Division B
Acceptable Solutions

Part 3 — Fire Protection, Occupant Safety and Accessibility

Section 3.8. Building Requirements for Persons with Disabilities

(See Appendix A.)
(See Appendix A.)

3.8.1. General

3.8.1.1. Application
1) This Section applies to the design and construction of buildings and occupancies to make them accessible by persons with disabilities.
2) The requirements of this Section take precedence over other requirements contained in this Part and in Part 9.
3) Access shall be provided to alterations, additions and changes in occupancy to the extent required in Subsection 3.8.4.
3.8.1.2. Openings through Firewalls
1) Where there are openings through a firewall, other than those for piping, tubing, wiring and conduit, the requirements of this Section shall apply to the floor areas on both sides of the firewall as if they were in the same building.

3.8.2. Classification Requirements

3.8.2.1. Application and Exemptions
1) Except as provided in Sentence (2), access shall be provided to all storeys of buildings of new construction.
2) This Subsection does not apply to
a) the storey next above or below the accessible storey in a building not more than two storeys in building height provided the storeys next above or below the accessible storey
i) change beginis less than 600 m2 in floor area,
ii) does not contain facilities integral to the principle function of the accessible storey, and
iii) does not contain an assembly major occupancy with an area more than 100 m2, (See Appendix A.)
b) the storey next above or below the accessible storey in a suite of not more than two storeys, where the accessible storeys is the first storey or basement, provided the storey next above or below the accessible storey
i) is less than 600 m2 in area,
ii) does not contain facilities integral to the principle function of the accessible storey, and
iii) does not contain an assembly major occupancy with an area more than 100 m2,
c) Group C dwelling units, row houses, boarding houses and lodging houses,
d) Group C apartment buildings and condominiums except to the extent described in Article 3.8.2.27.,
e) Group E shops and stores with a total retail floor space of less than 50 m2 (See Appendix A), andchange end
f) Group F Division 1 occupancies.
3.8.2.2. Design Requirements
1) To meet the requirements of Articles 3.8.2.3. to 3.8.2.39., the design requirements of Subsection 3.8.3. shall form an integral part of this Subsection.
3.8.2.3. Specific Requirements
1) Except where stated otherwise buildings and occupancies to which this Subsection applies shall, in addition to the requirements listed for specific occupancies, have
a) access from the street to at least one main entrance conforming to Article 3.8.3.5.,
b) where off-street parking is provided for persons with disabilities, change beginaccesschange end from the parking area to an entrance conforming to Article 3.8.3.5. change beginthatchange end serves the parking area unless the entrance in Clause (a) is located so as to conveniently serve both the parking area and the street,
c) access to all areas where work functions can reasonably be expected to be performed by persons with disabilities,
d) accessible washrooms conforming to Sentence (2), and
e) on each floor area to which access is required, egress conforming to Article 3.8.3.19.
2) In buildings and occupancies where water closets are required,
a) at least one universal toilet room change beginthatchange end conforms to Sentence 3.7.2.10.(9) change beginshall be providedchange end, and
b) where the occupant load of the building or occupancy exceeds 150, other public washrooms in floor areas required to be accessible shall conform to Sentences 3.7.2.10.(2) to (8).
(See Appendix A.)
3.8.2.4. Assembly Occupancies, Division 1
1) In assembly occupancies, all auditoria and theatres with an area of more than 100 m2 shall have an assistive listening system conforming to Article 3.8.3.20.
3.8.2.5. Theatres, Studios and Opera Houses
1) In Group A, Division 1 occupancies, access shall be provided to
a) a ticket office,
b) each type of refreshment facility,
c) each type of public facility, and
d) viewing positions conforming to Article 3.8.3.15. in the numbers required by Article 3.8.2.5.
Table 3.8.2.5.
Required Number of Viewing Positions in Theatres, Studios and Opera Houses
Forming part of Sentence 3.8.2.5.(1)
Seating Capacity of Occupancy(1) Number of Viewing Positions Required
Up to 100 2
101 to 200 3
201 to 350 4
351 and over 4 plus 1 for each additional 1 000 seats or part thereof
Notes to Table 3.8.2.5.:

