Division B
Acceptable Solutions
Part 9 — Housing and Small Buildings
Section 9.36. Energy Efficiency
9.36.1. General
9.36.1.1. Scope
1) This Section is concerned with the energy used by
buildings as a result of
a) the design and construction of the
building envelope, and
b) the design and construction or specification of systems and equipment for
i) heating, ventilating or air-conditioning, and
ii) service water heating.
(See Appendix A.) 9.36.1.2. Definitions
2) For the purpose of this Section, the term “overall thermal transmittance,” or U-value,
shall mean the rate, in W/(m
2∙K), at which heat is transferred through a
building assembly that is subject to temperature differences. (See
Appendix A.)
3) For the purpose of this Section, the term “effective thermal resistance,” or RSI value,
shall mean the inverse of the overall thermal transmittance of an assembly, in (m
2∙K)/W. (See
Appendix A.)
4) For the purpose of this Section, the term “fenestration” shall mean all
building envelope assemblies, including their frames, that transfer visible light, such as windows, clerestories, skylights, translucent wall panels, glass block assemblies,
transoms, sidelights, sliding, overhead or swinging glass doors, and glazed inserts
in doors, etc. (See
Appendix A.)
9.36.1.3. Compliance and Application
(See Appendix A.)5) 
The following are exempted from the requirements of this Section:
b) residential
buildings that are not intended for use in the winter months on a continuing basis.
(See Appendix A.)
9.36.2. Building Envelope
9.36.2.1. Scope and Application
1) Except as provided in
Sentence (2), this Subsection is concerned with the loss of energy due to heat transfer and air leakage through materials, components and assemblies, including their interfaces,
forming part of the
building envelope where it separates
conditioned space from unconditioned space, the exterior air or the ground.
3) Except for skylight shafts addressed in
Sentence 9.36.2.6.(4)
, for the purpose of this Subsection, wall assemblies inclined less than 60° from the horizontal shall be considered as roof assemblies, and roof assemblies inclined
60° or more from the horizontal shall be considered as wall assemblies.
4) The properties, performance and installation of windows, doors and skylights shall
also conform to
Section 9.7. 9.36.2.2. Determination of Thermal Characteristics of Materials, Components and Assemblies
1) The thermal characteristics of materials shall be determined by calculation or by
testing in accordance with the applicable product standards listed in the Code or,
in the absence of such standards or where such standards do not address the determination
of thermal resistance, in accordance with
a) ASTM C 177, “Steady-State Heat Flux Measurements and Thermal Transmission Properties
by Means of the Guarded-Hot-Plate Apparatus,” or
b) ASTM C 518, “Steady-State Thermal Transmission Properties by Means of the Heat Flow
Meter Apparatus.”
(See Table A-9.36.2.4.(1)D. in Appendix A for the thermal characteristics of commonly used materials.) 2) Calculations and tests performed in accordance with
Sentence (1) shall be carried out at an average temperature of 24±2°C and under a temperature differential of 22±2°C.
3) The thermal characteristics of windows, doors and skylights shall be determined by
calculation or testing in accordance with
a) CSA A440.2/A440.3, “Fenestration Energy Performance/User Guide to CSA A440.2-09, Fenestration
Energy Performance” for the reference sizes listed therein, or
b) NFRC 100, “Determining Fenestration Product U-factors” and NFRC 200, “Determining Fenestration Product Solar Heat Gain Coefficient and Visible
Transmittance at Normal Incidence” for the reference sizes listed therein.
(See Appendix A.) 4) The effective thermal resistance of opaque
building assemblies shall be determined from
b) laboratory tests performed in accordance with ASTM C 1363, “Thermal Performance of Building Materials and Envelope Assemblies by
Means of a Hot Box Apparatus,” using an indoor air temperature of 21±1°C and an outdoor air temperature of –35±1°C.
5) The thermal characteristics of log walls shall be determined by calculation in accordance
with Section 305 of ICC 400, “Design and Construction of Log Structures.” (See
Appendix A.)
9.36.2.3. Calculation of Ceiling, Wall, Fenestration and Door Areas
1) The gross

roof-ceiling assembly area

shall be calculated as the sum of the interior surface areas of insulated

roof-ceiling assemblies

and of skylight openings.
2) Except as permitted by
Sentence (3), the gross wall area shall be calculated as the sum of the interior surface areas of all exterior
building envelope assemblies above the finished ground level that are inclined 60° or more from the horizontal, including
b) fenestration and opaque portions of doors,
c) insulated walls extending from finished ground level to the interior side of the insulated

roof-ceiling assembly,

and
d) the exposed areas of below-ground
building envelope assemblies, where fenestration or doors are located below the plane of the adjacent finished ground.
(See Appendix A.) 4) Fenestration and door areas shall be the actual sizes of windows, doors and skylights
including all related frame and sash members.
5) The fenestration area made of flat panes that are not all in the same plane or curved
panes shall be measured along the surface of the glass. (See
Appendix A.)
9.36.2.4. Calculation of Effective Thermal Resistance of Assemblies
1) In calculating the effective thermal resistance of assemblies for the purpose of comparison
with the requirements of
Articles 9.36.2.6. and 9.36.2.8., the thermal bridging effect of closely spaced, repetitive structural members, such as studs and joists, and of ancillary members, such as lintels, sills and plates,
shall be accounted for. (See
Appendix A.)
2) Minor penetrations through assemblies, such as pipes, ducts, equipment with through-the-wall
venting, packaged terminal air conditioners or heat pumps, shelf angles, anchors and
ties and associated fasteners, and minor structural members that must partially or
completely penetrate the
building envelope to perform their intended function need not be taken into account in the calculation of the effective thermal resistance of that assembly.
