Division B
Acceptable Solutions
Part 9 — Housing and Small Buildings
Section 9.20. Masonry and Insulating Concrete Form Walls Not In Contact with the Ground
9.20.1. Application
9.20.1.1. General
Except as provided in Article 9.20.1.2., this Section applies to
For walls other than those described in Sentence (1), or where the masonry walls or insulating concrete form walls not in contact with the ground are designed for specified
loads on the basis of ultimate and serviceability limit states, Subsection 4.3.2. shall apply.
9.20.1.2. Earthquake Reinforcement
(See Appendix A.)
In locations where the spectral response acceleration, Sa(0.2), is greater than 0.55, loadbearing elements of masonry buildings more than 1 storey in building height shall be reinforced with not less than the minimum amount
of reinforcement required by Subsection 9.20.15.
In locations where the spectral response acceleration, Sa(0.2), is greater than 0.35 but less than or equal to 0.55, loadbearing elements of masonry buildings 3 storeys in building height shall be reinforced with not less than the minimum amount of reinforcement required by Subsection 9.20.15.9.20.2. Masonry Units
9.20.2.1. Masonry Unit Standards
ASTM C 73, “Calcium Silicate Brick (Sand-Lime Brick),”

9.20.2.2. Used Brick
Used bricks shall be free of old mortar, soot or other surface coating and shall conform to Article 9.20.2.1.9.20.2.3. Glass Blocks
Glass blocks shall not be used as loadbearing units or in the construction of fireplaces or chimneys. 9.20.2.4. Cellular Concrete
Masonry made with cellular concrete shall not be used in contact with the soil or exposed to the weather. 9.20.2.5. Stone

9.20.2.6. Concrete Blocks Exposed to the Weather
Concrete blocks exposed to the weather shall have density and water absorption characteristics conforming to concrete types A, B,
C, or D described in CAN/CSA-A165.1, “Concrete Block Masonry Units.”9.20.2.7. Compressive Strength
The compressive strength of concrete blocks shall conform to Table 9.20.2.7.| Table 9.20.2.7. Compressive Strength of Concrete Blocks Forming part of Sentence 9.20.2.7.(1) | ||
| Type of Unit | Minimum Compressive Strength Over Net Area, MPa | |
| Exposed to Weather | Not Exposed to Weather | |
| Solid or hollow concrete blocks | 15 | 10 |
|
Solid loadbearing cellular blocks |
Not permitted | 5 |
|
Solid non-loadbearing cellular blocks |
Not permitted | 2 |
9.20.3. Mortar and Grout

9.20.3.1. Materials

Cementitious materials and aggregates for mortar and grout shall comply with CAN/CSA-A179, “Mortar and Grout for Unit Masonry.”
If lime putty is used in mortar, it shall be made by slaking quicklime in water for not less than 24 h or soaking
hydrated lime in water for not less than 12 h.
9.20.3.2. Mortar and Grout Mixes
Mortar types shall be in accordance with Table 9.20.3.2.A
Mortar for glass block masonry shall be
Mortar shall be mixed within the proportion limits provided in Table 9.20.3.2.B, with sufficient water to bring the mixture to a consistency adequate for laying masonry units.
Grout shall be mixed within the proportion limits provided in Table 9.20.3.2.C, with sufficient water to provide a suitable flow to fill all voids completely, without excessive segregation or bleeding.
Except as provided in Sentence (6), mortar shall be used and placed in final position
Mortar and grout containing a set-control admixture shall be manufactured off-site in a batching plant and shall be used and placed
in final position within a time not exceeding the useful life stipulated
by the manufacturer.
