by volume.
The cementitious material described in Sentence (1) shall be mixed with not less than 3 nor more than 5 parts of aggregate per part of cementitious material by volume.
Ceramic tile applied to a mortar base shall be thoroughly soaked and pressed into place forcing the mortar into the joints while the
tile is wet.
9.29.10.3. Adhesives
Adhesives to attach ceramic and plastic tile shall be applied to the finish coat or brown coat of plaster that has been steel-trowelled
to an even surface or to gypsum board or to masonry provided the masonry
has an even surface.
9.29.10.4. Moisture-Resistant Backing
Ceramic and plastic tile installed on walls around bathtubs or showers shall be applied over moisture-resistant backing.
9.29.10.5. Joints between Tiles and Bathtub
The joints between wall tiles and a bathtub shall be suitably caulked with material conforming to CAN/CGSB-19.22-M, “Mildew-Resistant Sealing Compound for Tubs and Tiles.”