3) Major structural penetrations, such as balcony and canopy slabs, beams, columns and
ornamentation or appendages that must completely penetrate the
building envelope to perform their intended function, need not be taken into account in the calculation of the effective thermal resistance of the penetrated assembly, provided
a) the insulation is installed tight against the outline of the penetration, and
b) the sum of the areas of all such major structural penetrations is limited to a maximum
of 2% of the gross wall area calculated as described in
Sentence 9.36.2.3.(2).
(See Appendix A.) 4) Where a component of the
building envelope is protected by an enclosed unconditioned space, such as a sun porch, enclosed veranda, vestibule or attached garage, the required effective thermal resistance of
the
building envelope component between the
building and the unconditioned enclosure is permitted to be reduced by 0.16 (m
2∙K)/W. (See
Appendix A.)
9.36.2.5. Continuity of Insulation
1) Except as provided in
Sentences (2) to (9) and in
Sentence 9.36.2.4.(3) regarding balcony and canopy slabs, and except for clearances around components required for fire safety reasons, interior
building components that meet
building envelope components and major structural members that partly penetrate the
building envelope shall not break the continuity of the insulation and shall not decrease the effective thermal resistance at their projected area to less than that required
in
Articles 9.36.2.6. and 9.36.2.8. (See
Appendix A.)
2) Where an interior wall,
foundation wall,
firewall,
party wall or structural element penetrates an exterior wall or insulated roof or ceiling and breaks the continuity of the plane of insulation, the penetrating element shall be
insulated
a) on both of its sides, inward or outward from the
building envelope, for a distance equal to 4 times its uninsulated thickness to an effective thermal resistance not less than that required for exterior walls as stated in
Table 9.36.2.6.A. or 9.36.2.6.B.,
b) within the plane of insulation of the penetrated element to an effective thermal resistance
not less than 60% of that required for the penetrated element, or
c) within itself to an effective thermal resistance not less than that required for the
penetrated element.
(See Appendix A.) 3) Where a masonry fireplace or flue penetrates an exterior wall and breaks the continuity of the plane of insulation, it shall be insulated within the plane of insulation of
the wall or within itself to an effective thermal resistance not less than 55% of
that required for the exterior wall as stated in
Table 9.36.2.6.A. or 9.36.2.6.B. (See
Appendix A.)
4) Where an ornamentation or appendage penetrates an exterior wall and breaks the continuity
of the plane of insulation, the penetrating element shall be insulated
a) on both of its sides, inward or outward from the
building envelope, for a distance equal to 4 times the insulated thickness of the exterior wall to an effective thermal resistance not less than that required for the wall as
stated in
Table 9.36.2.6.A. or 9.36.2.6.B.,
b) within the plane of insulation of the wall to an effective thermal resistance not
less than 55% of that required for the exterior wall, or
c) within the penetrating element to an effective thermal resistance not less than that
required for the exterior wall.
5) Except as provided in
Sentences (8) and (9), where two planes of insulation are separated by a
building envelope assembly and cannot be physically joined, one of the planes of insulation shall be extended for a distance equal to at least 4 times the thickness of the assembly
separating the two planes. (See
Appendix A.)
6) 
Except as permitted by
Article 9.36.2.11., where mechanical, plumbing or electrical system components, such as pipes, ducts, conduits, cabinets, chases, panels or recessed heaters, are placed within and parallel
to a wall assembly required to be insulated, the effective thermal resistance of that
wall at the projected area of the system component shall be not less than that required
by
Tables 9.36.2.6.A., 9.36.2.6.B., 9.36.2.8.A. and 9.36.2.8.B. (See Appendix A.)
7) Except as permitted by
Article 9.36.2.11., where mechanical ducts, plumbing pipes, conduits for electrical services or communication cables are placed within the insulated portion of a floor or ceiling assembly, the
effective thermal resistance of the assembly at the projected area of the ducts, pipes,
conduits or cables shall be not less than 2.78 (m
2∙K)/W.
8) Joints and junctions between walls and other
building envelope components shall be insulated in a manner that provides an effective thermal resistance that is no less than the lower of the minimum values required for the respective
adjoining components. (See
Appendix A.)
9) Sentence (1) does not apply where the continuity of the insulation is interrupted
a) between the insulation in the
foundation wall and that of the floor slab,
c) at the horizontal portion of a
foundation wall that supports masonry veneer and is insulated on the exterior.
9.36.2.6. Thermal Characteristics of Above-ground Opaque Building Assemblies
Table 9.36.2.6.A. Effective Thermal Resistance of Above-ground Opaque Assemblies in Buildings without
a Heat-Recovery Ventilator Forming part of Sentence 9.36.2.6.(1) |
Above-ground Opaque Building Assembly | Heating Degree-Days of Building Location,(1) in Celsius Degree-Days |
Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
Minimum Effective Thermal Resistance (RSI), (m2∙K)/W |
Ceilings below attics |
6.91 |
8.67 |
8.67 |
10.43 |
10.43 |
10.43 |
Cathedral ceilings and flat roofs |
4.67 |
4.67 |
4.67 |
5.02 |
5.02 |
5.02 |
Walls(2) | 2.78 |
3.08 |
3.08 |
3.08 |
3.85 |
3.85 |
Floors over unheated spaces |
4.67 |
4.67 |
4.67 |
5.02 |
5.02 |
5.02 |
Table 9.36.2.6.B. Effective Thermal Resistance of Above-ground Opaque Assemblies in Buildings with a
Heat-Recovery Ventilator Forming part of Sentence 9.36.2.6.(1) |
Above-ground Opaque Building Assembly | Heating Degree-Days of Building Location,(1) in Celsius Degree-Days |
Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
Minimum Effective Thermal Resistance (RSI), (m2∙K)/W |
Ceilings below attics |
6.91 |
6.91 |
8.67 |
8.67 |
10.43 |
10.43 |
Cathedral ceilings and flat roofs |
4.67 |
4.67 |
4.67 |
5.02 |
5.02 |
5.02 |
Walls(2) | 2.78 |
2.97 |
2.97 |
2.97 |
3.08 |
3.08 |
Floors over unheated spaces |
4.67 |
4.67 |
4.67 |
5.02 |
5.02 |
5.02 |
3) A reduction in the effective thermal resistance of ceiling assemblies in attics under
sloped roofs is permitted for a length no greater than 1 200 mm but only to the extent imposed by the roof slope and minimum venting clearance, provided
the nominal thermal resistance of the insulation directly above the exterior wall
is not less than 3.52 (m
2∙K)/W. (See
Appendix A.)
