Division B
Acceptable Solutions

Part 3 — Fire Protection, Occupant Safety and Accessibility

Section 3.6. Service Facilities

(See Appendix A.)

3.6.1. General

3.6.1.1. Scope
1) Intent StatementThe provisions of this Section apply to horizontal service spaces, vertical service spaces, attic or roof spaces, ducts, crawl spaces, shaft spaces, service rooms, and mechanical penthouses, and facilities contained therein.
3.6.1.2. Electrical Wiring and Equipment
1) The installation of electrical wiring and electrical equipment shall conform to the Electrical Safety Regulation.

contentHistory

3.6.1.3. Storage Use Prohibition
1) Intent StatementService spaces shall not be designed to facilitate subsequent use as storage space.
3.6.1.4. Appliances Installed outside a Building
1) Intent StatementA fuel-fired appliance installed on the roof of a building or in another location outside the building shall be installed not less than
a) 1.2 m from a property line, measured horizontally, and
b) 3 m from an adjacent wall of the same building if that wall contains any opening within 3 storeys above and 5 m horizontally from the appliance, unless every opening within these limits is protected by
i) a closure having a fire-protection rating not less than 45 min determined in accordance with Article 3.1.8.4., or
ii) a wired glass assembly permitted for use in a vertical fire separation and described in Appendix D-2.3.14.

3.6.2. Service Rooms

3.6.2.1. Fire Separations around Service Rooms
1) Intent StatementExcept as permitted by Sentences (2), (8), (9) and (10), fuel-fired appliances shall be installed in service rooms separated from the remainder of the building by fire separations having a fire-resistance rating not less than 1 h.
2) Intent StatementExcept as required by Sentence (3), a fuel-fired appliance that serves only one room or suite is not required to be installed in a service room separated from the remainder of the building.
3) Intent StatementA solid-fuel-burning appliance shall not be located in a repair garage, a storage garage, or any other location where it could be exposed to flammable vapours or gases, unless
a) it is enclosed in a service room that is separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h,
b) it is supplied with combustion air directly from outside the building, and
c) the heat that it generates is supplied indirectly to the space served by means of ducts or piping.
4) Intent StatementA service room containing an incinerator shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 2 h.
5) Intent StatementEquipment that uses a liquid having a flash point below 93.3°C shall be installed in a service room separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
6) Electrical equipment that is required to be located in a service room according to the Electrical Safety Regulation shall be installed in a service room separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.

contentHistory

7) Intent StatementExcept as permitted by Sentence (8), in a storey that is not sprinklered throughout, a service room that contains service equipment other than that addressed by Sentences (1) to (6) shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
8) Intent StatementWhere a service room contains a limited quantity of service equipment, and the service equipment neither constitutes a fire hazard nor is essential to the operation of fire safety systems in the building, the requirements for a fire separation shall not apply.
9) Intent StatementA fire separation is not required between a fireplace and the space it serves.
10) Intent StatementA fire separation is not required between a roof-top appliance and the building it serves.
3.6.2.2. Service Rooms under Exits
1) Intent StatementA service room containing service equipment subject to possible explosion, such as boilers operating in excess of 100 kPa (gauge) and some types of refrigerating machinery and transformers, shall not be located directly under a required exit.
3.6.2.3. Service Equipment
1) Intent StatementA service room containing space heating, space cooling and service water heating appliances is permitted to contain other service equipment such as electrical service equipment.
3.6.2.4. Incinerator Rooms
1) Intent StatementA service room containing an incinerator shall not contain other fuel-fired appliances.
3.6.2.5. Combustible Refuse Storage
1) Intent Statement Except as required by Sentence 3.6.3.3.(9), a room for the storage of combustible refuse shall be
a) separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 1 h, and
(See Appendix A.)
3.6.2.6. Door Swing for Service Rooms
1) Intent StatementA swing-type door from a service room containing a boiler or incinerator shall swing outward from the room, except that the door shall swing inward if the door opens onto a corridor or any room used for an assembly occupancy. (See also Sentence 3.4.4.4.(7).)
3.6.2.7. Electrical Equipment Vaults
1) An electrical equipment vault change beginrequired by the Electrical Safety Regulation shall conform to Sentences (2) to (8).change end