(1) See Parts 2 and 3 of Division A.
3.8.2.6. Art Galleries, Exhibition Halls, Libraries and Museums
1) In art galleries, exhibition halls, libraries and museums, access shall be provided to all areas to which the public is admitted.
3.8.2.7. Bowling Alleys
1) In bowling alleys, access shall be provided to
a) viewing positions conforming to Article 3.8.3.15.,
b) each type of refreshment facility, and
c) all bowling lanes.
3.8.2.8. Amusement Arcades and Billiard Halls
1) In amusement arcades and billiard halls, access shall be provided to
a) each type of recreational facility, and
b) each type of refreshment facility.
3.8.2.9. Churches
1) In churches, similar places of worship and auxiliary halls, access shall be provided to viewing positions conforming to Article 3.8.3.15., where fixed seating is installed.
3.8.2.10. Clubs, Non-residential
1) In non-residential clubs, access shall be provided to
a) change begineachchange end type of membership facility, and
b) at least one bath or shower, conforming to Sentence 3.7.2.10.(10) or (11), where one or more baths or showers are provided.
3.8.2.11. Community, Dance and Lecture Halls
1) In community halls, dance halls and lecture halls, access shall be provided to
a) each type of public facility, and
b) viewing positions conforming to Article 3.8.3.15., where fixed seating is installed.
3.8.2.12. Courthouses
1) In courthouses, access shall be provided to
a) each public facility,
b) interview rooms, and
c) at least one holding room.
3.8.2.13. Gymnasiums
1) In gymnasiums, access shall be provided to
a) every type of public facility,
b) viewing positions conforming to Article 3.8.3.15., where fixed seating is installed, and
c) at least one changing room for each sex, where changing rooms are provided.
2) Changing rooms in Clause (c) shall each have at least one shower conforming to Sentence 3.7.2.10.(11), where showers are provided.
3.8.2.14. Restaurants
1) In restaurants,
a) access shall be provided to all public facilities, and
b) change begineach area providing seating shall be capable of providing clear space for use by persons in wheelchairs that is equivalent to not less than 1 per cent of such seating and is located so as
i) to provide viewing of any entertainment areas, and
ii) not to infringe on any aisle requirements.change end
3.8.2.15. Lodge Rooms
1) In lodge rooms, access shall be provided to all storeys, except those storeys containing only mechanical and storage areas.
3.8.2.16. Passenger Terminals
1) In passenger terminals, access shall be provided to all areas to which the public is admitted.
3.8.2.17. Schools and Colleges, Non-residential
1) Non-residential schools and colleges need not comply with Sentence 3.8.2.3.(1) but shall have
a) change beginto each administrative, educational, and recreational building, at least one entrance thatchange end
i) conforms to Article 3.8.3.5., and
ii) is accessible from adjacent parking stalls conforming to Article 3.8.3.4., and
b) from within each building, access to
i) all educational and recreational facilities,
ii) each type of refreshment facility,
iii) offices,
iv) lockers,
v) areas where work functions can reasonably be expected to be performed by persons with disabilities,
vi) viewing positions conforming to Article 3.8.3.15., where fixed seating is installed,
vii) accessible washrooms conforming to Sentence 3.8.2.3.(2), where washrooms are required, and
viii) at least one bath or shower, conforming to Sentences 3.7.2.10.(10) or (11), where one or more baths or showers are provided.
2) In addition to the washroom facilities required by Subclause (b)(vii), an accessible toilet room conforming to Sentence 3.7.2.10.(9) shall be provided in each principal building at a non-residential school or college.
3) In addition to the requirements of Sentence (1), every floor area change beginthatchange end is required to be accessible shall conform to Article 3.8.3.19.
3.8.2.18. Undertaking Premises
1) In undertaking premises, where change beginfixedchange end seating is installed in the chapel, access shall be provided to viewing positions conforming to Article 3.8.3.15.
3.8.2.19. Arenas and Ice Rinks
1) In arenas and ice rinks, access shall be provided to
a) each type of public facility,
b) at least one changing room for each sex, where changing rooms are provided, and
c) viewing positions conforming to Article 3.8.3.15. in the numbers required by Table 3.8.2.19., where fixed seating is installed.
Table 3.8.2.19.
Required Number of Viewing Positions in Arenas and Ice Rinks
Forming part of Sentence 3.8.2.19.(1)
Seating Capacity of Arena change beginorchange end Ice Rink Number of Viewing Positions change beginRequiredchange end
Up to 500 3
501 to 1 000 6
1 001 and over 6 plus 2 for each additional 1 000 seats or part thereof
