Division B
Acceptable Solutions

Part 9 — Housing and Small Buildings

Section 9.15. Footings and Foundations

9.15.1. Application

9.15.1.1. General
(See Appendix A and A-9.4.4.6. and 9.15.1.1. in Appendix A.)
1) Except as provided in Articles 9.15.1.2. and 9.15.1.3., this Section applies to
a) concrete or unit masonry foundation walls and concrete footings not subject to surcharge
i) on stable soils with an allowable bearing pressure of change begin75 kPa orchange end greater, and
ii) for buildings of wood-frame or masonry construction,
b) wood-frame foundation walls and wood or concrete footings not subject to surcharge
i) on stable soils with an allowable bearing pressure of 75 kPa or greater, and
ii) for buildings of wood-frame construction, and
c) flat insulating concrete form foundation walls and concrete footings not subject to surcharge (see A-9.15.1.1.(1)(c) and 9.20.1.1.(1)(b) in Appendix A)
i) on stable soils with an allowable bearing pressure of 75 kPa or greater, and
ii) for buildings of light-frame or flat insulating concrete form construction that are not more than 2 storeys in building height, with a maximum floor to floor height of 3 m, and containing only a single dwelling unit.

contentHistory

2) Intent StatementFoundations for applications other than as described in Sentence (1) shall be designed in accordance with Section 9.4.
9.15.1.2. Permafrost
1) Intent StatementBuildings erected on permafrost shall have foundations designed by a designer competent in this field in accordance with the appropriate requirements of Part 4.
9.15.1.3. Foundations for Deformation-Resistant Buildings
1) Intent StatementWhere the superstructure of a detached building conforms to the requirements of the deformation resistance test in Z240.2.1, “Structural Requirements for Manufactured Homes,” the foundation shall be constructed in conformance with
a) the remainder of this Section, or

9.15.2. General

9.15.2.1. Concrete
1) Intent StatementConcrete shall conform to Section 9.3.
9.15.2.2. Unit Masonry Construction
1) Intent StatementConcrete block shall conform to CAN/CSA-A165.1, “Concrete Block Masonry Units,” and shall have a compressive strength over the average net cross-sectional area of the block of not less than 15 MPa.
2) Intent StatementMortar, grout, mortar joints, corbelling and protection for unit masonry shall conform to Section 9.20.
3) Intent StatementFor concrete block foundation walls required to be reinforced,
a) mortar shall be Type S, conforming to CAN/CSA-A179, “Mortar and Grout for Unit Masonry,”
b) grout shall be coarse, conforming to CAN/CSA-A179, “Mortar and Grout for Unit Masonry,” and
c) placement of grout shall conform to CAN/CSA-A371, “Masonry Construction for Buildings.”
9.15.2.3. Pier-Type Foundations
1) Intent StatementWhere pier-type foundations are used, the piers shall be designed to support the applied loads from the superstructure.
2) Intent StatementWhere piers are used as a foundation system in a building of 1 storey in building height, the piers shall be installed to support the principal framing members and shall be spaced not more than 3.5 m apart along the framing, unless the piers and their footings are designed for larger spacings.
3) Intent StatementThe height of piers described in Sentence (2) shall not exceed 3 times their least dimension at the base of the pier.
4) Intent StatementWhere concrete block is used for piers described in Sentence (2), they shall be laid with cores placed vertically, and where the width of the building is 4.3 m or less, placed with their longest dimension at right angles to the longest dimension of the building.
9.15.2.4. Wood-Frame Foundations
1) Intent StatementFoundations of wood-frame construction shall conform to
b) Part 4.
(See Appendix A.)