contentHistory

2) Intent StatementAn electrical equipment vault referred to in Sentence (1) shall be separated from the remainder of the building by a fire separation of solid masonry or concrete construction having a fire-resistance rating not less than
a) 3 h if the vault is not protected by an automatic fire extinguishing system, or
b) 2 h if the vault is protected by an automatic fire extinguishing system.
3) Intent StatementIf a building is sprinklered throughout, an electrical equipment vault referred to in Sentence (1) need not be sprinklered provided
a) the vault is designed for no purpose other than to contain the electrical equipment, and
b) the vault contains a smoke detector which will actuate the building fire alarm system in the event of a fire in the vault.
4) Intent StatementOnly pipes or ducts necessary for fire protection or the proper operation of the electrical installation shall penetrate the fire separation referred to in Sentence (2).
5) Intent StatementExplosion-relief devices and vents or other protective measures conforming to Sentence 3.3.1.20.(2) shall be provided for an electrical equipment vault referred to in Sentence (1) that contains dielectric-liquid-filled electrical equipment. (See Appendix A.)
6) Intent StatementAn electrical equipment vault referred to in Sentence (1) shall be provided with a ventilation system designed in conformance with Part 6 to prevent the ambient temperature in the vault from exceeding 40°C.
7) Intent StatementThe ventilation system required by Sentence (6) shall be separate from the system for the remainder of the building and shall be designed so that it is automatically shut off in the event of a fire in the vault.
8) Intent StatementThe floor of an electrical equipment vault referred to in Sentence (1) shall be liquid tight and surrounded by liquid tight walls and sills of sufficient height to confine within the vault all of the liquid from the largest item of electrical equipment, but to a height of not less than 100 mm.
9) Intent Statementchange beginElectrical equipment vaults shall be secured against unauthorized entry.change end
3.6.2.8. Emergency Power Installations
1) Intent StatementWhere a generator intended to supply emergency power for lighting, fire safety and life safety systems change beginis located in a building, except where such building is used solely for the purpose of housing the generator and its ancillary equipment, itchange end shall be located in a room that
a) is separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 2 h, and
b) contains only the generating set and equipment related to the emergency power supply system.

3.6.3. Vertical Service Spaces and Service Facilities

3.6.3.1. Fire Separations for Vertical Service Spaces
1) Intent StatementExcept as required by Section 3.5., a vertical service space shall be separated from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to Table 3.6.3.1. for the fire-resistance rating required by Subsection 3.2.2. for
a) the floor assembly above the storey, or
b) the floor assembly below the storey, if there is no floor assembly above.
(See Appendix A.)
Table 3.6.3.1.
Fire Separations for Vertical Service Spaces
Forming part of Sentence 3.6.3.1.(1)

Fire-Resistance Rating of Fire Separation Required for Floor Assembly

Minimum Fire-Resistance Rating of Vertical Service Space

less than 45 min
45 min 45 min
1 h 45 min
1.5 h 1 h
2 h or more 1 h
2) Intent StatementA vertical service space that does not extend through the roof of a building shall be enclosed at the top with construction having a fire-resistance rating not less than that required for the vertical service space walls.
3) Intent StatementA vertical service space that does not extend to the bottom of a building shall be enclosed at the lowest level with construction having a fire-resistance rating not less than that required for the vertical service space walls.
4) Intent StatementA vent from a vertical service space not extending to the roof shall be enclosed within the building with construction having a fire-resistance rating not less than that required for the vertical service space walls.
5) Intent StatementOnly openings that are necessary for the use of the vertical service space shall be permitted through a vertical service space enclosure.
3.6.3.2. Foamed Plastic Protection
1) Intent StatementFoamed plastic insulation in a vertical service space shall be protected in conformance with Article 3.1.5.12.
3.6.3.3. Linen and Refuse Chutes
1) Intent StatementA linen chute or refuse chute shall
a) be impervious to moisture,
b) have a smooth internal surface,
c) be corrosion-resistant,
d) be constructed of noncombustible material, and
e) be located in a shaft in which there are no services other than noncombustible drain, waste and vent piping or noncombustible water piping.
2) Intent StatementA shaft containing a linen chute or refuse chute shall have a fire-resistance rating conforming to Sentence 3.6.3.1.(1), but not less than
a) 1 h if the chute outlet for the discharge room is protected by an automatic, self-latching closure held open by a fusible link, or
b) 2 h if no closure is provided at the chute outlet into the discharge room.
3) Intent StatementAn interior linen chute or refuse chute shall extend not less than 1 m above the roof and shall be vented above the roof with a vent which
a) has an unobstructed area not less than the cross-sectional area of the chute, and
b) is equipped with a cover that will open automatically, or that can be opened manually, in the event of a fire in the chute.
4) Intent StatementIntake openings for a linen chute or a refuse chute shall
a) have an area not more than 60% of the cross-sectional area of the chute, and
b) be fitted with closures designed to close automatically and latch after use.
5) Intent StatementIntake openings for a linen chute or a refuse chute shall be located in rooms or compartments that
a) have no dimension less than 750 mm,
b) are separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 45 min,
c) are designed for no other purpose, and
d) do not open directly into an exit.
6) Intent StatementSprinklers shall be installed at the top of each linen chute or refuse chute, at alternate floor levels and in the room or bin into which the chute discharges.
7) Intent StatementThe room into which a linen chute discharges shall be separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 1 h.
8) Intent StatementA refuse chute shall be equipped at the top with spray equipment for washing-down purposes.
9) Intent StatementA refuse chute shall discharge only into a room or bin separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 2 h.
10) Intent StatementThe room or bin into which a refuse chute discharges shall be of sufficient size to contain the refuse between normal intervals of emptying, be impervious to moisture and be equipped with a water connection and floor drain for washing-down purposes.
11) Intent StatementA room into which a refuse chute discharges shall contain no service equipment that is not related to refuse handling and disposal.
3.6.3.4. Exhaust Duct Negative Pressure
1) Intent Statement If a vertical service space contains an exhaust duct that serves more than one fire compartment,
a) the duct shall have a fan located at or near the exhaust outlet to ensure that the duct is under negative pressure, and
b) the individual fire compartments shall not have individual fans that exhaust directly into the duct in the vertical service space.

