Section 9.33. Heating and Air-conditioning

9.33.1. General

9.33.1.1. Application
1) Intent Statementchange beginThis Section applies to the design and installation of heating systems, including requirements for combustion air and air-conditioning systems serving only one dwelling unit.change end
2) Intent StatementThe design and installation of heating systems, including requirements for combustion air, and air-conditioning systems other than those change begindescribed in Sentence (1)change end shall conform to Part 6. (See Appendix A and Subsection 9.10.10.)
3) change beginSystems used for heating and air-conditioning shall conform to the energy efficiency requirements in Section 9.36.change end

contentHistory

9.33.2. Required Heating Systems

9.33.2.1. Required Heating Systems
1) Intent StatementResidential buildings intended for use in the winter months on a continuing basis shall be equipped with heating facilities conforming to this Section.

9.33.3. Design Temperatures

9.33.3.1. Indoor Design Temperatures
1) At the outside winter design temperature, required heating facilities shall be capable of maintaining an indoor air temperature of not less than
a) 22°C in all living spaces,
b) 18°C in unfinished basements, change beginandchange end
c) change beginReserved.change end
d) 15°C in heated crawl spaces.

contentHistory

9.33.3.2. Outdoor Design Temperatures
1) Intent StatementThe outdoor conditions to be used in designing heating and air-conditioning systems shall be determined in conformance with Article 1.1.3.1.

9.33.4. General Requirements for Heating and Air-conditioning Systems

9.33.4.1. Design of Heating and Air-conditioning Systems
1) Intent StatementHeating and air-conditioning systems, including ducting, and mechanical heating and refrigeration equipment, shall be designed, constructed and installed to conform to the relevant provincial or territorial regulations or municipal bylaws or, in the absence of such regulations or bylaws, with good practice such as that described in the ASHRAE Handbooks and Standards, the HRAI Digest, change beginthe CHC Handbook on Hydronic Heating Systems,change end the Hydronics Institute Manuals and the SMACNA Manuals. (See also Subsection 9.32.3. for the design of systems that also provide ventilation.)
9.33.4.2. change beginInstallation of Hydronic Heating Systems
1) Intent StatementThe installation of a hydronic heating system shall conform to applicable provincial or territorial regulations or municipal bylaws or, in the absence of such regulations or bylaws, to CAN/CSA-B214, “Installation Code for Hydronic Heating Systems.”
9.33.4.3. Reserved.
1) Reserved.change end

contentHistory

9.33.4.4. Access
1) Intent StatementEquipment forming part of a heating or air-conditioning system, with the exception of embedded pipes or ducts, shall be installed with provision for access for inspection, maintenance, repair and cleaning.
9.33.4.5. Protection from Freezing
1) Intent StatementEquipment forming part of a heating or air-conditioning system that may be adversely affected by freezing temperatures and that is located in an unheated area shall be protected from freezing.
9.33.4.6. Expansion, Contraction and System Pressure
1) Intent StatementHeating and cooling systems shall be designed to allow for expansion and contraction of the heat transfer fluid and to maintain the system pressure within the rated working pressure limits of all components of the system.
9.33.4.7. Structural Movement
1) Intent StatementMechanical systems and equipment shall be designed and installed to accommodate the maximum amount of structural movement provided for in the construction of the building.
2) Intent StatementWhere the building is in a location where the spectral response acceleration, Sa(0.2), is greater than 0.55, heating and air-conditioning equipment with fuel or power connections shall be secured to the structure to resist overturning and displacement. (See A-9.31.6.2.(3) in Appendix A.)
9.33.4.8. Asbestos
1) Intent StatementAsbestos shall not be used in air distribution systems or equipment in a form or in a location where asbestos fibres could enter the air supply or return systems.
9.33.4.9. Contaminant Transfer
1) Intent StatementSystems serving garages, and systems serving other occupied parts of a dwelling unit but located in or running through a garage, shall be designed and constructed in a manner such that means are not provided for the transfer of contaminants from the garage into other spaces in the dwelling unit.