2) Changing rooms in Clause (1)(b) shall each have at least one shower conforming to Sentence 3.7.2.10.(11), where showers are provided.
3.8.2.20. Swimming Pools
1) Swimming pools shall conform change begintochange end the requirements of Article 3.8.2.13.
3.8.2.21. Bleachers
1) Where bleachers are erected as other than temporary structures, they need not comply with Sentence 3.8.2.3.(1), but shall have access provided to
a) viewing positions adjacent to such structures conforming to Article 3.8.3.15. in the numbers required by Table 3.8.2.19., and
b) washroom facilities conforming to Sentence 3.8.2.3.(2), where washroom facilities are provided.
3.8.2.22. Grandstands, and Stadiums
1) In grandstands and stadiums, access shall be provided to
a) at least one refreshment facility,
b) offices,
c) at least one changing room for each sex, where changing rooms are provided, and
d) viewing positions conforming to 3.8.3.15. in the numbers required by Table 3.8.2.19.
2) Changing rooms in Clause (1)(c) shall each have at least one shower conforming to Sentence 3.7.2.10.(11), where showers are provided.
3) Where general seating areas are partially or totally covered, viewing positions required by Clause (1)(d) shall be covered.
3.8.2.23. Drive-in Theatres
1) Drive-in theatres need not comply with Sentence 3.8.2.3.(1), but access shall be provided to,
a) all public refreshment facilities, and
b) washrooms conforming to Sentence 3.8.2.3.(2).
3.8.2.24. Jails
1) Jails, penitentiaries, prisons and reformatories need not comply with Sentence 3.8.2.3.(1), but shall have
a) access from the street to at least one main entrance conforming to Article 3.8.3.5.,
b) where off-street parking is provided for persons with disabilities, access from the parking area to an additional entrance conforming to Article 3.8.3.5. unless the entrance in Clause (a) is located so as to conveniently serve both the parking area and the street,
c) access to areas where visitors are admitted, and
d) access to visitor washrooms, conforming to Sentence 3.8.2.3.(2), where visitor washrooms are provided.
3.8.2.25. Psychiatric Hospitals and Police Stations
1) Psychiatric hospitals with or without detention quarters, and police stations with detention quarters, need not comply with Sentence 3.8.2.3.(1), but shall have
a) access from the street to at least one main entrance conforming to Article 3.8.3.5.,
b) where off-street parking is provided for persons with disabilities, access from the parking area to an additional entrance conforming to Article 3.8.3.5. unless the entrance in Clause (a) is located so as to conveniently serve both the parking area and the street,
c) access to areas where work functions can reasonably be expected to be performed by persons with disabilities,
d) accessible public washrooms conforming to Sentence 3.8.2.3.(2) serving each area to which persons with disabilities are provided access, and
e) access to each type of facility.
3.8.2.26. Care change beginand Treatmentchange end Facilities
1) All occupancies in Group B, Divisions 2 change beginand 3change end shall comply at least with the requirements of Article 3.8.2.25.(See also Sentence 3.7.2.10.(12).)
3.8.2.27. change beginApartment and Condominium Buildingschange end
1) Apartment and condominium buildings need not comply with Sentence 3.8.2.3.(1), except that access shall be provided
a) from the street to the main entrance conforming to Article 3.8.3.5.,
b) from a private parking area to an entrance conforming to Article 3.8.3.5., and
c) where an elevator is provided, from the main entrance in Clause (a), or from the entrance in Clause (b), to an elevator conforming to Sentence 3.5.2.1.(3).
2) At the main entrance to an apartment or condominium building, the intercom system shall be installed with no user functions more than 1 375 mm above the finished paved area.
3) Each dwelling unit in an apartment or condominium building designed primarily for senior citizens and each adaptable dwelling unit shall be provided with special outlet boxes and cover plates as described in Sentence 3.2.4.20.(7). (See also Sentence 3.2.4.20.(8).)
3.8.2.28. Clubs, Residential
1) In residential clubs, the requirements of Article 3.8.2.10. shall apply, and
a) where sleeping accommodation for 10 or more persons is provided in single or double rooms, at least one such room shall conform to Article 3.8.3.14., and
b) a sleeping room, other than one required by Clause (a), shall be change beginequippedchange end with a visual warning system conforming to Sentence 3.2.4.20.(3).
3.8.2.29. Schools and Colleges, Residential
1) Residential schools and colleges need not comply with Sentence 3.8.2.3.(1), except that the requirements of Article 3.8.2.17. shall apply, and
a) access shall be provided to at least one bed space conforming to Clause 3.8.3.14.(1)(a) and (b), for every 40 bed spaces or part thereof, and