9.15.3. Footings

9.15.3.1. Footings Required
1) Intent StatementFootings shall be provided under walls, pilasters, columns, piers, fireplaces and chimneys that bear on soil or rock, except that footings may be omitted under piers or monolithic concrete walls if the safe loadbearing capacity of the soil or rock is not exceeded.
9.15.3.2. Support of Footings
1) Intent StatementFootings shall rest on undisturbed soil, rock or compacted granular fill.
2) Intent StatementGranular fill shall not contain pyritic material in a concentration that will damage the building to a degree that would adversely affect its stability or the performance of assemblies. (See also Article 9.4.4.4. and A-9.4.4.4.(1) in Appendix A.)
9.15.3.3. Application of Footing Width and Area Requirements
1) Intent StatementExcept as provided in Sentence 9.15.3.4.(2), the minimum footing width or area requirements provided in Articles 9.15.3.4. to 9.15.3.7. shall apply to footings, where
a) the footings support
i) foundation walls of masonry, concrete, or flat insulating concrete form walls,
ii) above-ground walls of masonry, flat insulating concrete form walls or light wood-frame construction, and
iii) floors and roofs of light wood-frame construction,
b) the span of supported joists does not exceed 4.9 m, and
c) the specified live load on any floor supported by the footing does not exceed 2.4 kPa (see Table 4.1.5.3.).
2) Intent StatementExcept as provided in Sentence 9.15.3.4.(2), where the span of the supported joists exceeds 4.9 m, footings shall be designed in accordance with Section 4.2.
3) Intent StatementWhere the specified live load exceeds 2.4 kPa, footings shall be designed in accordance with Section 4.2.
9.15.3.4. Basic Footing Widths and Areas
1) Intent StatementExcept as provided in Sentences (2) and (3) and in Articles 9.15.3.5. to 9.15.3.7., the minimum footing width or area shall comply with Table 9.15.3.4.
2) Intent StatementWhere the supported joist span exceeds 4.9 m in buildings with light wood-frame walls, floors and roofs, footing widths shall be determined according to
a) Section 4.2., or
b) the following formula
where
W= minimum footing width,
w= minimum width of footings supporting joists not exceeding 4.9 m, as defined by Table 9.15.3.4.,
Σ sjs= sum of the supported joist spans on each storey whose load is transferred to the footing, and
storeys= number of storeys supported by the footing.
(See Appendix A.)
3) Intent StatementWhere a foundation rests on gravel, sand or silt in which the water table level is less than the width of the footings below the bearing surface,
a) the footing width for walls shall be not less than twice the width required by Sentences (1) and (2), and Articles 9.15.3.5. and 9.15.3.6., and
b) the footing area for columns shall be not less than twice the area required by Sentences (1) and (2) and Article 9.15.3.7.
Table 9.15.3.4.
change beginMinimum Footing Sizes
Forming part of Sentence 9.15.3.4.(1)
No. of Floors Supported

Minimum Width of Strip Footings, mm

Minimum Footing Area for Columns Spaced 3 m o.c.,(1) m2

Supporting Exterior Walls(2)

Supporting Interior Walls(3)

1

250

200

0.4

2

350

350

0.75

3

450

500

1.0

change end
Notes to Table 9.15.3.4.:

(1) See Sentence 9.15.3.7.(1).
(2) See Sentence 9.15.3.5.(1).
(3) See Sentence 9.15.3.6.(1).