9.33.5. Heating and Air-conditioning Appliances

9.33.5.1. Capacity of Heating Appliances
1) The required capacity of heating appliances located in a dwelling unit and serving only that dwelling unit, shall be determined in accordance with change beginCSA F280, “Determining the Required Capacity of Residential Space Heating and Cooling Appliances,”change end except that the design temperatures shall conform to Subsection 9.33.3.

contentHistory

9.33.5.2. Appliance Installation Standards
1) Except as provided in Articles 9.33.5.3. and 9.33.5.4., the installation of heating and air-conditioning equipment, including mechanical refrigeration equipment, and including provisions for mounting, clearances and air supply, shall conform to change beginthe requirements ofchange end
a) change beginCAN/CSA-B139, “Installation Code for Oil-Burning Equipment,”change end for the installation of oil-burning equipment
b) change beginthe Safety Standards Act and the following of its regulations:
i) the Gas Safety Regulation, for the installation of natural gas- and propane-burning equipment,
ii) the Electrical Safety Regulation, and
iii) the Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety Regulation, for the installation of boilers, pressure vessels, pressure piping and mechanical refrigeration,
c) CAN/CSA-B365, “Installation Code for Solid-Fuel- Burning Appliances and Equipment,” and
d) CAN/CSA-C448, “Design and Installation of Earth Energy Systems.”change end
(See also Sentence 9.33.5.3.(1).)

contentHistory

2) change beginFor the purposes of Clause (1)(c), section 3.1 of CAN/CSA-B365, “Installation Code for Solid-Fuel-Burning Appliances and Equipment.” shall be read as though that section included the following paragraph:
a) an alternative safety approach under which a solid-fuel-burning boiler is accepted for use under section 10 of the Safety Standards Act.change end

contentHistory

9.33.5.3. Design, Construction and Installation Standard for Solid-Fuel-Burning Appliances
(See Appendix A.)
1) Intent StatementThe design, construction and installation, including the provision of combustion air, of solid-fuel-burning appliances and equipment, including stoves, change begincooktops, ovenschange end and space heaters, shall conform to CAN/CSA-B365, “Installation Code for Solid-Fuel-Burning Appliances and Equipment.”
9.33.5.4. Fireplaces
1) Intent StatementFireplaces shall conform to Section 9.22.