4) Except for tubular daylighting devices, the minimum effective thermal resistance values
for walls stated in
Tables 9.36.2.6.A. and 9.36.2.6.B. shall also apply to shafts for skylights.
9.36.2.7. Thermal Characteristics of Fenestration, Doors and Skylights
Table 9.36.2.7.A. Required Thermal Characteristics of Fenestration and Doors Forming part of Sentence 9.36.2.7.(1) |
Components |
Thermal Characteristics(1) | Heating Degree-Days of Building Location,(2) in Celsius Degree-Days |
Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
Fenestration(3) and doors |
Max. U-value, W/(m2∙K)
|
1.80 |
1.80 |
1.60 |
1.60 |
1.40 |
1.40 |
2) Skylights shall have an overall thermal transmittance not greater than the values
listed in
Table 9.36.2.7.B for the applicable

heating degree-day

category. (See
Appendix A.)
Table 9.36.2.7.B Overall Thermal Transmittance of Skylights Forming part of Sentence 9.36.2.7.(2) |
Component |
Heating Degree-Days of Building Location,(1) in Celsius Degree-Days |
Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
Maximum Overall Thermal Transmittance, W/(m2∙K) |
Skylights |
2.90 |
2.90 |
2.70 |
2.70 |
2.40 |
2.40 |
3) Except for site-assembled or site-glazed factory-made fenestration products, curtain
wall construction, and site-built windows and glazed doors that are tested in accordance
with
Sentence 9.36.2.2.(3), site-built windows and glazed doors need not comply with
Sentence (1), provided they are constructed in accordance with one of the options presented in
Table 9.36.2.7.C for the applicable climate zone. (See
Appendix A.)
Table 9.36.2.7.C Compliance Options for Site-built Windows and Glazed Portion of Doors Forming part of Sentence 9.36.2.7.(3) |
Component |
Description of Component |
Compliance Options |
Climate Zones 4 and 5 |
Climate Zones 6 and 7A |
Climate Zones 7B and 8 |
≤ 3999 HDD |
4000 to 5999 HDD |
≥ 6000 HDD |
1 |
2 |
3 |
1 |
2 |
3 |
1 |
2 |
Frame |
non-metallic |
✓ |
✓ |
— |
✓ |
✓ |
— |
✓ |
✓ |
thermally broken metallic |
— |
— |
✓ |
— |
— |
✓ |
— |
— |
Glazing |
double |
— |
✓ |
— |
— |
— |
— |
— |
— |
triple |
✓ |
— |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
argon-filled |
— |
✓ |
— |
✓ |
— |
✓ |
— |
✓ |
Low-e coating |
none |
✓ |
— |
— |
— |
— |
— |
— |
— |
number of panes with ≤ 0.10 |
— |
≥ 1 |
— |
— |
— |
— |
≥ 2 |
— |
number of panes with ≤ 0.20 |
— |
— |
2 |
≥ 1 |
2 |
≥ 2 |
— |
≥ 2 |
Spacer |
size, mm |
12.7 |
— |
12.7 |
≥ 12.7 |
12.7 |
≥ 12.7 |
≥ 12.7 |
≥ 12.7 |
non-metallic |
— |
✓ |
— |
— |
— |
— |
— |
— |
4) Glass block assemblies separating
conditioned space from unconditioned space or the exterior shall have
a) an overall thermal transmittance of not more than 2.9 W/(m2∙K), and
b) a total aggregate area of not more than 1.85 m2.
5) 
[Reserved.]

6) Storm windows and doors need not comply with
Sentence (1).
7) Vehicular access doors separating a
conditioned space from an unconditioned space or the exterior shall have a nominal thermal resistance of not less than 1.1 (m
2∙K)/W.
8) Access hatches separating a
conditioned space from an unconditioned space shall be insulated to a nominal thermal resistance of not less than 2.6 (m
2∙K)/W.
9) 
A door separating a
conditioned space from an unconditioned space or the exterior is not required to conform to
Sentence (1) if,
a) in the case of a
building in a location with a heating degree-day value of less than or equal to 3999, the door is one of not more than three nonconforming doors, each of which has an overall
thermal transmittance not greater than 2.10 W/m
2·K,
b) in the case of a
building in a location with a heating degree-day value of at least 4000 and not greater than 5999, the door is one of not more than two nonconforming doors, each of which has
an overall thermal transmittance not greater than 2.10 W/m
2·K,
c) in the case of a
building in a location with a heating degree-day value of greater than or equal to 6000, the door is one of not more than two nonconforming doors, each of which has an overall
thermal transmittance not greater than 2.00 W/m
2·K, or
d) in any case, the door is the only nonconforming door and has an overall thermal transmittance
not greater than 2.60 W/m2·K.