Grout used for reinforced masonry shall be placed in accordance with the requirements of CAN/CSA-A371, “Masonry Construction for Buildings.”| Table 9.20.3.2.A Mortar Use Forming part of Sentence 9.20.3.2.(1) | ||
| Location |
Building Element |
Mortar Type |
| Exterior, Above Ground |
Loadbearing walls and columns |
S |
|
Non-loadbearing walls and columns |
N or S | |
|
Parapets, chimneys, masonry veneer |
N or S | |
| Exterior, At or Below Ground |
Foundation walls and columns |
S |
| Interior |
Loadbearing walls and columns |
N |
|
Non-loadbearing walls and columns |
N | |
| Table 9.20.3.2.B Mortar Mix Proportions (by volume) Forming part of Sentence 9.20.3.2.(3) | |||||
| Mortar Type | Portland Cement | Lime | Masonry Cement Type N | Masonry Cement Type S | Fine Aggregate (damp, loose-state sand) |
| Type S | 1 | ½ | - | - | 3½ to 4½ |
| - | - | - | 1 | 2¼ to 3 | |
| ½ | - | 1 | - | 3½ to 4½ | |
| Type N | 1 | 1 | - | - | 4½ to 6 |
| - | - | 1 | - | 2¼ to 3 | |
| Table 9.20.3.2.C Grout Mix Proportions (by volume) Forming part of Sentence 9.20.3.2.(4) | |||
| Portland Cement | Lime | Fine Aggregate (sand) | Coarse Aggregate |
| 1 | 0 to 1/10 | 2¼ to 3 times the sum of the cement and lime volumes | 1 to 2 times the sum of the cement and lime volumes |
9.20.4. Mortar Joints
9.20.4.1. Thickness
Except as provided in Sentence (2), mortar joint thickness for burned clay brick and concrete masonry units shall be 10 mm.
9.20.4.2. Solid Masonry Units
9.20.4.3. Laying of Masonry Units
Hollow masonry units shall be laid with mortar applied to head and bed joints of both inner and outer face shells.
Vertically aligned webs of hollow masonry units shall be laid in a full bed of mortar
Except for head joints left open for weep holes and ventilation, solid masonry units shall be laid with full head and bed joints.
9.20.5. Masonry Support
9.20.5.1. Masonry Support
All masonry shall be supported on masonry, concrete or steel, except that masonry veneer walls may be supported on foundations of wood frame constructed in conformance with Sentence 9.15.2.4.(1). (See Appendix A.)
Every masonry wall shall be at least as thick as the wall it supports, except as otherwise permitted in Article 9.20.12.2.9.20.5.2. Lintels or Arches
Masonry over openings shall be supported by steel, masonry or reinforced concrete lintels, or masonry arches.
Steel angle lintels supporting masonry veneer above openings shall| Table 9.20.5.2. Maximum Allowable Spans for Steel Lintels Supporting Masonry Veneer Forming part of Sentence 9.20.5.2.(2) | |||||
|
Minimum Angle Size, mm (in.) |
Maximum Allowable Spans, m (ft.-in.) |
||||
| Vertical Leg | Horizontal Leg | Thickness |
Supporting |
Supporting |
Supporting |
|
|
|
|
2.55 (8-4) |
— | — |
|
|
|
|
2.59 (8-6) |
2.47 (8-1) |
2.30 (7-7) |
|
|
|
|
2.79 (9-2) |
2.66 (8-9) |
2.48 (8-2) |
|
|
|
|
3.47 (11-5) |
3.31 (10-10) |
3.08 (10-1) |
|
|
|
|
3.64 (11-11) |
3.48 (11-5) |
3.24 (10-8) |
Steel angle lintels supporting masonry other than veneer, masonry and reinforced concrete lintels, and masonry arches shall be designed
in accordance with Part 4 to support the imposed load.
Steel angle lintels supporting masonry shall be prime painted or otherwise protected from corrosion.
9.20.6. Thickness and Height
9.20.6.1. Thickness of Exterior Walls
Masonry exterior walls, other than cavity walls, in 1-storey buildings and the top storeys of 2- and 3-storey buildings shall be not less than 140 mm thick, provided the walls are not more than 2.8 m high at the eaves and 4.6
m high at the peaks of gable ends.
The exterior walls of the bottom storeys of 2-storey buildings, and exterior walls of the bottom 2 storeys of 3-storey buildings shall be not less than 190 mm thick.
In exterior walls composed of more than one wythe, each wythe shall be not less than 90 mm thick.
9.20.6.2. Cavity Walls
Cavity walls shall be made with not less than 90 mm wide units if the joints are raked
and not less than 75 mm wide units if the joints are
not raked.
The width of a cavity in a cavity wall shall be not less than 50 mm and not greater than 150 mm.