9.33.6. Air Duct Systems

9.33.6.1. Application
1) Intent StatementThe design, construction and installation of air duct distribution systems serving heating systems in which the rated heat input does not exceed 120 kW shall conform to this Subsection.
2) Intent StatementAir duct distribution systems in which the rated heat input exceeds 120 kW shall conform to Part 6 and Subsection 3.6.5.
9.33.6.2. Materials in Air Duct Systems
1) Intent StatementExcept as provided in Sentences (2) to (6) and in Article 3.6.4.3., all ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of steel, aluminum alloy, copper, clay, asbestos-cement or similar noncombustible material.
2) Intent StatementDucts, associated fittings and plenums are permitted to contain combustible material provided they
a) conform to the appropriate requirements for Class 1 duct materials in CAN/ULC-S110, “Test for Air Ducts,”
c) are not used in vertical runs serving more than 2 storeys, and
d) are not used in air duct systems in which the air temperature may exceed 120°C.
3) Intent StatementDuct sealants shall have a flame-spread rating of not more than 25 and a smoke developed classification of not more than 50.
4) Intent StatementDuct connectors that contain combustible materials and that are used between ducts and air outlet units shall
a) conform to the appropriate requirements for Class 1 air duct materials in CAN/ULC-S110, “Test for Air Ducts,”
b) be limited to 4 m in length,
c) be used only in horizontal runs, and
d) not penetrate required fire separations.
5) Intent StatementCombustible ducts that are part of a duct system carrying only ventilation air and that are contained entirely within a dwelling unit need not comply with the requirements of Sentences (1) to (4).
6) Intent StatementExcept as provided in Sentences 9.33.6.13.(2) and (3), ducts that are part of a return-air duct system and that are contained entirely within a dwelling unit need not comply with the requirements of Sentences (1) to (4).
7) Intent StatementMaterials referred to in Sentences (1) to (6), when used in a location where they may be subjected to excessive moisture, shall
a) have no appreciable loss of strength when wet, and
b) be corrosion-resistant.
9.33.6.3. Tape
1) Intent StatementTape used for sealing duct joints in air ducts, plenums and other parts of air duct systems shall meet the flame-resistance requirements for fabric in CAN/ULC-S109, “Flame Tests of Flame-Resistant Fabrics and Films.”
9.33.6.4. Coverings, Linings, Adhesives and Insulation
1) Intent StatementCoverings, linings and associated adhesives and insulation of air ducts, plenums and other parts of air duct systems shall be of noncombustible material when exposed to heated air or radiation from heat sources that would result in the exposed surface exceeding a temperature of 120°C.
2) Intent StatementExcept as provided in Sentence (3), when combustible coverings and linings, including associated adhesives and insulation, are used, they shall have
a) a flame-spread rating of not more than 25 on any exposed surface or any surface that would be exposed by cutting through the material in any direction, and
b) a smoke developed classification of not more than 50.
3) Intent StatementThe outer covering of ducts, plenums and other parts of air duct systems used within an assembly of combustible construction are permitted to have
a) an exposed surface flame-spread rating of not more than 75, and
b) a smoke developed classification greater than 50.
4) Intent StatementCombustible coverings and linings described in Sentences (2) and (3) shall not flame, glow, smoulder or smoke when tested in accordance with the method of test in ASTM C 411, “Hot-Surface Performance of High-Temperature Thermal Insulation,” at the maximum temperature to which the coverings and linings are to be exposed in service.
5) Intent StatementExcept as provided in Sentence (6), foamed plastic insulation shall not be used as part of an air duct or for insulating an air duct.
6) Intent StatementFoamed plastic insulation is permitted to be used in a ceiling space that acts as a return air plenum provided the foamed plastic insulation is protected from exposure to the plenum in accordance with Sentence 3.1.5.12.(2).
7) Intent StatementCombustible coverings and linings of ducts, including associated adhesives and insulation, shall be interrupted
a) at the immediate area of operation of heat sources in a duct system, such as electric resistance heaters or fuel-burning heaters or furnaces, and
b) where the duct penetrates a fire separation.
8) Intent StatementLinings of ducts shall be installed so that they will not interfere with the operation of volume or balancing dampers or of fire dampers, fire stop flaps and other closures.
9.33.6.5. Galvanized Steel or Aluminum Supply Ducts
1) Intent StatementGalvanized steel or aluminum supply ducts shall conform to Table 9.33.6.5.
2) Intent StatementThe design of fittings for ducts shall conform to ANSI/SMACNA 006, “HVAC Duct Construction Standards – Metal and Flexible,” except that metal thicknesses shall conform to Table 9.33.6.5.
Table 9.33.6.5.
Minimum Metal Thickness of Ducts
Forming part of Article 9.33.6.5.
Type of Duct

Maximum Diameter, mm (in.)

Maximum Width or Depth, mm (in.)

Minimum metal thickness, mm (in.)

Duct Material
Galvanized Steel Aluminum

Round ducts serving single dwelling units

125 (5) or less

0.254 (.010)

0.30 (.012)

Round

350 (14)

0.33 (.013)

0.30 (.012)

Over 350 (14)

0.41 (.016)

0.41 (.016)

Rectangular, enclosed

350 (14)

0.33 (.013)

0.30 (.012)

Over 350 (14)

0.41 (.016)

0.41 (.016)

Rectangular, not enclosed, for single dwelling units, with required clearance up to 12 mm (½ in.)

350 (14)

0.33 (.013)

0.41 (.016)

Over 350 (14)

0.41 (.016)

0.48 (.019)

Rectangular, not enclosed, with required clearance of more than 12 mm (½ in.)

350 (14)

0.41 (.016)

0.41 (.016)

Over 350 (14)

0.48 (.019)

0.48 (.019)