b) a bed space other than one required by Clause (a) shall be change beginequippedchange end with a visual warning system conforming to Sentence 3.2.4.20.(3).
2) A bathroom provided to serve a bed space described in Clause 3.8.2.29.(1)(a) shall conform to Clause 3.8.3.14.(1)(h).
3.8.2.30. Dormitories
1) In dormitories, access shall be provided to
a) each type of facility,
b) at least one bed space conforming to Clauses 3.8.3.14.(1)(a) and (b), for every 40 bed spaces or part thereof, and
c) at least one bath or shower conforming to Sentences 3.7.2.10.(10) or (11) where one or more baths or showers are provided.
2) A bed space other than change beginone required bychange endClause (b) shall be change beginequippedchange end with a visual warning system conforming to Sentence 3.2.4.20.(3).
3) A bathroom provided to serve a bed space described in Clause 3.8.2.30.(1)(b) shall conform to Clause 3.8.3.14.(1)(h).
3.8.2.31. Hotels and Motels
1) In hotels and motels, access shall be provided to
a) every type of public facility, including those located outside the building,
b) all storeys to which the public is admitted, and
c) one sleeping unit conforming to Article 3.8.3.14. for every 40 sleeping units or part thereof.
2) At least one sleeping unit, other than those required change beginbychange endClause (1)(c), for every 20 sleeping units or part thereof shall be change beginequippedchange end with a visual warning system conforming to Sentence 3.2.4.20.(3).
3) Accessible washrooms required by Clause 3.8.2.3.(1)(d) need only be those provided for public use.
3.8.2.32. Business and Personal Service Occupancies
1) In a Group D occupancy with multiple suites, at least one accessible washroom, conforming to Sentence 3.8.2.3.(2), shall either
a) be available to all suites, or
b) be provided in each suite not having access to a washroom described in Clause (a).
2) In offices, dental offices, medical offices, fire stations, police stations without detention quarters, radio stations, telephone exchanges and small tool and appliance rental and service premises, access shall be provided to areas to which the public is admitted.
3.8.2.33. Banks
1) In banks and financial institutions, access shall be provided to
a) every type of public facility,
b) at least one teller location conforming to Article 3.8.3.18., and
c) automated teller machines, night deposit boxes and similar services, where provided, which shall be installed to be usable by persons in wheelchairs.
3.8.2.34. Barbers and Hairdressers
1) Where one or more hairdressing sinks are provided in barber shops, hairdressing shops and beauty parlours, access shall be provided to at least one hairdressing sink which shall be usable by persons in wheelchairs.
3.8.2.35. Laundry and Dry-cleaning, Self-service
1) In self-service laundry and dry-cleaning premises, access shall be provided to at least one of each type of equipment installed for public use.
3.8.2.36. Mercantile Occupancies
1) In a Group E occupancy with multiple suites, at least one accessible washroom, conforming to Sentence 3.8.2.3.(2), shall either
a) be available to all suites, or
b) be provided in each suite not having access to a washroom described in Clause (a).
2) In Group E buildings, access shall be provided to all public facilities and to all areas to which the public is admitted. (See Appendix A.)
3.8.2.37. High Hazard Occupancies
1) change beginGroup F, Division 1 occupancieschange end need not conform to the requirements of this Subsection.
3.8.2.38. Industrial Occupancies, Service Stations and Parking Garages
1) Except as provided in Sentences (2) and (3), in Group F, Division 2 and 3 occupancies, access shall be provided to all areas to which the public is admitted.
2) Service stations need not comply with Sentence 3.8.2.3.(1) except that for service stations with washrooms, regardless of service station floor area, the washrooms shall conform to Sentence 3.8.2.3.(2).
3) In storage garages, access need only be provided to storeys containing the accessible parking required by Article 3.8.3.4. or local bylaws.
3.8.2.39. Public Toilets
1) Public toilets located in highway rest areas, campgrounds, picnic grounds, parks, recreational vehicle parks, and mobile home parks need not comply with Sentence 3.8.2.3.(1)change beginexcept that the following shall be provided:change end
a) access from a roadway to at least one toilet building by means of a path of travel conforming to Article 3.8.3.2., and
b) within the toilet building, toilet facilities conforming to Sentence 3.8.2.3.(2).
2) Where permanent bath or shower facilities are provided to serve areas described in Sentence (1), at least one bath or shower shall be accessible as described in Clause (1)(a) and conform to Sentences 3.7.2.10.(10) or (11).