The minimum thickness of cavity walls above the supporting base shall be 230 mm for the top 7.6 m and 330 mm for the remaining portion, except that where 75 mm wide units are used, the wall
height above the top of the foundation wall shall not exceed 6 m.
9.20.6.3. Thickness of Interior Walls
The thickness of loadbearing interior walls shall be determined on the basis of the maximum lateral support
spacing as provided in Sentences 9.20.10.1.(2) and (3).
The thickness of interior non-loadbearing walls shall be9.20.6.4. Masonry Veneer
Except for masonry veneer where each masonry unit is supported individually by the structural backing, masonry veneer shall be of
solid units not less than 75 mm thick.
Veneer described in Sentence (1) over wood-frame walls shall have not less than a 25 mm air
space behind the veneer.
Masonry veneer shall conform to Subsection 4.3.2., where the masonry units are required to be individually supported
by the structural backing.
9.20.6.5. Parapet Walls
The height of parapet walls above the adjacent roof surface shall be not more than 3 times the parapet wall thickness.
Parapet walls shall be solid from the top of the parapet to not less than 300 mm below the adjacent roof level.
9.20.6.6. Stone or Concrete Facings
Slab and panel facings of precast concrete and natural or artificial stone shall conform to Subsection 4.3.2.9.20.7. Chases and Recesses
9.20.7.1. Maximum Dimensions
Except as permitted in Sentence 9.20.7.2.(2) and Article 9.20.7.4., the depth of any chase or recess shall not exceed one third the thickness of the wall, and the width of the chase or
recess shall not exceed 500 mm.
9.20.7.2. Minimum Wall Thickness
Except as permitted in Sentence (2) and Article 9.20.7.4., no chase or recess shall be constructed in any wall 190 mm or less in thickness.
Recesses may be constructed in 190 mm walls provided they do not exceed 100 mm in depth, 750 mm in height and 500 mm in width.
9.20.7.3. Separation of Chases or Recesses
Chases and recesses shall be not less than9.20.7.4. Non-Conforming Chases or Recesses
Chases or recesses that do not conform to the limits specified in Articles 9.20.7.1. to 9.20.7.3. shall be considered as openings, and any masonry supported above such a chase or recess shall be supported by a lintel
or arch as provided in Article 9.20.5.2.9.20.7.5. Chases or Recesses Cut into Walls
Chases and recesses shall not be cut into walls made with hollow units after the masonry units are in place.
9.20.8. Support of Loads
9.20.8.1. Capping of Hollow Masonry Walls
Except as permitted in Sentence (2), loadbearing walls of hollow masonry units supporting roof or floor framing members shall be capped with
not less than 50 mm of solid masonry or have the top
course filled with concrete.
Capping required in Sentence (1) may be omitted where the roof framing is supported on a wood plate not
less than 38 mm by 89 mm.
9.20.8.2. Cavity Walls Supporting Framing Members
Floor joists supported on cavity walls shall be supported on solid units not less than 57 mm high.
Floor joists described in Sentence (1) shall not project into the cavity.
Roof and ceiling framing members bearing on cavity walls shall be supported on9.20.8.3. Bearing of Beams and Joists
In no case shall the minimum length of end bearing of beams supported on masonry be less than 90 mm.
The length of end bearing of floor, roof or ceiling joists supported on masonry shall be not less than 40 mm.
9.20.8.4. Support of Beams and Columns
Beams and columns supported on masonry walls shall be supported on pilasters where the thickness of the masonry wall or wythe is less
than 190 mm.
Not less than 190 mm depth of solid masonry or concrete shall be provided under the beam or column referred to in Sentence (1).
Pilasters required in Sentence (1) shall be bonded or tied to masonry walls.
Concrete pilasters required in Sentence (1) shall be not less than 50 mm by 300 mm.
Unit masonry pilasters required in Sentence (1) shall be not less than 100 mm by 290 mm. 9.20.8.5. Distance to Edge of Supporting Members
(See Appendix A.)
Masonry veneer of hollow units resting on a bearing support shall not project more than
Masonry veneer of solid units resting on bearing support shall not project more than one third of the width of the veneer.
