Division B
Acceptable Solutions

Part 9 — Housing and Small Buildings

Section 9.18. Crawl Spaces

9.18.1. General

9.18.1.1. Application
1) Intent StatementThis Section applies to crawl spaces whose exterior walls have less than 25% of their total area above exterior ground level open to the outdoors.
9.18.1.2. Foundations
1) Intent StatementFoundations enclosing crawl spaces shall conform to Section 9.15.
9.18.1.3. Heated and Unheated Crawl Spaces
1) Intent Statement Crawl spaces shall be considered to be heated where the space
a) is used as a hot air plenum,
b) contains heating ducts that are not sealed and insulated to minimize heat loss to the space, or
c) is not separated from heated space in accordance with Section 9.25.
2) Intent StatementHeating of heated crawl spaces shall conform to Section 9.33.
3) Intent StatementInsulation, an air barrier system and a vapour barrier shall be installed in the walls of heated crawl spaces in accordance with Section 9.25.

9.18.2. Access

9.18.2.1. Access Openings
1) Intent StatementAn access opening of not less than 500 mm by 700 mm shall be provided to each crawl space where the crawl space serves a single dwelling unit, and not less than 550 mm by 900 mm for other crawl spaces.
2) Intent StatementAccess openings shall be fitted with a door or hatch, except when the crawl space is heated and the access opening into the crawl space is from an adjacent heated space.

9.18.3. Ventilation

9.18.3.1. Ventilation of Unheated Crawl Spaces
1) Intent StatementUnheated crawl spaces shall be ventilated by natural or mechanical means.
2) Intent StatementWhere an unheated crawl space is ventilated by natural means, ventilation shall be provided to the outside air by not less than 0.1 m2 of unobstructed vent area for every 50 m2 of floor area.
3) Intent StatementVents shall be
a) uniformly distributed on opposite sides of the building, and
b) designed to prevent the entry of snow, rain and insects.
9.18.3.2. Ventilation of Heated Crawl Spaces
1) Intent StatementHeated crawl spaces shall be ventilated in accordance with Section 9.32.

9.18.4. Clearance

(See also Article 9.3.2.9.)
9.18.4.1. Access Way to Services
1) Intent StatementWhere equipment requiring service such as plumbing cleanouts, traps and burners is located in crawl spaces, an access way with a height and width of not less than 600 mm shall be provided from the access door to the equipment and for a distance of 900 mm on the side or sides of the equipment to be serviced.

9.18.5. Drainage

9.18.5.1. Drainage
1) Intent StatementExcept where it can be shown to be unnecessary, the ingress of water into a crawl space shall be controlled by grading or drainage.
2) Intent StatementDrainage of foundation walls shall conform to Article 9.14.2.1.
3) Intent StatementDrainage of the ground cover or floor-on-ground in the crawl space shall conform to Subsection 9.16.3.
4) Intent StatementDrains shall conform to Section 9.14.

9.18.6. Ground Cover

9.18.6.1. Ground Cover in Unheated Crawl Spaces
1) Intent StatementWhere a crawl space is unheated, a ground cover shall be provided consisting of not less than
a) 50 mm of asphalt,
b) 100 mm of 15 MPa Portland cement concrete,
c) Type S roll roofing, or
d) 0.10 mm polyethylene.
2) Intent StatementJoints in sheet-type ground cover required in Sentence (1) shall be lapped not less than 100 mm and weighted down.
9.18.6.2. Ground Cover in Heated Crawl Spaces
1) Intent StatementWhere a crawl space is heated, a ground cover consisting of not less than 0.15 mm polyethylene sheet conforming to CAN/CGSB-51.34-M, “Vapour Barrier, Polyethylene Sheet for Use in Building Construction,” shall be change begininstalled as part of an air barrier system in accordance with Subsection 9.25.3.change end
2) Intent StatementThe ground cover required in Sentence (1) shall have its joints lapped not less than 300 mm, and
a) be sealed and change beginevenlychange end weighted down, or
b) be covered with concrete not less than 50 mm thick.
3) Intent StatementThe perimeter of the ground cover required in Sentence (1) shall be sealed to the foundation wall. (See A-9.13.4., A-9.25.3.4. and 9.25.3.6., and A-9.25.3.6.(2) and (3) in Appendix A.)
4) Intent Statementchange beginAll penetrations of the ground cover required in Sentence (1) shall be sealed against air leakage. (See Subsection 9.25.3.)change end

9.18.7. Fire Protection

9.18.7.1. Crawl Spaces as Warm Air Plenums
1) Intent StatementOnly crawl spaces under 1-storey portions of dwelling units shall be used as warm-air plenums.
2) Intent StatementEnclosing material in crawl spaces described in Sentence (1), including insulation, shall have a surface flame-spread rating not greater than 150.
3) Intent StatementCombustible ground cover in crawl spaces described in Sentence (1) shall be protected beneath each register opening with noncombustible material.
4) Intent StatementThe noncombustible register protection described in Sentence (3) shall
a) extend not less than 300 mm beyond the projection of the register opening, and
b) have up-turned edges.
(See Appendix A.)