9.33.6.6. Construction of Ducts and Plenums
1) Intent StatementWhere the installation of heating supply ducts in walls and floors creates a space between the duct and construction material, the space shall be fire stopped with noncombustible material at each end.
2) Intent StatementDucts shall be securely supported by metal hangers, straps, lugs or brackets, except that, where zero clearance is permitted, wooden brackets are permitted to be used.
3) Intent StatementAll round duct joints shall be tight-fitting and lapped not less than 25 mm.
4) Intent StatementRectangular duct connections shall be made with S and drive cleats or equivalent mechanical connections.
5) Intent StatementDuct systems shall have no openings other than those required for the proper operation and maintenance of the system.
9.33.6.7. Installation of Ducts and Plenums
1) Intent StatementAir duct systems serving garages shall not be interconnected with other parts of the dwelling unit.
2) Intent StatementTrunk supply ducts shall not be nailed directly to wood members.
3) Intent StatementBranch ducts shall be supported at suitable spacings to maintain alignment and prevent sagging.
4) Intent StatementDucts passing through unheated spaces shall have all joints taped or otherwise sealed to ensure that the ducts are airtight throughout their length.
5) Intent StatementCombustible ducts in concrete slabs-on-ground that are connected to a furnace supply plenum shall be located not closer than 600 mm to that plenum and not less than 600 mm from its connection to a riser or register.
6) Intent StatementDucts in or beneath concrete slabs-on-ground shall be watertight and corrosion-, decay-, and mildew-resistant.
7) Intent StatementUnderground ducts shall
a) be constructed to provide interior drainage from and access to all low points, and
b) not be connected directly to a sewer.
9.33.6.8. Clearances of Ducts and Plenums
1) Intent StatementThe clearance of furnace plenums from combustible material shall conform to the appropriate standards in Sentence 9.33.5.2.(1).
2) Intent StatementWhere the plenum clearance required in Sentence (1) is 75 mm or less, the clearance between a supply duct and combustible material shall
a) be equal to the required plenum clearance within 450 mm of the plenum, and
b) be not less than 12 mm at a distance of 450 mm or more from the plenum, except that this clearance may be reduced to zero beyond a bend or offset in the duct sufficiently large to shield the remainder of the supply duct from direct radiation from the furnace heat exchanger. (See A-3.6.5.6.(2) in Appendix A.)
3) Intent StatementWhere the plenum clearance required in Sentence (1) is more than 75 mm but not more than 150 mm, the clearance between a supply duct and combustible material shall be
a) equal to the required plenum clearance within a horizontal distance of 1.8 m of the plenum, and
b) not less than 12 mm at a horizontal distance of 1.8 m or more from the plenum, except that this distance may be reduced to zero beyond a bend or offset in the duct sufficiently large to shield the remainder of the duct from direct radiation from the furnace heat exchanger. (See A-3.6.5.6.(3) in Appendix A.)
4) Intent StatementWhere the plenum clearance required in Sentence (1) is more than 150 mm, the clearance between a supply duct and combustible material shall be
a) equal to the required plenum clearance within a horizontal distance of 1 m of the plenum,
b) not less than 150 mm within a horizontal distance between 1 m and 1.8 m from the plenum, and
c) not less than 25 mm at a horizontal distance of 1.8 m or more from the plenum, except that this distance may be reduced to 8 mm beyond a bend or offset in the duct sufficiently large to shield the remainder of the supply duct from direct radiation from the furnace heat exchanger. (See A-3.6.5.6.(4) in Appendix A.)
5) Intent StatementWhere a register is installed in a floor directly over a pipeless furnace, a double-walled register box with not less than 100 mm between walls, or a register box with the warm-air passage completely surrounded by the cold-air passage, shall be permitted in lieu of the clearances listed in Sentences (2), (3) and (4).
9.33.6.9. Adjustable Dampers and Balance Stops
1) Intent StatementAll branch supply ducts that are not fitted with diffusers with adjustable balance stops shall be supplied with adjustable dampers and fitted with devices to indicate the positions of the dampers.
9.33.6.10. Warm-Air Supply Outlets and Return Inlets — General
1) Intent StatementSupply outlets and return openings in the dwelling unit, when located less than 2 m above the floor, shall be protected by grilles having openings of a size that will not allow the passage of a 15 mm diam sphere.