contentHistory

9.15.3.5. Adjustments to Footing Widths for Exterior Walls
1) Intent StatementThe strip footing widths for exterior walls shown in Table 9.15.3.4. shall be increased by
a) 65 mm for each storey of masonry veneer over wood-frame construction supported by the foundation wall,
b) 130 mm for each storey of masonry construction supported by the foundation wall, and
c) 150 mm for each storey of flat insulating concrete form wall construction supported by the foundation wall.
9.15.3.6. Adjustments to Footing Widths for Interior Walls
1) Intent StatementThe minimum strip footing widths for interior loadbearing masonry walls shown in Table 9.15.3.4. shall be increased by 100 mm for each storey of masonry construction supported by the footing.
2) Intent StatementFootings for interior non-loadbearing masonry walls shall be not less than 200 mm wide for walls up to 5.5 m high and the width shall be increased by 100 mm for each additional 2.7 m of height.
9.15.3.7. Adjustments to Footing Area for Columns
1) Intent StatementThe footing area for column spacings other than shown in Table 9.15.3.4. shall be adjusted in proportion to the distance between columns.
9.15.3.8. Footing Thickness
1) Intent StatementFooting thickness shall be not less than the greater of
a) 100 mm, or
b) the width of the projection of the footing beyond the supported element.
9.15.3.9. Step Footings
1) Intent StatementWhere step footings are used,
a) the vertical rise between horizontal portions shall not exceed 600 mm, and
b) the horizontal distance between risers shall not be less than 600 mm.

9.15.4. Foundation Walls

9.15.4.1. Permanent Form Material
1) Intent StatementInsulating concrete form units shall be manufactured of polystyrene conforming to the performance requirements of CAN/ULC-S701, “Thermal Insulation, Polystyrene, Boards and Pipe Covering,” for Type 2, 3 or 4 polystyrene.
9.15.4.2. Foundation Wall Thickness and Required Lateral Support
1) Intent StatementExcept as required in Sentence (2), the thickness of foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A for walls not exceeding change begin3.0 mchange end in unsupported height.
Table 9.15.4.2.A
Thickness of Solid Concrete and Unreinforced Concrete Block Foundation Walls
Forming part of Sentence 9.15.4.2.(1)

Type of Foundation Wall

Minimum Wall Thickness, mm

Maximum Height of Finished Ground Above Basement Floor or Crawl Space Ground Cover, m

Height of Foundation Wall Laterally Unsupported at the Top(1)(2)

Height of Foundation Wall Laterally Supported at the Top(1)(2)

change begin≤ 3.0 mchange end change begin≤ 2.5 mchange end change begin> 2.5 m and
≤ 2.75 mchange end
change begin> 2.75 m and
≤ 3.0 mchange end

Solid concrete, 15 MPa min. strength

150 0.8 1.5 change begin1.5change end change begin1.4change end
200 1.2 2.15 change begin2.15change end change begin2.1change end
250 1.4 2.3 change begin2.6change end change begin2.5change end
300 1.5 2.3 change begin2.6change end change begin2.85change end

Solid concrete, 20 MPa min. strength

150 0.8 1.8 change begin1.6change end change begin1.6change end
200 1.2 2.3 change begin2.3change end change begin2.2change end
250 1.4 2.3 change begin2.6change end change begin2.85change end
300 1.5 2.3 change begin2.6change end change begin2.85change end

Unreinforced concrete block

140 0.6 0.8
190 0.9 1.2change end (3) change begin(3)change end
240 1.2 1.8 change begin(3)change end change begin(3)change end
290 1.4 2.2
Notes to Table 9.15.4.2.A:

(1) See Article 9.15.4.3.change end
(2) change beginSee Article 9.15.4.6.change end
(3) change beginSee Table 9.15.4.2.Bchange end
2) Intent StatementThe thickness of concrete in flat insulating concrete form foundation walls shall be not less than the greater of
a) 140 mm, or
b) the thickness of the concrete in the wall above.
3) Intent StatementFoundation walls made of flat insulating concrete form units shall be laterally supported at the top and at the bottom.
4) Intent StatementThe thickness and reinforcing of foundation walls made of reinforced concrete block and subject to lateral earth pressure shall conform to Table 9.15.4.2.B and Sentences (5) to (8), where
a) change beginthe walls are laterally supported at the top,change end
b) change beginaverage stable soils are encountered, andchange end
c) change beginwind loads on the exposed portion of the foundation are no greater than 0.70 kPa.change end
Table 9.15.4.2.B
change beginReinforced Concrete Block Foundation Walls Laterally Supported at the Top(1)
Forming part of Sentence 9.15.4.2.(4)
Maximum Height of Finished Ground Above Basement Floor or Crawl Space Ground Cover, m(2) Size and Spacing of Continuous Vertical Reinforcement, m at mm o.c.
190 mm Minimum Wall Thickness 240 mm Minimum Wall Thickness
Foundation Wall Height Foundation Wall Height
≤ 2.5 m ≤ 2.75 m ≤ 3.0 m ≤ 2.5 m ≤ 2.75 m ≤ 3.0 m
0.8 (3) (3) (3) (3) (3) (3)
1 (3) 1-15M at 1 800 1-15M at 1 800 (3) (3) (3)
1.2 (3) 1-15M at 1 600 1-15M at 1 600 (3) 1-20M at 2 000 1-20M at 2 000
1.4 1-15M at 1 600 1-15M at 1 600 1-15M at 1 600 (3) 1-20M at 1 800 1-20M at 1 800
1.6 1-15M at 1 400 1-15M at 1 400 1-15M at 1 400 (3) 1-20M at 1 600 1-20M at 1 600
1.8 1-15M at 1 400 1-15M at 1 400 1-15M at 1 200 (3) 1-20M at 1 600 1-20M at 1 600
2 1-15M at 1 200 1-15M at 1 000 2-15M at 1 200 1-20M at 1 600 1-20M at 1 600 1-20M at 1 600
    or        
    1-20M at 1 200        
2.2 2-15M at 1 200 2-15M at 1 000 2-15M at 1 000 1-20M at 1 400 1-20M at 1 400 1-20M at 1 400
2.4 2-15M at 1 000 2-15M at 1 000 2-15M at 800 1-20M at 1 400 1-20M at 1 400 1-20M at 1 200
2.6 n/a 2-15M at 800 2-15M at 800 n/a 1-20M at 1 000 1-20M at 1 000
    or or      
    1-25M at 1 000 1-25M at 1 000      
2.8 n/a n/a 1-20M at 600 n/a n/a 1-20M at 800
            or
            2-15M at 1 000
3 n/a n/a 1-20M at 400 n/a n/a 2-15M at 800
      or      
      1-25M at 600     change end
Notes to Table 9.15.4.2.B:

(1) See Article 9.15.4.3.
(2) See Article 9.15.4.6.
(3) No reinforcement required.
5) Intent StatementFor concrete block walls required to be reinforced, continuous vertical reinforcement shall
a) be provided at wall corners, wall ends, wall intersections, at changes in wall height, at the jambs of all openings and at movement joints,
b) extend from the top of the footing to the top of the foundation wall, and
c) where foundation walls are laterally supported at the top, have not less than 50 mm embedment into the footing, if the floor slab does not provide lateral support at the wall base.
6) Intent StatementFor concrete block walls required to be reinforced, a continuous horizontal bond beam containing not less than one 15M bar shall be installed
a) along the top of the wall,
b) at the sill and head of all openings greater than 1.20 m in width, and
c) at structurally connected floors.
7) Intent StatementIn concrete block walls required to be reinforced, all vertical bar reinforcement shall be installed along the centre line of the wall.
8) Intent StatementIn concrete block walls required to be reinforced, ladder- or truss-type lateral reinforcement not less than 3.8 mm in diameter (no. 9 ASWG) shall be installed in the bed joint of every second masonry course.
9.15.4.3. Foundation Walls Considered to be Laterally Supported at the Top
1) Intent StatementSentences (2) to (4) pertain to lateral support for walls described in Sentence 9.15.4.2.(1).
2) Intent StatementFoundation walls shall be considered to be laterally supported at the top if
a) such walls support a solid masonry superstructure,
b) the floor joists are embedded in the top of the foundation walls, or
c) the floor system is anchored to the top of the foundation walls with anchor bolts, in which case the joists may run either parallel or perpendicular to the foundation walls.
3) Intent StatementUnless the wall around an opening is reinforced to withstand earth pressure, the portion of the foundation wall beneath an opening shall be considered laterally unsupported if
a) the opening is more than 1.2 m wide, or
b) the total width of the openings in the foundation wall constitutes more than 25% of the length of the wall.
4) Intent StatementFor the purposes of Sentence (3), the combined width of the openings shall be considered as a single opening if the average width is greater than the width of solid wall between them.
5) Intent StatementFlat insulating concrete form foundation walls shall be considered to be laterally supported at the top if the floor joists are installed according to Article 9.20.17.5.
9.15.4.4. Foundation Walls Considered to be Laterally Supported at the Bottom
1) Intent StatementFlat insulating concrete form foundation walls shall be considered to be laterally supported at the bottom where the foundation wall
a) supports backfill not more than 1.2 m in height,
b) is supported at the footing by a shear key and at the top by the ground floor framing, or
c) is doweled to the footing with not less than 15M bars spaced not more than 1.2 m o.c.
9.15.4.5. Reinforcement for Flat Insulating Concrete Form Foundation Walls
1) Intent StatementHorizontal reinforcement in flat insulating concrete form foundation walls shall
a) consist of
i) one 10M bar placed not more than 300 mm from the top of the wall, and
ii) 10M bars at 600 mm o.c., and
b) be located
i) in the inside half of the wall section, and
ii) with a minimum cover of 30 mm from the inside face of the concrete.
2) Intent StatementVertical reinforcement in flat insulating concrete form foundation walls shall be
a) provided in accordance with
i) Table 9.15.4.5.A for 140 mm walls,
ii) Table 9.15.4.5.B for 190 mm walls, and
iii) Table 9.15.4.5.C for 240 mm walls,
b) located in the inside half of the wall section with a minimum cover of 30 mm from the inside face of the concrete wall, and
c) where interrupted by wall openings, placed not more than 600 mm from each side of the openings.
3) Intent StatementCold joints in flat insulating concrete form foundation walls shall be reinforced with no less than one 15M bar spaced at not more than 600 mm o.c. and embedded 300 mm on both sides of the joint.
4) Intent StatementReinforcing around openings in flat insulating concrete form foundation walls shall comply with Article 9.20.17.3. or 9.20.17.4.
Table 9.15.4.5.A
Vertical Reinforcement for 140 mm Flat Insulating Concrete Form Foundation Walls
Forming part of Sentence 9.15.4.5.(2)

Max. Height of Finished Ground Above Finished Basement Floor, m

Minimum Vertical Reinforcement

Maximum Unsupported Basement Wall Height

2.44 m 2.75 m 3.0 m
1.35 10M at 400 mm o.c. 10M at 400 mm o.c. 10M at 400 mm o.c.
1.6 10M at 400 mm o.c. 10M at 380 mm o.c. 10M at 380 mm o.c.
2 10M at 380 mm o.c. 10M at 380 mm o.c. 10M at 380 mm o.c.
2.2 10M at 250 mm o.c. 10M at 250 mm o.c. 10M at 250 mm o.c.
2.35 n/a 10M at 250 mm o.c. 10M at 250 mm o.c.
2.6 n/a 10M at 250 mm o.c. 10M at 250 mm o.c.
3 n/a n/a 15M at 250 mm o.c.
Table 9.15.4.5.B
Vertical Reinforcement for 190 mm Flat Insulating Concrete Form Foundation Walls
Forming part of Sentence 9.15.4.5.(2)

Max. Height of Finished Ground Above Finished Basement Floor, m

Minimum Vertical Reinforcement

Maximum Unsupported Basement Wall Height

2.44 m 2.75 m 3.0 m
2.2 None required 10M at 400 mm o.c. 10M at 400 mm o.c.
2.35 n/a 10M at 300 mm o.c. 10M at 300 mm o.c.
2.6 n/a 10M at 300 mm o.c. 15M at 400 mm o.c.
3.0 n/a n/a 15M at 400 mm o.c.
Table 9.15.4.5.C
Vertical Reinforcement for 240 mm Flat Insulating Concrete Form Foundation Walls
Forming part of Sentence 9.15.4.5.(2)