3.6.4. Horizontal Service Spaces and Service Facilities

3.6.4.1. Scope
1) Intent StatementThis Subsection applies to horizontal service spaces and service facilities, including ceiling spaces, duct spaces, crawl spaces and attic or roof spaces.
3.6.4.2. Fire Separations for Horizontal Service Spaces
1) Intent StatementA horizontal service space that penetrates a required vertical fire separation shall be separated from the remainder of the building it serves in conformance with Sentence (2).
2) Intent StatementIf a horizontal service space or other concealed space is located above a required vertical fire separation other than a vertical shaft, this space need not be divided at the fire separation as required by Article 3.1.8.3. provided the construction between this space and the space below is a fire separation with a fire-resistance rating equivalent to that required for the vertical fire separation, except that the fire-resistance rating is permitted to be not less than 30 min if the vertical fire separation is not required to have a fire-resistance rating more than 45 min. (See Appendix A.)
3.6.4.3. Plenum Requirements
1) Intent StatementA concealed space used as a plenum within a floor assembly or within a roof assembly need not conform to Sentence 3.1.5.15.(1) and Article 3.6.5.1., provided
a) all materials within the concealed space have a flame-spread rating not more than 25 and a smoke developed classification not more than 50, except for
i) tubing for pneumatic controls,
ii) optical fibre cables and electrical wires and cables change beginwith combustible insulation, jackets or sheathes that are used for the transmission of voice, sound or data and conform to Sentences 3.1.4.3.(2) and 3.1.5.18.(2),change end
iii) totally enclosed non-metallic raceways change beginwith an FT6 rating, when tested in accordance with Clause 3.1.5.20.(1)(a), in buildings required to be of noncombustible constructionchange end, and
iv) change begintotally enclosed non-metallic raceways with an FT4 rating, when tested in accordance with Clause 3.1.5.20.(1)(a), in buildings permitted to be of combustible construction, andchange end
b) the supports for the ceiling membrane are of noncombustible material having a melting point not below 760°C.
2) Intent StatementIf a concealed space referred to in Sentence (1) is used as a return-air plenum and incorporates a ceiling membrane that forms part of the required fire-resistance rating of the assembly, every opening through the membrane shall be protected by a fire stop flap that
a) stops the flow of air into the concealed space in the event of a fire,
b) is supported in a manner that will maintain the integrity of the ceiling membrane for the duration of time required to provide the required fire-resistance rating, and
c) conforms to the appropriate requirements of Appendix D.
3.6.4.4. Attic or Roof Space Access
1) Intent StatementAn attic or roof space more than 600 mm high shall be provided with access from the floor immediately below by a hatchway not less than 550 mm by 900 mm or by a stairway.
3.6.4.5. Horizontal Service Space Access
1) Intent StatementA horizontal service space, consisting of ceiling and duct spaces, which is more than 1 200 mm high and 600 mm wide shall have inspection doors not less than 300 mm in both horizontal and vertical dimensions placed so that the entire interior of the duct or space can be viewed.
3.6.4.6. Crawl Space Access
1) Intent StatementA crawl space shall have at least one access opening not less than 550 mm by 900 mm.