10) A
building described in
Clause (9)(a) or (b) is permitted to have an additional nonconforming door with an overall thermal transmittance
not greater than 2.10 W/m
2·K if the effective thermal resistance of the ceilings of the building is at least 0.88 m
2·K/W greater than the relevant value shown in
Table 9.36.2.6.A. or
Table 9.36.2.6.B., as applicable.

9.36.2.8. Thermal Characteristics of Building Assemblies Below-Grade or in Contact with the Ground
1) Except as provided in
Sentence (2) and
Article 9.36.2.5., the effective thermal resistance of
building assemblies that are below-
grade or in contact with the ground shall be not less than that shown for the applicable

heating degree-day

category in
a)
Table 9.36.2.8.A., where the ventilation system does not include heat-recovery equipment, or
(See Appendix A.)
Table 9.36.2.8.A. Effective Thermal Resistance of Assemblies Below-Grade or in Contact with the Ground
in Buildings without a Heat-Recovery Ventilator Forming part of Sentences 9.36.2.8.(1) to (9) |
Building Assembly Below-Grade or in Contact with the Ground(1) | Heating Degree-Days of Building Location,(2) in Celsius Degree-Days |
Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
Minimum Effective Thermal Resistance (RSI), (m2∙K)/W |
Foundation walls |
1.99 |
2.98 |
2.98 |
3.46 |
3.46 |
3.97 |
Unheated floors(3) below frost line(4)(5) above frost line(5) | uninsulated
1.96 | uninsulated 1.96
|
uninsulated 1.96
|
uninsulated 1.96
|
uninsulated 1.96
|
uninsulated 1.96
|
Heated and unheated floors on permafrost |
n/a |
n/a |
n/a |
n/a |
4.44 |
4.44 |
Heated floors(6) | 2.32 |
2.32 |
2.32 |
2.84 |
2.84 |
2.84 |
Slabs-on-grade with an integral footing(6) | 1.96 | 1.96 |
1.96 |
3.72 |
3.72 |
4.59 |
Table 9.36.2.8.B. Effective Thermal Resistance of Assemblies Below-Grade or in Contact with the Ground
in Buildings with a Heat-Recovery Ventilator Forming part of Sentences 9.36.2.8.(1) to (9) |
Building Assembly Below-Grade or in Contact with the Ground(1) | Heating Degree-Days of Building Location,(2) in Celsius Degree-Days |
Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
Minimum Effective Thermal Resistance (RSI), (m2∙K)/W |
Foundation walls |
1.99 |
2.98 |
2.98 |
2.98 |
2.98 |
2.98 |
Unheated floors(3) below frost line(4)(5) above frost line(5) | uninsulated
1.96 | uninsulated 1.96
|
uninsulated 1.96
|
uninsulated 1.96
|
uninsulated 1.96
|
uninsulated 1.96
|
Heated and unheated floors on permafrost |
n/a |
n/a |
n/a |
n/a |
4.44 |
4.44 |
Heated floors(6) | 2.32 |
2.32 |
2.32 |
2.84 |
2.84 |
2.84 |
Slabs-on-grade with an integral footing(6) | 1.96 | 1.96 |
1.96 |
2.84 |
2.84 |
3.72 |
3) Where the top of a section of
foundation wall is on average less than 600 mm above the adjoining ground level, the above-ground portion of that section of wall shall be insulated to the effective thermal resistance required in
Table 9.36.2.8.A. or 9.36.2.8.B. 4) Unheated floors-on-ground that are above the frost line and have no embedded heating pipes, cables or ducts shall be insulated to the effective thermal resistance required
in
Table 9.36.2.8.A. or 9.36.2.8.B.a) on the exterior of the
foundation wall down to the footing, or
b) on the interior of the
foundation wall and, as applicable,
i) beneath the slab for a distance not less than 1.2 m horizontally or vertically down from its perimeter with a thermal break along the edge of the slab that meets at least 50% of the required thermal resistance,
ii) on top of the slab for a distance not less than 1.2 m horizontally from its perimeter, or
iii) within the wooden sleepers below the floor for a distance not less than 1.2 m horizontally from its perimeter.
(See Appendix A.) 5) Except as provided in
Sentence (6), floors-on-ground with embedded heating ducts, cables or pipes shall be insulated to the effective thermal resistance required in
Table 9.36.2.8.A. or 9.36.2.8.B. under their full bottom surface including the edges.
6) Where only a portion of a floor-on-ground has embedded heating ducts, cables or pipes,
that heated portion shall be insulated to the effective thermal resistance required
in
Table 9.36.2.8.A. or 9.36.2.8.B. under its full bottom surface to 1.2 m beyond its perimeter including exterior edges if applicable.
7) In addition to the requirements stated in
Sentences (5) and (6), heated floors-on-ground shall be insulated to the effective thermal resistance required in
Table 9.36.2.8.A. or 9.36.2.8.B. vertically
a) around their perimeter, or
b) on the outside of the
foundation wall, extending down to the level of the bottom of the floor.
8) Floors on permafrost shall be insulated to the effective thermal resistance required
in
Table 9.36.2.8.A. or 9.36.2.8.B. under the entire slab and around all edges, and under the integral perimeter footing.
9) Slabs-on-grade with an integral perimeter footing shall
a) be insulated to the effective thermal resistance required in
Table 9.36.2.8.A. or 9.36.2.8.B. under the entire slab and around all edges, but not under the integral perimeter footing, and
b) be constructed with skirt insulation having the same effective thermal resistance
as the insulation installed under the slab.