2) Intent StatementCombustible grilles, diffusers and other devices for the supply and return air openings installed in walls and ceilings shall have a flame-spread rating of
a) not more than 200 in bathrooms, and
b) not more than 150 in rooms or spaces other than bathrooms.
9.33.6.11. Warm-Air Supply Outlets
1) Intent StatementIn a dwelling unit, a warm-air supply outlet shall be provided in each finished room that is located adjacent to unheated space.
2) Intent StatementExcept as provided in Sentence (3), when a room described in Sentence (1) is located adjacent to exterior walls, such outlet shall be located so as to bathe at least one exterior wall or window with warm air, except in bathrooms, utility rooms or kitchens, where this may not be practical.
3) Intent StatementWhere the heating system is also designed to provide ventilation air, ceiling outlets or outlets located high on interior walls are permitted to be installed, provided the outlets are designed for this purpose and are installed with diffusers.
4) Intent StatementAt least one warm-air supply outlet shall be provided for each 40 m2 of floor surface area in unfinished basements serving dwelling units, and it shall be located so as to provide adequate distribution of warm air throughout the basement.
5) Intent StatementAt least one warm-air supply outlet shall be provided for each 80 m2 of floor surface area in heated crawl spaces serving dwelling units, and it shall be located so as to provide adequate distribution of warm air throughout the crawl space.
6) Intent StatementExcept for pipeless furnaces, the capacity of warm-air supply outlets serving dwelling units shall be not less than the design heat loss from the area served and shall not exceed 3 kW per outlet.
7) Intent StatementIn basements and heated crawl spaces, the calculated heat gain from the supply ducts and plenum surfaces is permitted to be considered in calculating the design heat loss.
8) Intent StatementThe temperature of supply air at warm-air supply outlets shall not exceed 70°C.
9) Intent StatementWarm-air supply outlets located in finished areas shall be provided with diffusers and adjustable openings and shall not be located on a furnace plenum.
9.33.6.12. Return-Air Inlets
1) Intent StatementReturn-air inlets shall not be installed in an enclosed room or crawl space that provides combustion air to a furnace.
2) Intent StatementExcept for unfinished areas and floor levels which are less than 900 mm above or below an adjacent floor level which is provided with a return-air inlet, at least one return-air inlet shall be provided in each floor level in a dwelling unit.
3) Intent StatementProvision shall be made for the return of air from all rooms by leaving gaps beneath doors, using louvred doors or installing return duct inlets.
9.33.6.13. Return-Air System
(See Appendix A.)
1) Intent StatementThe return-air system shall be designed to handle the entire air supply.
2) Intent StatementWhere any part of a return duct will be exposed to radiation from the furnace heat exchanger or other radiating part within the furnace, such part of a return duct directly above or within 600 mm of the outside furnace casing shall be noncombustible.
3) Intent StatementReturn ducts serving solid-fuel-burning furnaces shall be constructed of noncombustible material.
4) Intent StatementCombustible return ducts shall be lined with noncombustible material
a) below floor registers,
b) at the bottom of vertical ducts, and
c) under furnaces having a bottom return.
5) Intent StatementSpaces between studs or joists used as return ducts shall be separated from the unused portions of such spaces by tight-fitting metal stops or wood blocking.
6) Intent StatementA vertical return duct shall have openings to return air on not more than one floor.
7) Intent StatementThe return-air system shall be designed so that the negative pressure from the circulating fan cannot
a) affect the furnace combustion air supply, nor
b) draw combustion products from joints or openings in the furnace or flue pipe.
9.33.6.14. Filters and Odour Removal Equipment
1) Intent StatementAir filters for air duct systems shall conform to the requirements for Class 2 air filter units as described in ULC-S111, “Fire Tests for Air Filter Units.”
2) Intent StatementWhen electrostatic-type filters are used, they shall be installed so as to ensure that the electric circuit is automatically de-energized when filter access doors are opened or, in dwelling units, when the furnace circulation fan is not operating.
3) Intent StatementWhen odour removal equipment of the adsorption type is used it shall be
a) installed to provide access so that adsorption material can be reactivated or renewed, and
b) protected from dust accumulation by air filters installed on the inlet side.