3.6.5. Air Duct and Plenum Systems

3.6.5.1. Duct Materials
1) Intent StatementExcept as permitted by Sentences (2) to (5) and Article 3.6.4.3., all ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of steel, aluminum alloy, copper, clay, asbestos-cement or other noncombustible material.
2) Intent StatementExcept as permitted by Sentence (3), ducts, associated fittings and plenums are permitted to contain combustible material provided they
a) conform to the appropriate requirements for Class 1 duct materials in CAN/ULC-S110, “Test for Air Ducts,”
b) conform to Article 3.1.5.15. in a building required to be of noncombustible construction,
c) conform to Subsection 3.1.9.,
d) are used only in horizontal runs in a building required to be of noncombustible construction,
e) are not used in vertical runs serving more than 2 storeys in a building permitted to be of combustible construction, and
f) are not used in air duct systems in which the air temperature could be more than 120°C.
3) Intent StatementCombustible ducts which are part of a duct system conveying only ventilation air and are contained entirely within a dwelling unit need not comply with the requirements of Sentences (1) and (2).
4) Intent StatementDuct sealants shall have a flame-spread rating not more than 25 and a smoke developed classification not more than 50.
5) Intent StatementDuct connectors that contain combustible materials and that are used between ducts and air outlet units shall
a) conform to the appropriate requirements for Class 1 air duct materials in CAN/ULC-S110, “Test for Air Ducts,”
b) be not more than 4 m long,
c) be used only in horizontal runs, and
d) not penetrate a required fire separation.
3.6.5.2. Vibration Isolation Connectors
1) Intent StatementExcept as permitted by Sentence (2), vibration isolation connectors in air duct systems shall be noncombustible.
2) Intent StatementCombustible fabric vibration isolation connectors are permitted provided they
a) are not more than 250 mm long,
b) comply with the flame-resistance requirements of CAN/ULC-S109, “Flame Tests of Flame-Resistant Fabrics and Films,” and
c) are not used in a location where they are exposed to heated air or radiation from heat sources that could cause the exposed surface temperature to be more than 120°C.
3.6.5.3. Tape
1) Intent StatementTape used to seal joints in air ducts, plenums and other parts of air duct systems shall meet the flame-resistance requirements for fabric in CAN/ULC-S109, “Flame Tests of Flame-Resistant Fabrics and Films.”
3.6.5.4. Coverings, Linings, Adhesives and Insulation
1) Intent StatementCoverings, linings and associated adhesives and insulation for air ducts, plenums and other parts of air duct systems that would have an exposed surface temperature more than 120°C when exposed to heated air or radiation from heat sources shall be of noncombustible material.
2) Intent StatementExcept as permitted by Sentence (3), combustible coverings and linings, including associated adhesives and insulation, shall have
a) a flame-spread rating not more than 25 on any exposed surface or any surface that would be exposed by cutting through the material in any direction, and
b) a smoke developed classification not more than 50.
3) Intent StatementThe outer covering of ducts, plenums and other parts of air duct systems used within an assembly of combustible construction is permitted to have
a) an exposed surface flame-spread rating not more than 75, and
b) a smoke developed classification not more than 50.
4) Intent StatementCombustible coverings and linings referred to in Sentences (2) and (3) shall not flame, glow, smoulder or smoke when tested in accordance with the method of test in ASTM C 411, “Hot-Surface Performance of High-Temperature Thermal Insulation,” at the maximum temperature to which the coverings and linings are to be exposed in service.
5) Intent StatementExcept as permitted by Sentence (6), foamed plastic insulation shall not be used as part of an air duct system or for insulating an air duct.
6) Intent StatementFoamed plastic insulation is permitted to be installed in a ceiling space that is used as a return air plenum provided the foamed plastic insulation is protected from exposure to the plenum in accordance with Article 3.1.5.12.
7) Intent StatementCombustible coverings and linings of ducts, including associated adhesives and insulation, shall be interrupted where the duct penetrates a fire separation and at the immediate area of operation of heat sources in a duct system, including electric resistance heaters or fuel-burning heaters or furnaces.
3.6.5.5. Insulation and Coverings
1) Intent StatementInsulation and coverings on pipes in which the temperature of the fluid exceeds 120°C shall
a) be made of noncombustible material, or
b) not flame, glow, smoulder or smoke when tested in accordance with ASTM C 411, “Hot-Surface Performance of High-Temperature Thermal Insulation,” at the maximum temperature to which the insulation or covering is to be exposed in service.