(See Appendix A.) (See also Sentences 9.25.2.3.(5) and 9.36.2.5.(8).) 9.36.2.9. Airtightness
2) An
air barrier system installed to meet the requirements of
Sentence (1) shall be continuous
a) across construction, control and expansion joints,
b) across junctions between different
building materials and assemblies, and
c) around penetrations through all
building assemblies.
3) Windows, doors and skylights and their components shall comply with the minimum air
leakage requirements stated in
4) Vehicular access doors that separate heated garages from unconditioned spaces or the
exterior shall be weatherstripped around their perimeter to prevent air leakage.
5) Fireplaces shall be equipped with doors, enclosures or devices to restrict air movement
through the
chimney when the fireplace is not in use. (See
Appendix A.)
9.36.2.10. Construction of Air Barrier Details
2) Materials referred to in
Sentence (1) shall be
a) compatible with adjoining materials, and
b) free of holes and cracks.
(See A-9.36.2.10.(5)(b) in Appendix A.) 4) Where the
air barrier system consists of timber logs, all joints shall be sealed to resist airflow through gaps between logs that have shifted due to in-service conditions such as shrinkage and
settling.
5) Where the
air barrier system consists of flexible sheet material, all joints shall be
a) lapped not less than 50 mm,
c) structurally supported.
6) Sealant material used for the purpose of creating a continuous
air barrier system shall
a) be a non-hardening type, or
7) Penetrations by electrical wiring, outlets, switches or recessed light fixtures through
the plane of airtightness shall be constructed airtight
a) where the component is designed to provide a seal against air leakage, by sealing
the component to the air barrier material (see
Appendix A), or
b) where the component is not designed to provide a seal against air leakage, by covering
the component with an air barrier material and sealing it to the adjacent air barrier
material.
8) The joints between the
foundation wall and the sill plate, between the sill plate and
rim joist, between the
rim joist and the subfloor material, and between the subfloor material and the bottom plate of the wall above shall be constructed airtight by
a) sealing all joints and junctions between the structural components, or
b) covering the structural components with an air barrier material and sealing it to
the adjacent air barrier material.
9) The interfaces between windows, doors and skylights and wall/ceiling assemblies shall
be constructed airtight by sealing all joints and junctions between the air barrier
material in the wall and the window, door or skylight frame. (See
Appendix A.) (See also
Subsection 9.7.6.)
10) Cantilevered floors and floors over unheated spaces or over the exterior shall be
constructed airtight by one of the following methods or a combination thereof:
a) sealing all joints and junctions between the structural components, or
b) covering the structural components with an air barrier material and sealing it to
the adjacent air barrier material.
11) Interior walls that meet exterior walls or ceilings whose plane of airtightness is
on the interior of the
building envelope and knee walls that separate
conditioned space from unconditioned space shall be constructed airtight by
a) sealing all junctions between the structural components,
b) covering the structural components with an air barrier material and sealing it to the adjacent air barrier material, or
c) maintaining the continuity of the
air barrier system above or through the interior wall or below or through the knee wall, as applicable.
12) Steel-lined
chimneys that penetrate the
building envelope shall be constructed airtight by blocking the void between required clearances for metal
chimneys and surrounding construction with sheet metal and sealant capable of withstanding high temperatures.
13) Masonry or concrete chimneys that penetrate the
building envelope shall be constructed airtight by mechanically fastening a metal flange or steel stud that extends not less than 75 mm out from the
chimney and sealing the air barrier material to it with a sealant capable of withstanding high temperatures.
14) Ducts that penetrate the
building envelope shall be constructed airtight by sealing the penetration through the
building envelope. (See
Appendix A.)
15) Plumbing vent stack pipes that penetrate the
building envelope shall be constructed airtight by
a) sealing the air barrier material to the vent stack pipe with a compatible sealant or sheathing tape, or
b) installing a rubber gasket or prefabricated roof flashing at the penetration of the
plane of airtightness then sealing it and mechanically fastening it to the top plate.
16) Where a
party wall meets the plane of airtightness, that junction shall be constructed airtight by sealing any voids within the
party wall at the perimeter to the adjacent air barrier material and by
a) sealing all junctions between the structural components, or
b) covering the structural components with an air barrier material and sealing it to the adjacent air barrier material.
17) Where the concrete in a flat insulating concrete form wall acts as the air barrier,
the continuity of the plane of airtightness shall be maintained between the concrete
and adjacent air barrier materials.