Where the masonry veneer described in Sentence (2) is rough stone masonry,9.20.9. Bonding and Tying
9.20.9.1. Joints to be Offset or Reinforced
Vertical joints in adjacent masonry courses shall be offset unless each wythe of masonry is reinforced with the equivalent of
not less than 2 corrosion-resistant steel bars of 3.76 mm diam placed in the horizontal joints at vertical intervals
not exceeding 460 mm.
Where joints in the reinforcing referred to in Sentence (1) occur, the bars shall be lapped not less than 150 mm.
9.20.9.2. Bonding or Tying of Other than Masonry Veneer
Except as provided in Article 9.20.9.5. regarding masonry veneer, masonry walls that consist of 2 or more wythes shall
have the wythes bonded or tied together with masonry bonding units
as described in Article 9.20.9.3. or with metal ties as described in Article 9.20.9.4.9.20.9.3. Bonding
Where wythes are bonded together with masonry units, the bonding units shall comprise not less than 4% of the wall surface area.
Bonding units described in Sentence (1) shall be spaced not more than 600 mm vertically and horizontally in the case of brick masonry and 900 mm o.c. in the case of block or tile.
Units described in Sentence (1) shall extend not less than 90 mm into adjacent wythes.
9.20.9.4. Tying
Where 2 or more wythes are tied together with metal ties of the individual rod type, the ties
shall conform to the requirements in Sentences (3) to (6).
Other ties may be used where it can be shown that such ties provide walls that are at least as strong and as durable as those made with the individual rod type.
Metal ties of the individual rod type shall
Metal ties of the individual rod type shall
Where 2 or more wythes in walls other than cavity walls and masonry veneer/masonry backing walls are tied together with metal ties of the individual rod type, the space
between wythes shall be completely filled with mortar.
Ties described in Sentence (5) shall be
Except as required in Sentences (8) and (9), where the inner and outer wythes of cavity walls are tied with individual wire ties, the ties shall be
spaced not more than 900 mm apart horizontally and 400 mm apart vertically.
Within 100 mm of the bottom of each floor or roof assembly where the cavity extends below the assemblies, the ties described
in Sentence (7) shall be spaced not more than 600 mm apart horizontally.
Within 300 mm of any openings, the ties described in Sentence (7) shall be spaced not more than 900 mm apart.
9.20.9.5. Ties for Masonry Veneer
Masonry veneer 75 mm or more in thickness and resting on a bearing support shall be tied to masonry backing or to wood framing
members with straps that are| Table 9.20.9.5. Veneer Tie Spacing Forming part of Sentence 9.20.9.5.(1) | |
| Maximum Vertical Spacing, mm | Maximum Horizontal Spacing, mm |
| 400 | 800 |
| 500 | 600 |
| 600 | 400 |
Straps described in Sentence (1) that are fastened to wood framing members shall be
Masonry veneer individually supported by masonry or wood-frame backing shall be secured to the backing in conformance with Subsection 4.3.2.9.20.9.6. Reinforcing for Glass Block
Glass block shall have horizontal joint reinforcement of 2 corrosion-resistant bars of not less than 3.76 mm diam or expanded metal
strips not less than 75 mm wide
Reinforcement required in Sentence (1) shall be lapped not less than 150 mm. 9.20.10. Lateral Support
9.20.10.1. Lateral Support Required
Masonry walls shall be laterally supported by floor or roof construction or by intersecting masonry walls or buttresses.
The spacing of supports required in Sentence (1) shall be not more than
In applying Sentence (2), the thickness of cavity walls shall be taken as the greater of
Floor and roof constructions providing lateral support for walls as required in Sentence (1) shall be constructed to transfer lateral loads to walls or buttresses approximately at right angles to the
laterally supported walls.
9.20.11. Anchorage of Roofs, Floors and Intersecting Walls
9.20.11.1. Anchorage to Floor or Roof Assemblies where Masonry Walls Require Lateral Support
Where required to receive lateral support (see Subsection 9.20.10.), masonry walls shall be anchored to each
floor or roof assembly at maximum intervals of 2 m, except
that anchorage to floor joists not more than 1 m above grade may be omitted.
Anchors required in Sentence (1) shall be corrosion-resistant and be not less than the equivalent of 40 mm by 4.76 mm thick steel straps.
Anchors required in Sentence (1) shall be shaped to provide a mechanical key with the masonry and shall be
securely fastened to the horizontal support to develop the full strength
of the anchor.