Max. Height of Finished Ground Above Finished Basement Floor, m

Minimum Vertical Reinforcement

Maximum Unsupported Basement Wall Height

2.44 m 2.75 m 3.0 m
2.2 None required None required None required
2.6 n/a 15M at 400 mm o.c. 15M at 400 mm o.c.
3.0 n/a n/a 15M at 400 mm o.c.
9.15.4.6. Extension above Ground Level
1) Intent StatementExterior foundation walls shall extend not less than 150 mm above finished ground level.
9.15.4.7. Reduction in Thickness
1) Intent StatementWhere the top of a foundation wall is reduced in thickness to permit the installation of floor joists, the reduced section shall be not more than 350 mm high and not less than 90 mm thick.
2) Intent StatementWhere the top of a foundation wall is reduced in thickness to permit the installation of a masonry exterior facing, the reduced section shall be
a) not less than 90 mm thick, and
b) tied to the facing material with metal ties conforming to Sentence 9.20.9.4.(3) spaced not more than
i) 200 mm o.c. vertically, and
ii) 900 mm o.c. horizontally.
3) Intent StatementThe space between wall and facing described in Sentence (2) shall be filled with mortar.
9.15.4.8. Corbelling
1) Intent Statement Corbelling of masonry foundation walls supporting cavity walls shall conform to Article 9.20.12.2.
9.15.4.9. Crack Control Joints
1) Intent StatementCrack control joints shall be provided in foundation walls more than 25 m long at intervals of not more than 15 m.
2) Intent StatementJoints required in Sentence (1) shall be designed to resist moisture penetration and shall be keyed to prevent relative displacement of the wall portions adjacent to the joint.
9.15.4.10. Interior Masonry Walls
1) Intent StatementInterior masonry foundation walls not subject to lateral earth pressure shall conform to Section 9.20.

9.15.5. Support of Joists and Beams on Masonry Foundation Walls

9.15.5.1. Support of Floor Joists
1) Intent StatementExcept as permitted in Sentence (2), foundation walls of hollow masonry units supporting floor joists shall be capped with not less than 50 mm of solid masonry or concrete, or have the top course filled with mortar or concrete.
2) Intent StatementCapping required in Sentence (1) need not be provided
a) in localities where termites are not known to occur,
b) when the joists are supported on a wood plate not less than 38 mm by 89 mm, and
c) when the siding overlaps the foundation wall not less than 12 mm.
9.15.5.2. Support of Beams
1) Intent StatementNot less than 190 mm depth of solid masonry shall be provided beneath beams supported on masonry.
2) Intent StatementWhere the beam referred to in Sentence (1) is supported below the top of the foundation walls, the ends of such beams shall be protected from the weather.
9.15.5.3. Pilasters
1) Intent StatementPilasters shall be provided under beams that frame into unit masonry foundation walls 140 mm or less in thickness.
2) Intent StatementPilasters required in Sentence (1) shall be not less than 90 mm by 290 mm and shall be bonded or tied into the wall.
3) Intent StatementThe top 200 mm of pilasters required in Sentence (1) shall be solid.

9.15.6. Parging and Finishing of Masonry Foundation Walls

9.15.6.1. Foundation Walls below Ground
1) Intent StatementConcrete block foundation walls shall be parged on the exterior face below ground level as required in Section 9.13.
9.15.6.2. Foundation Walls above Ground
1) Intent StatementExterior surfaces of concrete block foundation walls above ground level shall have tooled joints, or shall be parged or otherwise suitably finished.
9.15.6.3. Form Ties
1) Intent StatementAll form ties shall be removed at least flush with the concrete surface.