9.36.2.11. Trade-off Options for Above-ground Building Envelope Components and Assemblies
(See Appendix A.)2) The effective thermal resistance of one or more above-ground opaque
building envelope assemblies is permitted to be less than that required in
Article 9.36.2.6., provided
a) the total areas of all proposed and reference assemblies are equal,
b) the effective thermal resistance of one or more other proposed above-ground opaque
building envelope assembly areas is increased to more than that required by
Article 9.36.2.6., and
c) the sum of the areas of all traded above-ground opaque
building envelope assemblies divided by their respective effective thermal resistance is less than or equal to what it would be if all assemblies complied with
Article 9.36.2.6. (See Appendix A and A-9.36.2.11.(2) and (3) in Appendix A.) 3) The effective thermal resistance of one or more windows, as calculated in accordance with
Sentence (5), is permitted to be less than that required in
Article 9.36.2.7., provided
a) the total areas of all traded windows are equal,
b) the traded windows are located in the same orientation,
c) the effective thermal resistance of one or more other windows is increased to more than that required by
Article 9.36.2.7., and
d) the sum of the areas of all traded windows divided by their respective effective thermal
resistance is less than or equal to what it would be if all windows complied with
Article 9.36.2.7. (See Appendix A and A-9.36.2.11.(2) and (3) in Appendix A.) 4) The effective thermal resistance of one or more portions of floor insulation or ceiling insulation in attics under sloped roofs in
buildings that are one
storey in
building height is permitted to be less than that required in
Article 9.36.2.6., provided
a) the total area of fenestration, excluding skylights, and doors does not exceed 15% of the above-ground gross wall area as calculated in accordance with
Article 9.36.2.3.,
b) the floor-to-ceiling height measured from the top of the subfloor to the underside
of the finished ceiling of the
storey does not exceed 2.34 m,
c) the distance measured from the top of the subfloor to the underside of the bottom
chord of the truss or joist of the roof is not more than 2.39 m, and
d) the difference between the sum of the proposed areas of ceilings or floors divided
by their respective proposed effective thermal resistance and the sum of the reference
areas of ceilings or floors divided by their respective thermal resistance required
in
Article 9.36.2.6. is not more than the difference between 17% fenestration and door area and the proposed fenestration and door areas divided by the required effective thermal resistance values
for windows and doors in
Article 9.36.2.7. (See Appendix A and A-9.36.2.11.(2) and (3) in Appendix A.) 5) The effective thermal resistance of windows shall be determined using the following equation: RSI = 1/U.
6) The reduction in effective thermal resistance of above-ground opaque
building envelope assemblies permitted by
Sentences (2) and (4) shall result in an RSI value that is not less than
7) The effective thermal resistances of above-ground opaque assemblies with embedded
heating cables, pipes or membranes are not permitted to be traded.
9.36.3. HVAC Requirements
9.36.3.1. Scope and Application
1) This Subsection is concerned with the efficient use of energy by systems and equipment
used for heating, ventilating and air-conditioning (HVAC).
2) Where HVAC systems, equipment or techniques other than those described in this Subsection
are used, the
building shall be designed and constructed in accordance with the energy efficiency requirements of the NECB.
9.36.3.2. Equipment and Ducts
3) Except for
exhaust ducts leading directly to the exterior, ducts and
plenums carrying conditioned air and located outside the plane of insulation shall
a) except as provided in
Sentence (4), have all joints sealed against air infiltration and exfiltration with
i) sealants or gaskets made from liquids, mastics or heat-applied materials,
ii) mastic with embedded fabric, or
iii) foil-faced butyl tape, and
4) Fabric-backed tape with rubber adhesives shall not be used as a primary sealant to
meet the requirements of
Clause (3)(a).
5) The underside of rectangular ducts installed under an insulated floor over an unconditioned
space is permitted to be insulated to a lower level than required in
Sentence (3) but not to less than 2.11 (m
2∙K)/W, provided both sides of such ducts are insulated to a compensating higher thermal resistance so that the resulting heat loss does not exceed that of ducts complying
with
Sentence (3). (See
Appendix A.)
9.36.3.3. Air Intake and Outlet Dampers
1) Except as provided in
Sentences (3) and (4), every duct or opening intended to discharge air to the outdoors shall be equipped with
a) a motorized damper, or
b) a gravity- or spring-operated backflow damper.
2) Except as provided in
Sentences (3) and (4) and except in locations with fewer than 3500 heating degree-days as listed in Appendix C, every outdoor air intake duct or opening shall be equipped with a motorized damper
that remains in the “open” position if the damper fails.
3) Where other regulations are in effect that do not permit dampers, air intakes and
outlets need not comply with
Sentences (1) and (2).
4) Air intakes and outlets serving HVAC systems that are required to operate continuously
need not comply with
Sentences (1) and (2). (See
Appendix A.)
9.36.3.4. Piping for Heating and Cooling Systems
2) Except for high-temperature refrigerant piping, all piping forming part of a heating
or air-conditioning system shall be located
a) inside the plane of insulation, or
b) within or outside the plane of insulation, provided the piping is insulated to a thermal
resistance not less than that required in
Subsection 9.36.2. for exterior above-ground walls.
(See Appendix A.) 9.36.3.5. Equipment for Heating and Air-conditioning Systems
1) Equipment for heating and air-conditioning systems shall be located
a) inside the plane of insulation, or
b) outdoors or in an unconditioned space, provided the equipment is designated by the manufacturer for such installation.
(See Appendix A.) 9.36.3.6. Temperature Controls
1) Except for manually fuelled solid-fuel-fired
appliances, the supply of heating and cooling energy to each
dwelling unit,
suite or common space shall be controlled by thermostatic controls that activate the appropriate supply when the temperature in a
conditioned space fluctuates ±0.5°C from the set-point temperature for that space.
2) Where heating and cooling systems are controlled by separate thermostatic controls,
means shall be provided to prevent these controls from simultaneously calling for
heating and cooling.
4) Controls required by
Sentence (1) shall be designed such that lowering the set-point temperature on the thermostat for the heating system will not cause cooling energy to be expended to reach the lowered
setting, and raising the set-point temperature on the thermostat for the cooling system
will not cause heating energy to be expended to reach the raised setting.
5) Automatic devices or manually operated dampers, valves or switches shall be provided,
as appropriate for the heating system used, to allow the heating of each zone to be
adjusted.
6) Heat pumps equipped with supplementary heaters shall incorporate controls to prevent
supplementary heater operation when the heating load can be met by the heat pump alone,
except during defrost cycles.
7) Heat pumps with a programmable thermostat shall be equipped with setback controls
that will temporarily suppress electrical back-up or adaptive anticipation of the
recovery point, in order to prevent the activation of supplementary heat during the
heat pump’s recovery. (See
Appendix A.)