When joists are parallel to the wall, anchors required in Sentence (1) shall extend across not less than 3 joists.
9.20.11.2. Bonding and Tying Intersecting Masonry Walls where Walls Require Lateral Support
Where bonding is used to satisfy the requirements of Sentence (1), 50% of the adjacent masonry units in the intersecting wall, distributed uniformly over the height of the intersection, shall be embedded
in the laterally supported wall.
Where tying is used to satisfy the requirements of Sentence (1), the ties shall be9.20.11.3. Anchoring Intersecting Wood-Frame Walls to Masonry Walls
Wood-frame walls shall be anchored to masonry walls that they intersect with not less than 4.76 mm diam corrosion-resistant
steel rods spaced not more than 900 mm o.c. vertically.
Anchors required in Sentence (1) shall be fastened to the wood framing at one end and shaped to provide a
mechanical key at the other end to develop the strength of the anchor.
9.20.11.4. Anchoring Wood-Frame Roof Systems to Masonry Walls
Except as permitted in Sentence (2), roof systems of wood-frame construction shall be anchored to exterior masonry walls
by not less than 12.7 mm diam anchor bolts,
The roof system described in Sentence (1) is permitted to be anchored by nailing the wall furring strips to the side of the rafter plate.
9.20.11.5. Anchoring Masonry Cornices, Sills and Trim to Masonry Walls
Cornices, sills or other trim of masonry material which project beyond the wall face shall have not less than 65% of their mass, but not less than
90 mm, within the wall or shall be adequately anchored to the
wall with corrosion-resistant anchors.
9.20.11.6. Anchoring to Masonry Piers
Where anchor bolts are to be placed in the top of a masonry pier, the pier shall conform to the requirements of Sentence 9.15.2.3.(4) and shall be capped with concrete or reinforced masonry not less than 200 mm thick.
9.20.12. Corbelling
9.20.12.1. Corbelling
The units referred to in Sentence (1) shall be corbelled so that the horizontal projection of any unit does not exceed 25 mm and the total projection does not
exceed one third of the total wall thickness.
9.20.12.2. Corbelling for Cavity Walls
Cavity walls of greater thickness than the foundation wall on which they rest shall not be corbelled but may project 25 mm over
the outer face of the foundation wall disregarding parging.
Where the foundation wall referred to in Sentence (1) is unit masonry, it is permitted to be corbelled to meet flush with the inner face of
a cavity wall provided9.20.12.3. Corbelling for Masonry Veneer
Masonry veneer resting on a bearing support shall not project more than 25 mm beyond the supporting base where the
veneer is not less than 90 mm thick, and 12 mm beyond the supporting base where the veneer is less than 90 mm thick.
In the case of rough stone veneer, the projection, measured as the average projection of the stone units, shall not exceed one-third
the bed width beyond the supporting base.
9.20.13. Control of Rainwater Penetration
9.20.13.1. Materials for Flashing
Materials used for flashing shall conform to Table 9.20.13.1.| Table 9.20.13.1. Flashing Materials Forming part of Sentence 9.20.13.1.(1) | ||
| Material | Minimum Thickness, mm | |
| Exposed Flashing | Concealed Flashing | |
| Aluminum | 0.48 | — |
| Copper | 0.46 | 0.46 |
| Copper or aluminum laminated to felt or kraft paper | — | 0.05 |
| Galvanized steel | 0.33 | 0.33 |
| Lead sheet | 1.73 | 1.73 |
| Polyethylene | — | 0.50 |
| Roll roofing, Type S | — | standard |
| Zinc | 0.46 | 0.46 |
Aluminum flashing in contact with masonry or concrete shall be effectively coated or separated from the masonry or concrete by
an impervious membrane.
9.20.13.2. Fastening of Flashing
Fastening devices for flashing shall be corrosion-resistant and, where metal flashing is used, shall be compatible with the flashing
with respect to galvanic action.
9.20.13.3. Location of Flashing
Flashing shall be installed in masonry and masonry veneer walls9.20.13.4. Extension of Flashing
When installed beneath jointed masonry window sills or over the heads of openings, flashing shall extend from the front edge of
the masonry up behind the sill or lintel.
