Division B
Acceptable Solutions
Part 9 — Housing and Small Buildings
Section 9.30. Flooring
9.30.1. General
9.30.1.1. Required Finished Flooring
Finished flooring shall be provided in all residential occupancies. 9.30.1.2. Water Resistance
Where water permeable finished flooring in bathrooms, kitchens, public entrance halls and laundry areas is supported by a subfloor
of a type that would be damaged by water, such flooring shall be installed
over a membrane with a water permeance not exceeding 18 ng/(Pa•s•m2) when tested in accordance with ASTM E 96/E 96M, “Water Vapor Transmission of Materials.” (See Appendix A.) 9.30.1.3. Sleepers
Wood sleepers supporting finished flooring over a concrete base supported on the ground shall be not less than 19 mm by 38 mm and shall be treated with a wood preservative.
9.30.1.4. Finish Quality
Finished flooring shall have a surface that is smooth, even and free from roughness or open defects.
9.30.2. Panel-Type Underlay
9.30.2.1. Required Underlay

Panel-type underlay shall be provided under resilient flooring, parquet flooring, felted-synthetic-fibre floor coverings or carpeting
on panel-type subflooring whose edges are unsupported. (See Article 9.23.15.3.) 9.30.2.2. Materials and Thickness
Panel-type underlay shall be not less than 6 mm thick and shall conform to
Panel-type underlay under ceramic tile applied with adhesive shall be not less than9.30.2.3. Fastening
Panel-type underlay shall be fastened to the subfloor with staples, annular grooved flooring nails or spiral nails, spaced not more than 150 mm o.c. along the edges and 200 mm o.c. both
ways at other locations.
Nails for panel-type underlay shall be not less than 19 mm long for 6 mm thick underlay and 22 mm long for 7.9 mm thick underlay.
Staples for panel-type underlay shall9.30.2.4. Joints Offset
Where panel-type underlay is required to be installed over plywood, OSB or waferboard, the joints in the underlay shall be offset not
less than 200 mm from the joints in the underlying subfloor.
9.30.2.5. Surface Defects
Underlay beneath resilient or ceramic floors applied with an adhesive shall have all holes or open defects on the surface patched
so that the defects will not be transmitted to the finished surface.
9.30.3. Wood Strip Flooring
9.30.3.1. Thickness
The thickness of wood strip flooring shall conform to Table 9.30.3.1.| Table 9.30.3.1. Thickness of Wood Strip Flooring Forming part of Sentence 9.30.3.1.(1) | |||
| Type of Flooring |
Max. Joist Spacing, mm (in.) |
Minimum Thickness of Flooring, mm (in.) |
|
| With Subfloor | No Subfloor | ||
| Matched hardwood |
400 (16) |
7.9 (5/16) |
19.0 (¾) |
| (interior use only) |
600 (24) |
7.9 (5/16) |
33.3 (1 5/16) |
| Matched softwood |
400 (16) |
19.0 (¾) |
19.0 (¾) |
| (interior or exterior use) |
600 (24) |
19.0 (¾) |
31.7 (1¼) |
| Square edge softwood |
400 (16) |
— |
25.4 (1) |
| (exterior use only) |
600 (24) |
— |
38.1 (1½) |
9.30.3.2. Strip Direction and End Joints
Wood strip flooring shall not be laid parallel to lumber subflooring unless a separate underlay is provided.
If wood strip flooring is applied without a subfloor, it shall be laid at right angles to the joists so that the end joints are staggered
and occur over supports or are end matched.
If the flooring is end matched, it shall be laid so that no 2 adjoining strips break joints in the same space between supports
and each strip bears on no fewer than 2 supports.
9.30.3.3. Nailing
When nails are used, wood strip flooring shall be toe nailed or face nailed with not less than one nail per strip at the spacings
shown in Table 9.30.3.3., except that face nailed strips more than 25 mm in width shall have at least 2 nails
per strip.
| Table 9.30.3.3. Nailing of Wood Strip Flooring Forming part of Sentence 9.30.3.3.(1) | ||
|
Finish Floor Thickness, mm (in.) |
Minimum Length of Flooring Nails, mm (in.) |
Maximum Spacing of Flooring Nails, mm (in.) |
|
7.9 (5/16) |
38(1) (1 ½) |
200 (8) |
|
11.1 (7/16) |
51 (2) |
300 (12) |
|
19.0 (¾) |
57 (2 ¼) |
400 (16) |
|
25.4 (1) |
63 (2 ½) |
400 (16) |
|
31.7 (1 ¼) |
70 (2 ¾) |
600 (24) |
|
38.1 (1 ½) |
83 (3 ¼) |
600 (24) |
| Notes to Table 9.30.3.3.: | |
|
|
|
| (1) | See Article 9.30.3.4. |
9.30.3.4. Staples
Staples are permitted to be used to fasten wood strip flooring not more than 7.9 mm in thickness provided the staples
are not less than 29 mm long with a shank diameter of 1.19 mm and with 4.7 mm crowns.
9.30.4. Parquet Flooring
9.30.4.1. Adhesive
Adhesive used to attach parquet block flooring shall be suitable for bonding wood to the applicable subfloor material.
9.30.5. Resilient Flooring
9.30.5.1. Materials
Resilient flooring used on concrete slabs supported on ground shall consist of asphalt, rubber, unbacked vinyl or vinyl with an inorganic type backing.

Flooring described in Sentence (1) shall be attached to the base with a suitable waterproof and alkali-resistant adhesive.
9.30.6. Ceramic Tile
9.30.6.1. Substrate
Ceramic tile shall be set in a mortar bed or applied to a sound smooth base with a suitable adhesive.
Panel-type subfloor to which ceramic tile is to be applied with adhesive shall have its edges supported according to Article 9.23.15.3.