9.36.3.7. Humidification
1) Where an HVAC system is equipped with a means for adding moisture to maintain specific
humidity levels, an automatic humidity control device shall be provided.
9.36.3.8. Heat Recovery from Dehumidification in Spaces with an Indoor Pool or Hot Tub
(See Appendix A.)2) Spaces containing an indoor pool need not comply with
Sentence (1), provided a stationary mechanical or desiccant dehumidification system is installed that provides at least 80% of the dehumidification that would result from compliance
with
Sentence (1).
3) Spaces containing an indoor pool or hot tub having a total water surface area of less
than 10 m
2 need not comply with
Sentence (1), provided they are equipped with a cover having a nominal thermal resistance not less than 2.1 (m
2∙K)/W.
4) Heat-recovery systems used to meet the requirements of
Sentence (1) shall
a) be capable of recovering at least 40% of the sensible heat from exhausted air when tested in accordance with ANSI/AHRI 1060, “Performance Rating of Air-to-Air Exchangers for Energy Recovery Ventilation,”(see
Appendix A), or
b) have a sensible-heat-recovery efficiency complying with
Sentence 9.36.3.9.(3) when tested in accordance with CAN/CSA-C439, “Rating the Performance of Heat/Energy-Recovery Ventilators.”
5) The sensible heat, in kW, referred to in
Clause (4)(a), which is the sensible heat content of the total quantity of exhausted air, shall
be calculated as follows:
where
Te= temperature of exhausted air before heat recovery, in °C,
To= outdoor 2.5% January design temperature as listed in Appendix C, in °C, and
Q= rated capacity of exhaust system at normal temperature of exhausted air, in L/s.
9.36.3.9. Heat Recovery from Ventilation Systems
1) This Article applies where a self-contained mechanical ventilation system is installed
whose principal exhaust component is equipped with heat-recovery capability. (See
Appendix A.)
2) Where an integrated mechanical system (IMS) with a heat-recovery ventilator provides
the principal exhaust ventilation, the IMS shall
b) have a minimum overall thermal performance factor conforming to
Table 9.36.3.10. 3) When tested in conformance with the low-temperature thermal and ventilation test methods
described in CAN/CSA-C439, “Rating the Performance of Heat/Energy-Recovery Ventilators” heat-recovery ventilators described in
Sentence (1) shall have a sensible heat-recovery efficiency of
a) at least 60% at an outside air test temperature of 0°C for locations with a 2.5% January design temperature greater than or equal to –10°C, and
b) at least 60% at an outside air test temperature of 0°C and at least 55% at an outside
air test temperature of –25°C for locations with a 2.5% January design temperature
less than –10°C.
(See Appendix A.) 9.36.3.10. Equipment Efficiency
Table 9.36.3.10. HVAC Equipment Performance Requirements Forming part of Sentences 9.36.3.9.(2) and 9.36.3.10.(1) |
Component or Equipment |
Heating or Cooling Capacity, kW |
Standard |
Minimum Performance(1) |
Air-Cooled Unitary Air Conditioners and Heat Pumps – Electrically Operated |
Split system |
≤ 19 |
CAN/CSA-C656 | SEER = 14.5 |
EER = 11.5 |
HSPF = 7.1 (region 5 in standard) |
Single-package system |
≤ 19 |
CAN/CSA-C656 (including General Instruction No. 2) |
SEER = 14 |
EER = 11 |
HSPF = 7.0 (region 5 in standard) |
All systems |
> 19 |
CAN/CSA-C746 | See Level 2 in standard |
Water-Cooled Unitary Air Conditioners and Heat Pumps – Electrically Operated |
Ground-source and water-source heat pumps |
|
|
|
open loop |
< 40 |
CAN/CSA-C13256-1 | COPc ≥ 4.75, COPh ≥ 3.6
|
closed loop |
|
|
COPc ≥ 3.93, COPh ≥ 3.1
|
Water-to-water heat pumps |
|
|
|
open loop |
< 40 |
CAN/CSA-C13256-2 | COPc ≥ 5.60, COPh ≥ 3.4
|
closed loop |
|
|
COPc ≥ 4.21, COPh ≥ 2.8
|
Internal water-loop heat pumps |
< 5 |
CAN/CSA-C13256-1 | COPc ≥ 3.28, COPh ≥ 4.2
|
≥ 5 and ≤ 40 |
COPc ≥ 3.52, COPh ≥ 4.2
|
Water-cooled air conditioners – all types |
< 19 |
ANSI/AHRI 210/240 or CTI 201 |
COP = 3.54, ICOP = 3.60 |
Direct-Expansion Ground-Source Heat Pumps – Electrically Operated |
Direct-expansion ground-source heat pumps |
≤ 21 |
CSA C748 | EER = 13.0 |
COPh = 3.1
|
Room Air Conditioners and Room Air Conditioner Heat Pumps |
Room air conditioners with reverse cycle |
|
|
|
with louvered sides |