3.8.3. Design Requirements

3.8.3.1. Application
1) This Subsection applies to all buildings and parts of buildings that are required to be accessible under Subsection 3.8.2., change beginincluding without limitationchange end exterior paths and stairs within property lines from streets, parking areas and ancillary areas to at least one main entrance of these buildings.
3.8.3.2. Paths of Travel
1) Walks to at least one main entrance and all ancillary areas that are required to be accessible shall
a) be provided by means of a continuous plane not interrupted by steps or abrupt changes in level,
b) have a permanent, firm and slip-resistant surface,
c) have an uninterrupted width of not less than 1 500 mm, and a gradient not more than 1 in 20,
d) have a curb not less than 75 mm high where, in the absence of walls, railings, or other barriers on either or both sides of the walk, the vertical drop from the walk is more than 75 mm,
e) not have gratings with openings that will permit the passage of a sphere more than 13 mm in diameter and have all elongated openings oriented approximately perpendicular to the direction of travel,
f) change beginwhere the path of travel is level and even with adjacent walking surfaces, have a texture, not less than 1 500 mm in width, that differs from the texture of the surrounding walking surfaces,change end
g) be free from obstructions for the full width of the walk to a height of not less than 1 980 mm, except that handrails are permitted to project not more than 100 mm from either or both sides into the clear area, and
h) be designed as a ramp where the gradient of the walk is more than 1 in 20.
3.8.3.3. Ramps
1) Where ramps are required to provide interior and exterior access, they shall
a) have an uninterrupted width of not less than 1 500 mm, except as permitted change beginby Sentences (4) and (6), andchange end Clause (7)(b),
b) have, where the vertical drop at the side of the ramp is more than 75 mm, either
i) a curb not less than 75 mm high, or
ii) walls, railings or other barriers that extend to within 75 mm of the finished ramp surface,
c) be free from obstructions for the full width of the ramp to a height of not less than 1 980 mm, except that handrails, excluding those to ramps in Sentence (4) and Clause (7)(b), are permitted to project not more than 100 mm from either or both sides into the clear area,
d) be provided with an unobstructed, level area not less than 1 500 mm long by the width of the ramp at the bottom and top ends and at abrupt changes in direction,
e) have a level landing not less than 1 500 mm long by the width of the ramp at intervals conforming to Table 3.8.3.3., and
f) have gradients and maximum lengths conforming to Table 3.8.3.3.
2) Except as permitted change beginbychange end Sentences (3)  and (5), handrails conforming to change beginArticle 3.4.6.5.change end shall be installed on both sides of ramps.
3) Where ramps described in Sentence (1) have a gradient not more than 1 in 12 and are not more than 2 m long, handrails are required on one side only.
4) Ramps with a gradient more than 1 in 12 shall have an uninterrupted width of 890 mm to 940 mm between handrails.
Table 3.8.3.3.
Ramps
Forming part of Article 3.8.3.3.
Gradient Maximum Length Maximum Landing Intervals Handrails Required(1)
over 1 in 20 to 1 in 16 None 12 m both sides(2)
over 1 in 16 to 1 in 12 None 9 m both sides(2)
over 1 in 12 to 1 in 10(3) 6 m both sides(2)
over 1 in 10 to 1 in 8 600 mm not required
Notes to Table 3.8.3.3.:

(1) See Sentence 3.8.3.3.(2).
(2) See Sentence 3.8.3.3.(3).
(3) See Sentence 3.8.3.3.(4).
5) Handrails are not required to curb cut ramps.
6) A ramp in a passageway up to and including 6 m in width shall be at least 915 mm wide between handrails.
7) Ramps in passageways over 6 m in width shall be either
a) one ramp at least 1 500 mm wide, or
b) two ramps each at least 915 mm wide between handrails.
3.8.3.4. Parking Stalls for Persons with Disabilities
1) Where parking is provided, one parking stall for persons with disabilities shall be provided for each sleeping unit required to conform to Article 3.8.3.14. and for each viewing position required to conform to Article 3.8.3.15. and shall
a) be at least 3 700 mm wide,
b) have a firm, slip-resistant and level surface,
c) be located close, and be accessible, to an entrance conforming to Article 3.8.3.5., and
d) be clearly identified as being solely for the use of persons with disabilities.
2) In all other occupancies, where more than 50 parking stalls are provided, parking stalls for persons with disabilities shall be provided in the ratio of 1 for every 100 or part thereof.
3.8.3.5. Main Entrances
1) A building shall have at least one main entrance conforming to Sentences 3.3.1.13.(10) to (12).
2) Where change beginaccess is not provided to any main entrancechange end, a sign (see Sentence 3.8.3.12.(3)) shall be installed as far ahead of any wheelchair obstruction as is practical so as to indicate clearly the location of the accessible main entrance.
3) Access shall be provided from every accessible main entrance to all parts of the building required change beginby Subsection 3.8.2. to be accessible.change end
4) change beginPower operation that functions for passage in both directions shall be provided for all doors in an accessible path of travel at the exterior accessible entrances to
a) a hotel,
b) a Group B, Division 2 major occupancy,
c) a Group B, Division 3 major occupancy, and
d) any of the following that is more than 5OO m2 in area:
5) If a walkway or pedestrian bridge connects two accessible storeys in different buildings, the path of travel from one storey to the other storey by means of the walkway or bridge shall be accessible.
3.8.3.6. Interior Passageways
1) In passageways, abrupt changes in floor level shall not exceed 13 mm, except where ramps conforming to Sentences 3.8.3.3.(6) and (7) are provided.
3.8.3.7. Public Aisles
1) The effective width between any two structures or fixtures in public aisles in merchandising establishments and exhibition facilities shall be not less than 1 100 mm.
3.8.3.8. Turnstiles
1) Where turnstiles, controlled checkout lanes or other restricted passageways are constructed to control the flow of pedestrian traffic, at least one such facility shall be
a) change beginnot less than 800 mm wide andchange end
b) clearly marked for use by persons in wheelchairs.
3.8.3.9. Food Service Lines
1) Where permanent food service lines are provided, they shall
a) be not less than 920 mm wide, and
b) have not less than 920 mm wide entry and egress points.
3.8.3.10. Floor Levels
1) Except for floors and levels specifically excluded in Subsection 3.8.2., floors and levels at different elevations shall be connected by
a) change begina ramp conforming to Article 3.8.3.3.,
b) an elevator conforming to Appendix E of ASME A17.1/CSA B44, “Safety Code for Elevators and Escalators,”
c) an elevating device for persons with disabilities conforming to CAN/CSA-B355, “Lifts for Persons with Physical Disabilities,” or
d) other means acceptable to the authority having jurisdiction.change end
3.8.3.11. Tactile Warning Systems
1) To assist persons with a visual impairment, tactile warning strips conforming to Sentence (2) shall be provided at the top of a stairway and at intermediate landings intercepted by other paths of travel.
2) change beginTactile warning strips required by Sentence (1) shall measure 725 mm to 775 mm by the full width of the stair and be
a) locatedchange end one tread width back from the top riser,
b) slip-resistant,
c) durable,
d) not more than 3 mm above or below the surrounding floor surface,
e) detectable change beginwhen walked upon,change end as being different from the surrounding flooring, and
f) in a contrasting colour to the surrounding flooring. (See Appendix A.)
3.8.3.12. Directional Signs
1) Except as permitted change beginbychange end Sentence (2), signs conforming to Sentence (3) shall be installed to provide adequate identification of, and direction to,
a) an alternate main entrance as required by Sentence 3.8.3.5.(2),
b) alternate access routes,
c) accessible viewing positions,
d) accessible refreshment facilities,
e) accessible washrooms and toilet rooms,
f) levels of a multi-level parking structure containing parking stalls for persons with disabilities,
g) parking stalls conforming to Article 3.8.3.4., and
h) accessible checkout lanes.
2) Sentence (1) need not apply to buildings or parts of buildings where the degree of accessibility provided is such as to make these signs unnecessary.
3) Signs required by Sentence (1) shall
a) be located so as to be easily read and understood,
b) be located so as to be seen by a person in a wheelchair,
c) have a glare-free surface,
d) for parking spaces, be 1 500 mm above the ground measured to the bottom of the sign,
e) have characters with a stroke width-to-height ratio of from 1:6 to 1:10 and a character width-to-height ratio of from 3:5 to 1:1 using only Arabic numerals and sans-serif letters,
f) have characters and symbols in colours that contrast highly with their backgrounds, and
g) contain the International Symbol of Accessibility for persons with disabilities and any additional wording and symbols necessary to convey full understanding.
3.8.3.13. Door Numbers
1) To assist persons with a visual impairment, change beginin occupancies described in Sentence (2),change end doors and openings that lead from any public area and through which the public is permitted to pass shall be identified by Arabic numerals or sans-serif letters or both change beginthatchange end shall be
a) not less than 25 mm high and raised between 0.7 mm and 3 mm with a high stroke width-to-height ratio for ease of reading by touch, and
b) located at the side of doors or openings, centered 1 350 mm above the finished floor and within 150 mm of the jamb.
2) The identification of doors and openings change beginrequired by Sentence (1)change end shall apply to the following occupancies
a) fine arts theatres,
b) bowling alleys,
c) court houses,
d) restaurants,
e) passenger terminals,
f) hotels and motels,
g) offices, including dental and medical offices, and
h) such other occupancies, and parts of occupancies, as required by the authority having jurisdiction.
3.8.3.14. Sleeping Units
1) Where accessible sleeping units are required by Subsection 3.8.2., they shall have
a) sufficient space to provide a turning area of not less than 1 500 mm diameter on one side of a bed,
b) sufficient space to provide a clearance of not less than 900 mm to allow for functional use of units by persons in wheelchairs,
c) an accessible balcony where balconies are provided,
d) at least one closet that provides