2) Intent StatementExcept as permitted by Sentence (5), where combustible insulation is used on piping in a horizontal service space or a vertical service space, the insulation and coverings on that piping shall have a flame-spread rating, on any exposed surface and on any surface that would be exposed by cutting through the material in any direction,
a) not more than 25 in a building required to be of noncombustible construction, or
b) not more than 75 in a building permitted to be of combustible construction.
3) Intent StatementExcept as permitted by Sentence (5), insulation and coverings on piping located in rooms and spaces other than the service spaces described in Sentence (2) shall have a flame-spread rating not more than that required for the interior finish of the ceiling of the room or space.
4) Intent StatementExcept as permitted by Sentence (5), combustible insulation and covering used on piping in a building within the scope of Subsection 3.2.6. shall have a smoke developed classification not more than 100.
5) Intent StatementNo flame-spread rating or smoke developed classification limits are required for combustible insulation and coverings used on piping located within a
a) concealed space in a wall,
b) floor slab, or
c) noncombustible enclosure.
3.6.5.6. Clearance of Ducts and Plenums
1) Intent StatementThe clearance of furnace plenums from combustible material shall conform to the requirements of the appropriate standards referenced in Sentence 6.2.1.4.(1).
2) Intent StatementIf the plenum clearance required in accordance with Sentence (1) is not more than 75 mm, the clearance between a supply duct and combustible material shall be not less than
a) the required plenum clearance within a horizontal distance of 450 mm from the plenum, and
b) 12 mm at a horizontal distance of 450 mm or more from the plenum, except that this clearance is permitted to be reduced to zero beyond a bend or offset in the duct sufficiently large to shield the remainder of the supply duct from direct radiation from the furnace heat exchanger.
(See Appendix A.)
3) Intent StatementIf the plenum clearance required in accordance with Sentence (1) is more than 75 mm but not more than 150 mm, the clearance between a supply duct and combustible material shall be not less than
a) the required plenum clearance within a horizontal distance of 1 800 mm from the plenum, and
b) 12 mm at a horizontal distance of 1 800 mm or more from the plenum, except that this distance is permitted to be reduced to zero beyond a bend or offset in the duct sufficiently large to shield the remainder of the supply duct from direct radiation from the furnace heat exchanger.
(See Appendix A.)
4) Intent StatementIf the plenum clearance required in accordance with Sentence (1) is more than 150 mm, the clearance between a supply duct and combustible material shall be not less than
a) the required plenum clearance within a horizontal distance of 1 000 mm from the plenum,
b) 150 mm within a horizontal distance between 1 000 mm and 1 800 mm from the plenum, and
c) 25 mm at a horizontal distance of 1 800 mm or more from the plenum, except that this distance is permitted to be reduced to 8 mm beyond a bend or offset in the duct sufficiently large to shield the remainder of the supply duct from direct radiation from the furnace heat exchanger.
(See Appendix A.)
5) Intent StatementIf a register is installed in a floor directly over a pipeless furnace, a double-walled register box with not less than 100 mm between walls, or a register box with the warm-air passage completely surrounded by the cold-air passage, shall be permitted instead of the clearances listed in Sentences (2), (3) and (4).
3.6.5.7. Supply, Return, Intake and Exhaust-Air Openings
1) Intent StatementCombustible grilles, diffusers and other devices for supply, return, and exhaust-air openings in rooms shall conform to the flame-spread rating and smoke developed classification requirements for the interior finish of the surface on which they are installed.
3.6.5.8. Return-Air System
1) Intent StatementExcept as required by Sentences (2) and (3), return ducts shall be constructed of material having a flame-spread rating not more than 150.
2) Intent StatementIf any part of a return duct will be exposed to radiation from the furnace heat exchanger or other radiating part within the furnace, that part of a return duct directly above or within 600 mm of the outside furnace casing shall be noncombustible.
3) Intent StatementReturn ducts serving solid-fuel-burning furnaces shall be constructed of noncombustible material.
4) Intent StatementCombustible return ducts shall be lined with noncombustible material
a) below floor registers,
b) at the bottom of vertical ducts, and
c) under furnaces having a bottom return.