9.20.13.5. Flashing for Weep Holes in Masonry/Masonry Walls
Flashing beneath weep holes in cavity walls and masonry veneer/masonry backing walls shall9.20.13.6. Flashing for Weep Holes in Masonry Veneer
Flashing beneath weep holes in masonry veneer over masonry backing walls shall conform to the flashing requirements for cavity walls and masonry veneer/masonry backing walls in Article 9.20.13.5.
Flashing beneath weep holes in masonry veneer over wood-frame walls shall be installed so that it extends from a point not less
than 5 mm beyond the outer face of the building element below the flashing to a point 150 mm up the wood-frame wall.
Where the frame wall is sheathed with a sheathing membrane, a non-wood-based rigid exterior insulating sheathing or a semi-rigid
insulating sheathing with an integral sheathing membrane, the flashing
shall be installed behind the sheathing membrane or insulating sheathing.
Flashing described in Sentence (2) is permitted to conform to the requirements for concealed flashing in Table 9.20.13.1.9.20.13.7. Flashing Joints
9.20.13.8. Required Weep Holes
Weep holes spaced not more than 800 mm apart shall be provided at the bottom of
The cavities or air spaces described in Sentence (1) shall include those above lintels over window and door openings required to be flashed in conformance with Article 9.20.13.3.9.20.13.9. Protection of Interior Finish
Except as provided in Sentence (3), where the interior finish of the exterior walls of a building is a type that may be damaged by moisture, exterior masonry walls, other than cavity walls or walls that are protected for their full height by a roof of a carport or porch, shall be covered on the interior surface with sheathing
membrane conforming to CAN/CGSB-51.32-M, “Sheathing, Membrane, Breather Type,” lapped not less than 100 mm at the joints.
In situations described in Sentence (1), flashing shall be provided where water will accumulate, to lead it to the exterior.
Where insulation that effectively limits the passage of water is applied by a waterproof adhesive or mortar directly to parged masonry,
the requirements for sheathing membrane in Sentence (1) do not apply. (See Appendix A.)9.20.13.10. Mortar Droppings
Cavity walls shall be constructed so that mortar droppings are prevented from forming a bridge to allow
the passage of rain water across the cavity.
9.20.13.11. Caulking at Door and Window Frames
The junction of door and window frames with masonry shall be caulked in conformance with Subsection 9.27.4.9.20.13.12. Drips beneath Window Sills
Where no flashing is installed beneath window sills, such sills shall be provided with a drip not less than 25 mm from
the wall surface.
9.20.14. Protection during Work
9.20.14.1. Laying Temperature of Mortar and Masonry
Mortar and masonry shall be maintained at a temperature not below 5°C during installation and for not less than 48 h after installation.
9.20.14.2. Protection from Weather
The top surface of uncompleted masonry exposed to the weather shall be completely covered with a waterproofing material when construction is not in progress.
9.20.15. Reinforcement for Earthquake Resistance
9.20.15.1. Amount of Reinforcement
Where reinforcement is required in this Section, masonry walls shall be reinforced horizontally and vertically with steel having
a total cross-sectional area of not less than 0.002 times the horizontal
cross-sectional area of the wall, so that not less than one-third
of the required steel area is installed either horizontally or vertically
and the remainder in the other direction.