i) a clear opening not less than 900 mm wide,
ii) clothes hanger rods capable of being lowered to a height of 1 200 mm, and
iii) at least one shelf capable of being lowered to a height of 1 200 mm,
e) accessible light switches, thermostats and other controls that are specifically provided for use by the occupant change beginand arechange end located between 900 mm and 1 200 mm above the finished floor,
f) accessible electrical receptacles located between 455 mm and 1 200 mm above the finished floor,
g) an accessible razor outlet where a razor outlet is provided, and
h) a bathroom, where provided as part of a sleeping unit,
i) conforming to Sentence 3.7.2.10.(3), except that the water closet seat shall be between 355 mm and 405 mm above the finished floor and shall have available a 115 mm high lift seat having openings on each side and the front for personal hygiene,
ii) conforming to Clause 3.7.2.10.(4)(a), except that the grab bar need only be not less than 600 mm long with the centre line located 715 mm to 840 mm above the finished floor change beginandchange end the bar projecting 50 mm beyond the front edge of the water closet,
iii) conforming to Clause 3.7.2.10.(4)(b),
iv) conforming to Sentences 3.7.2.10.(5), (7), (8) and (10) only to the extent of providing the same type of facilities provided in sleeping units for persons without disabilities, and
v) having clear floor space not less than 1 500 mm by 1 500 mm, which may include the water closet.
3.8.3.15. Viewing Positions
1) Each viewing position required by Subsection 3.8.2. shall be
a) change begineither
i) a level area with removable seating to allow the space to be used by persons in wheelchairs, or
ii) a clear and level area not less than 900 mm wide and either 1 525 mm long to permit side entry of the wheelchair or 1 220 mm long where the wheelchair enters from the front or rear of the space and shall provide a clear view of the event taking place,
b) arranged so that at least two positions are side by side, and
c) located so as not to interfere with egress from any row of seating or infringe on any aisle requirements.
2) In motion picture theatres, viewing positions shall not be located in the front third portion of the seating area.change end
3.8.3.16. Public Telephones
1) In each location where more than one public telephone is installed, at least one change beginpublic telephonechange end shall
a) be provided with unobstructed access, not less than 800 mm wide and 800 mm deep, change beginto within 300 mm of the front of the telephone,change end
b) have a vertical clearance of not less than 715 mm under a directory shelf,
c) have the centre of the coin slot not more than 1 200 mm above the finished floor,
d) have an adjacent shelf at least 250 mm wide by 350 mm deep with a clearance above the shelf of at least 250 mm(See Appendix A),
e) have a handset incorporating a hearing aid coupler coil, and
f) be identified as being usable by persons in wheelchairs and persons with a hearing disability.
3.8.3.17. Drinking Fountains
1) In each location where drinking fountains or fountains are installed, change beginat leastchange end one fountain shall
a) have a spout opening not less than 750 mm nor more than 915 mm above the finished floor,
b) have lever or push-bar controls operable by a force of not more than 22 N located either on the front or on both sideschange begin, and
c) where located in an alcove, conform to Sentence (2).change end
2) change beginA drinking fountain described by Clause (1)(c) shall
a) be located in an alcove not less than 800 mm wide, and
b) be of the surface-mounted type.change end
3.8.3.18. Counters
1) change beginWhere counters serving the public and intended as a work surface for extended business transactions are provided, at least one accessible counter shall be provided that
a) has its work surface not more than 865 mm above the floor, and
b) is not less than 760 mm long centered over the knee space required by Sentence (2). (See Appendix A and Appendix Note A-3.8.2.1. in Appendix A.)change end
2) Knee space beneath an accessible counter intended to be used as a work surface shall be not less than
a) 760 mm wide,
b) 685 mm high, and
c) 485 mm deep.
3.8.3.19. Egress from Floor Areas
1) Every floor area that is not sprinklered throughout and that is required to be accessible shall
a) be served by an elevator
ii) protected against fire in conformance with Clause 3.2.6.5.(3)(b) or (c), and
iii) in a building over 3 storeys in building height, protected against smoke movement so that the hoistway will not contain more than 1% by volume of contaminated air from a fire floor during a period of 2 h after the start of a fire, assuming an outdoor temperature equal to the January design temperature on a 2.5% basis determined in conformance with Article 1.1.3.1.,
b) be divided into at least 2 zones by fire separations conforming to Sentences (2), (3) and (4) so that
i) persons with disabilities can be accommodated in each zone, and
ii) the travel distance from any point in one zone to a doorway leading to another zone shall be not more than the travel distance permitted by Sentence 3.4.2.5.(1) for the occupancy classification of the zone,
c) in the case of residential occupancies, be provided with balconies conforming to Sentence (5), except on the storey containing the accessible entrance,
d) have an accessible exterior exit at ground level, or
e) have a ramp conforming to Article 3.8.3.3. leading to ground level.(See Appendix A.)
2) Except as permitted by Sentence (3), the fire separations referred to in Clause (1)(b) shall have a fire-resistance rating not less than 1 h.
3) The fire-resistance rating of the fire separations referred to in Clause (1)(b) is permitted to be less than 1 h but not less than 45 min provided the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1 h for
a) the floor assembly above the floor area, or
b) the floor assembly below the floor area, if there is no floor assembly above.
4) A closure in a fire separation referred to in Clause (1)(b) shall be weatherstripped or otherwise designed and installed to retard the passage of smoke. (See Appendix Note A-3.3.3.5.(6) in Appendix A.)
5) A balcony required by Clause (1)(c) shall
a) have direct access from the suite or floor area,
b) be not less than 1.5 m deep from the outside face of the exterior wall to the inside edge of the balcony, and
c) provide not less than 2 m2 of balcony space for each accessible sleeping room.
3.8.3.20. Assistive Listening Devices
1) Where assistive listening systems are required, they shall be provided throughout the entire seating area except that with an induction loop system only half the seating area need be encompassed. (See Appendix A)
3.8.3.21. Controls
1) Except as required by Sentence 3.5.2.1.(3) for elevators, controls for the operation of building services or safety devices, including electrical switches, thermostats and intercom switches, intended to be operated by the occupant and located in or adjacent to an accessible path of travel shall be
a) change beginaccessible to a person in a wheelchair,
b) operable with one hand, and
c) mounted between 400 mm and 1 200 mm above the floor.change end