9.33.7. Radiators and Convectors

9.33.7.1. Recessed Radiators and Convectors
1) Intent StatementEvery steam or hot water radiator and convector located in a recess or concealed space or attached to the face of a wall of combustible construction shall be provided with a noncombustible lining or backing.
9.33.7.2. Surface Temperature
1) Intent StatementThe exposed surface temperature of a steam or hot water radiator shall not exceed 70°C unless precautions are taken to prevent human contact.

9.33.8. Piping for Heating and Cooling Systems

9.33.8.1. Piping Materials and Installation
1) Intent StatementPiping shall be made from materials designed to withstand the effects of temperatures and pressures that may occur in the system. (See Articles 3.1.5.16., 3.1.9.1. and 9.10.9.6. for fire safety requirements.)
2) Intent StatementEvery pipe used in a heating or air-conditioning system shall be installed to allow for expansion and contraction due to temperature changes.
3) Intent StatementSupports and anchors for piping in a heating or air-conditioning system shall be designed and installed to ensure that undue stress is not placed on the supporting structure.
9.33.8.2. Insulation and Coverings
1) Intent StatementInsulation and coverings on pipes shall be composed of material suitable for the operating temperature of the system to withstand deterioration from softening, melting, mildew and mould.
2) Intent StatementInsulation and coverings on pipes in which the temperature of the fluid exceeds 120°C
a) shall be made of noncombustible material, or
b) shall not flame, glow, smoulder or smoke when tested in accordance with ASTM C 411, “Hot-Surface Performance of High-Temperature Thermal Insulation,” at the maximum temperature to which such insulation or covering is to be exposed in service.
3) Intent StatementExcept as provided in Sentence (6), where combustible insulation is used on piping in a horizontal or vertical service space, the insulation and coverings on such pipes shall have a flame-spread rating throughout the material of not more than
4) Intent StatementExcept as provided in Sentence (6), insulation and coverings on piping located in rooms and spaces other than the service spaces described in Sentence (3) shall have a flame-spread rating not more than that required for the interior finish for the ceiling of the room or space.
5) Intent StatementPipes that are exposed to human contact shall be insulated so that the exposed surface does not exceed 70°C. (See A-6.2.9.2.(2) in Appendix A.)
6) Intent StatementNo flame-spread rating or smoke developed classification limitations are required where combustible insulation and coverings are used on piping when such piping is
a) located within a concealed space in a wall,
b) located in a floor slab, or
c) enclosed in a noncombustible raceway or conduit.
9.33.8.3. Clearances
1) Intent StatementClearances between combustible material and bare pipes carrying steam or hot water shall conform to Table 9.33.8.3.
Table 9.33.8.3.
Clearance between Steam or Hot Water Pipes and Combustible Material
Forming part of Sentence 9.33.8.3.(1)
Steam or Water Temperature (T), °C Minimum Clearance, mm

T ≤ 95

no clearance required

95 < T ≤ 120

15
T > 120 25
9.33.8.4. Protection
1) Intent StatementWhere a pipe carrying steam or hot water at a temperature above 120°C passes through a combustible floor, ceiling or wall, the construction shall be protected by a sleeve of metal or other noncombustible material not less than 50 mm larger in diameter than the pipe.
2) Intent StatementUnprotected steam or hot water pipes that pass through a storage space shall be covered with not less than 25 mm thickness of noncombustible insulation to prevent direct contact with the material stored.

9.33.9. Refrigerating Systems and Equipment for Air-conditioning

9.33.9.1. Cooling Units
1) Intent StatementWhere a cooling unit is combined with a fuel-fired furnace in the same duct system, the cooling unit shall be installed
a) in parallel with the heating furnace,
b) upstream of the furnace, provided the furnace is designed for such application, or
c) downstream of the furnace, provided the cooling unit is designed to prevent excessive temperature or pressure in the refrigeration system.

9.33.10. Chimneys and Venting Equipment

9.33.10.1. Requirement for Venting
1) Intent StatementExcept as provided in Articles 9.33.10.2. and 9.33.10.3., the products of combustion from oil-, gas- and solid-fuel-burning appliances, including stoves, change begincooktops, ovenschange end and space heaters, shall be vented in conformance with the applicable appliance installation standard listed in Sentences 9.33.5.2.(1) and 9.33.5.3.(1).
9.33.10.2. Factory-Built Chimneys
1) Intent StatementFactory-built chimneys serving solid-fuel-burning appliances, and their installation, shall conform to CAN/ULC-S629-M, “650°C Factory-Built Chimneys.” (See Appendix A.)
9.33.10.3. Masonry or Concrete Chimneys
1) Intent StatementMasonry or concrete chimneys shall conform to Section 9.21.