9.20.15.2. Installation Standard
Where reinforcement for masonry is required in this Section, it shall be installed in conformance with the requirements for reinforced
masonry as contained in CAN/CSA-A371, “Masonry Construction for Buildings.”9.20.16. Corrosion Resistance
9.20.16.1. Corrosion Resistance of Connectors
Carbon steel connectors required to be corrosion-resistant shall be galvanized to at least the minimum standards in Table 9.20.16.1.| Table 9.20.16.1. Minimum Requirements for Galvanizing Forming part of Sentence 9.20.16.1.(1) | ||
| Connector Material | ASTM Standard | Coating Class or Thickness |
| Wire ties and continuous reinforcing (hot-dipped galvanizing) |
A 153/A 153M |
Class B2 or 458 g/m2 |
| Hardware and bolts |
A 153/A 153M |
See A 153/A 153M |
|
Strip, plate, bars and rolled sections (not less than 3.18 mm thick) |
A 123/A 123M |
610 g/m2 |
|
Sheet (less than 3.18 mm thick) |
A 123/A 123M |
305 g/m2 on material 0.76 mm thick(1) |
| Notes to Table 9.20.16.1.: | |
|
|
|
| (1) | ASTM A 123/A 123M does not apply to metal less than 3.18 mm thick. Galvanizing coatings may be interpolated for thicknesses between 3.18 mm and 0.76 mm. |
9.20.17. Above-Ground Flat Insulating Concrete Form Walls
9.20.17.1. Thickness of Flat Insulating Concrete Form Walls
The thickness of the concrete in flat insulating concrete form walls not in contact with the ground shall be9.20.17.2. Reinforcement for Flat Insulating Concrete Form Walls
Horizontal reinforcement in above-grade flat insulating concrete form walls shall
Vertical reinforcement in above-grade flat insulating concrete form walls shall
Vertical reinforcement required by Sentence (2) and interrupted by wall openings shall be placed not more than 600 mm from each side of the opening.
9.20.17.3. Openings in Non-Loadbearing Flat Insulating Concrete Form Walls
No openings shall occur within 1 200 mm of interior and exterior corners of exterior non-loadbearing flat insulating concrete form walls.
Portions of walls above openings in non-loadbearing flat insulating concrete form walls shall have a minimum depth of concrete of no less than 200 mm across
the width of the opening.
Openings that are more than 600 mm but not more than 3 000 mm in width in non-loadbearing flat insulating concrete form walls shall be reinforced at the top and bottom with one 10M bar.
Openings more than 3 000 mm in width in non-loadbearing flat insulating concrete form walls shall be reinforced on all four sides with two 10M bars.
Reinforcing bars described in Sentences (3) and (4) shall extend 600 mm beyond the edges of the opening.
The cumulative width of openings in non-loadbearing flat insulating concrete form walls shall not make up more than 70% of the length
of
any wall.
9.20.17.4. Openings in Loadbearing Flat Insulating Concrete Form Walls

No openings shall occur within 1 200 mm of interior and exterior corners of exterior loadbearing flat insulating concrete form walls.
In loadbearing flat insulating concrete form walls, lintels shall be provided over all openings wider than 900 mm.
Lintels described in Sentence (2) shall be constructed in accordance with Tables A-17, A-18 or A-19
Lintels described in Sentence (2) over openings wider than 1 200 mm shall be reinforced for shear with 10M stirrups at a maximum spacing of half the distance
from the bottom reinforcing bar to the top of the lintel.
9.20.17.5. Framing Supported on Flat Insulating Concrete Form Walls
Floor joists supported on the side of flat insulating concrete form walls shall be supported with joist hangers secured to wood ledger
boards.
The ledger boards referred to in Sentence (1) shall be not less than
Anchor bolts shall be used to secure ledger boards to flat insulating concrete form walls and shall be
Floor joists and building frames supported on the top of flat insulating concrete form walls shall
be anchored in conformance with Article 9.23.6.1.| Table 9.20.17.5. Maximum Anchor Bolt Spacing for the Connection of Floor Ledgers to Flat Insulating Concrete Form Walls Forming part of Sentence 9.20.17.5.(3) | ||
| Maximum Clear Floor Span, m | Maximum Anchor Bolt Spacing, mm | |
| Staggered 12.7 mm Diameter Anchor Bolts | Staggered 16 mm Diameter Anchor Bolts | |
| 2.44 | 450 | 500 |
| 3.0 | 400 | 450 |
| 4.0 | 300 | 400 |
| 5.0 | 275 | 325 |
9.20.17.6. Anchoring of Roof Framing to the Top of Flat Insulating Concrete Form Walls
Roof framing supported on the top of flat insulating concrete form walls shall be fixed to the top plates, which shall be anchored
to the wall with anchor bolts
The anchor bolts described in Sentence (1) shall be placed in the centre of the flat insulating concrete form wall and shall be embedded no less than 100 mm into the concrete.
Attachment of roof framing to wood top plates shall be in accordance with Table 9.23.3.4.9.20.17.7. Protection from Precipitation and Damage
Above-ground flat insulating concrete form walls shall be protected from precipitation and damage in conformance with Section 9.27.