3.8.4. Alterations and Additions to Existing Buildings

3.8.4.1. Application
1) Except as provided in change beginSentence (2)change end, access as described in Article 3.8.4.2. to 3.8.4.8. shall be provided
a) change beginto additions to existing buildings where such additions have internal pedestrian connections with the existing buildings,
b) to existing parts of buildings to which additions described in Clause (a) are made, and
c) to the extent required by Article 3.8.4.5., to existing buildings
i) where the occupancy is changed, or
ii) that are altered or renovated.change end
2) This Subsection does not apply to
b) vertical additions of one storey not more than 600 m2 in floor area regardless of occupancy, or
c) horizontal or vertical additions to occupancies described in Clauses 3.8.2.1.(2)(b) to (e).change end
3.8.4.2. Specific Requirements
1) Exterior access shall be provided to an addition except where access to the addition is provided by way of the existing building.
2) Walks and ramps for an addition shall conform to Subsection 3.8.3.
3) A main entrance to an addition shall be accessible except where the addition is accessible by an accessible path of travel from an accessible main entrance serving the existing building.
3.8.4.3. Vertical Additions
1) Where there is a vertical addition of one storey and of more than 600 m2 in floor area, or of two or more storeys regardless of floor area,
a) access shall be provided to all additional storeys, and
b) the additional storeys shall conform to Sbusections 3.8.2. and 3.8.3.
3.8.4.4. Horizontal Additions
1) Where an existing building is extended horizontally, the requirements of Subsections 3.8.2. and 3.8.3. shall be applied to the addition except as described in Articles 3.8.4.2. and 3.8.4.6., and Sentence 3.8.4.8.(2).
3.8.4.5. Alterations and Occupancy Change
1) Where an existing building is altered or renovated, or where the occupancy is changed, access shall be provided in conformance with Subsections 3.8.2. and 3.8.3. where
a) persons with disabilities could reasonably be expected to be employed in, or could reasonably be expected to use, such an occupancy or building, and
b) providing such access would be practical.
3.8.4.6. Sleeping Units
1) Where sleeping units are provided in an addition, the percentage of accessible sleeping units required by Subsection 3.8.2. to conform to Article 3.8.3.14. shall be based on the sum of sleeping units in the addition and in the existing building.
2) The accessible sleeping units required by Sentence (1) may be distributed between the addition and the existing building.
3.8.4.7. Existing Facilities
1) Where an addition is required to be accessible, facilities located in the existing buildingchange beginthatchange end are necessary to the operation of the addition shall be accessible.
3.8.4.8. Egress from Floor Areas
1) The egress requirements of Article 3.8.3.19. shall apply to the vertical additions described in Sentence 3.8.4.3.(1).
2) Where an existing storey is extended horizontally, the egress requirements of Article 3.8.3.19. shall apply to
a) the extended portion of the storey, or
b) the combined area of the existing storey and the extension.

3.8.5. Adaptable Dwelling Units

3.8.5.1. Application
1) This Subsection applies to
a) the design and construction of one storey change beginadaptable dwelling unitschange end in multiple unit residential occupancy buildings change beginthatchange end employ interior corridors or exterior passageways for access to the dwelling units, and
b) the paths of travel and common facilities intended for use by the residents.
3.8.5.2. Construction Requirements
1) The construction of adaptable dwelling units and the buildings in which they are located shall conform to the requirements in this Subsection and change begintochange end access requirements for residential occupancy buildings elsewhere in this Code.
3.8.5.3. Building Access Requirements
1) Buildings containing change beginadaptable dwelling unitschange end shall
a) conform to Article 3.8.2.27., and
b) provide access to all common facilities.
2) Corridors and passageways providing access to adaptable dwelling unit entrances and common facilities shall
a) change beginbe not less than 1 220 mm in width, and
b) provide a clear area not less than 1 500 mm by 1 500 mm
i) adjacent to the elevator entrance, and
ii) at intervals not exceeding 10 m where the corridor or passageway exceeds 10 m measured from the elevator entrance to the end of the corridor or passageway.change end
3) Except as permitted in Sentence 3.8.5.4.(1), doorways in the accessible path of travel throughout the building shall have a clear opening width not less than 850 mm.
3.8.5.4. Adaptable Dwelling Unit Doorways
1) Within an adaptable dwelling unit, doorways providing access to common living areas and at least one bathroom and one bedroom shall have a clear opening width of not less than 800 mm.
2) Floor space on both sides of the bathroom and bedroom doors referred to in Sentence (1) shall conform to Clause 3.3.1.13.(10)(b).
3.8.5.5. Adaptable Dwelling Unit Bathrooms
1) The bathroom referred to in Sentence 3.8.5.4.(1) shall be designed to be adaptable for use by persons in wheelchairs by providing
a) a dimension from the front edge of the toilet to the facing wall of not less than 800 mm,
b) a dimension from the front face of the bathtub or shower to the centre line of the toilet not less than 510 mm, and
c) a clear floor area in front of the lavatory not less than 760 mm wide by 1 220 mm deep centred on the lavatory.
2) Walls adjacent to the toilet and bathtub or shower shall accommodate the future installation of grab bars conforming to Clauses 3.7.2.10.(4)(a) and (j) or 3.7.2.10.(11)(j) which will resist a vertical and horizontal load of not less than 1.3 kN. (See Appendix A.)
3.8.5.6. Adaptable Dwelling Unit Kitchens
1) The kitchen in an adaptable dwelling unit shall be designed so that the range and sink are adjacent or can have a continuous counter between them.
3.8.5.7. Outlets, Switches and Controls
1) Electrical, telephone, cable and data outlets intended for use by the occupants shall be located between 455 mm and 1 200 mm above the floor.
2) Switches and controls intended for occupant use shall be located between 900 mm and 1 200 mm above the floor.

contentHistory