< 10.55 |
ANSI/AHAM RAC-1 |
EER = 8.5 |
without louvered sides |
|
|
EER = 8.0 |
Room air conditioners without reverse cycle and with louvered sides |
< 1.8 |
CAN/CSA-C368.1 | EER = 10.7 |
≥ 1.8 and < 2.3 |
EER = 10.7 |
≥ 2.3 and < 4.1 |
EER = 10.8 |
≥ 4.1 and < 5.9 |
EER = 10.7 |
≥ 5.9 |
EER = 9.4 |
Room air conditioner heat pumps with louvered sides |
< 5.9 |
EER = 9.9 |
≥ 5.9 |
EER = 9.5 |
Room air conditioners without louvered sides and without reverse cycle |
< 1.8 |
EER = 9.9 |
≥ 1.8 and < 2.3 |
EER = 9.9 |
≥ 2.3 and < 4.1 |
EER = 9.4 |
≥ 4.1 and < 5.9 |
EER = 9.4 |
≥ 5.9 |
EER = 9.4 |
Room air conditioner heat pumps without louvered sides |
< 4.1 |
EER = 9.2 |
≥ 4.1 |
EER = 8.8 |
Room air conditioner, casement only |
All capacities |
EER = 9.5 |
Room air conditioner, casement slider |
All capacities |
EER = 9.5 |
Boilers |
Electric boilers | ≤ 88 |
— |
Must be equipped with automatic water temperature control(2) |
Gas-fired boilers(3) | ≤ 88 |
CAN/CSA-P.2 | AFUE ≥ 90% |
> 88 and ≤ 117.23 |
AHRI BTS |
Et ≥ 83%
|
Oil-fired boilers | ≤ 88 |
CSA B212 or ANSI/ASHRAE 103 |
AFUE ≥ 85% |
Warm-Air Furnaces, Combination Warm-Air Furnace/Air-conditioning Units, Duct Furnaces
and Unit Heaters |
Gas-fired warm-air furnaces(3) | ≤ 65.9 |
CAN/CSA-P.2 | AFUE ≥ 92% |
> 65.9 and ≤ 117.23 |
CAN/CSA-P.8 | Et ≥ 78.5%
|
Gas-fired duct furnaces(3) | ≤ 117.23 |
ANSI Z83.8/CSA 2.6 | Et ≥ 81%
|
Gas-fired unit heaters(3) | ≤ 117.23 |
CAN/CSA-P.11 | Et ≥ 82%
|
Oil-fired warm-air furnaces | ≤ 66 |
CSA B212 | AFUE ≥ 85% |
Oil-fired duct furnaces and unit heaters | — |
UL 731 |
Ec ≥ 80%
|
Combined space- and water-heating systems (combos) |
≤ 87.9 if boiler-based |
CAN/CSA-P.9(4) | TPF = 0.65 |
≤ 73.2 if based on service water heater |
Integrated mechanical systems |
— |
CSA-P.9 | OTPF = 0.78 |
Other |
Gas-fired fireplaces and stoves(3) | — |
— |
(5) |
Solid-fuel-burning space-heating equipment |
— |
EPA 40 CFR, Part 60, Subpart AAA or CSA B415.1(6) | See standard(7) |
Dehumidifiers |
≤ 87.5 L/day |
CAN/CSA-C749 | See standard(7) |
2) Natural gas and propane fireplaces shall be
a) direct-vent (sealed), and
b) pilot-on-demand, interrupted or intermittent ignition systems without a standing pilot
light.
9.36.3.11. Solar Thermal Systems
1) Space-heating systems that use solar thermal technology shall conform to the manufacturer’s
design requirements and installation procedures.
2) Service water heating systems that use solar thermal technology shall be installed
in accordance with

Book II (Plumbing Systems) of this Code

.
9.36.4. Service Water Heating Systems
9.36.4.1. Scope and Application
1) This Subsection is concerned with the efficient use of energy by systems used to heat
service water for household use as well as for indoor pools and hot tubs.
2) Where service water heating equipment or techniques other than those described in
this Subsection are used, the
building shall be designed and constructed in accordance with the energy efficiency requirements of the NECB.
9.36.4.2. Equipment Efficiency
2) Hot service water storage tanks not listed in
Table 9.36.4.2. shall be covered with insulation having a minimum thermal resistance of 1.8 (m
2∙K)/W.
Table 9.36.4.2. Service Water Heating Equipment Performance Standards Forming part of Sentences 9.36.4.2.(1) and (2) |
Storage-Type Service Water Heaters |
Component |
Input(1) | Standard |
Performance Requirement(2) |
Electric |
≤ 12 kW (50 L to 270 L capacity) |
CAN/CSA-C191 | SL ≤ 25 + 0.20V (top inlet) |
SL ≤ 40 + 0.20V (bottom inlet) |
≤ 12 kW (> 270 L and ≤ 454 L capacity) |
SL ≤ (0.472V) – 38.5 (top inlet) |
SL ≤ (0.472V) – 33.5 (bottom inlet) |
>12 kW (> 75 L capacity) |
ANSI Z21.10.3/CSA 4.3 and DOE 10 CFR, Part 431, Subpart G |
S = 0.30 + 27/Vm |
Heat pump water heaters |
≤ 24 A and ≤ 250 V |
CAN/CSA-C745 | EF ≥ 2.0 |
Gas-fired(3) | < 22 kW |
CAN/CSA-P.3 | EF ≥ 0.67 – 0.0005V |
≥ 22 kW |
ANSI Z21.10.3/CSA 4.3 |
Et ≥ 80% and standby loss ≤ rated input(4)/(800 + 16.57∙√V) |
Oil-fired |
≤ 30.5 kW |
CAN/CSA-B211 | EF ≥ 0.59 – 0.0005V |
> 30.5 kW |
ANSI Z21.10.3/CSA 4.3 and DOE 10 CFR, Part 431, Subpart
G
|
Et ≥ 78% and standby loss ≤ rated input(4)/(800 + 16.57∙√V) |
Tankless Service Water Heaters |
Component |
Input(1) | Standard |
Performance Requirement(2) |
Gas-fired(3) | ≤ 73.2 kW |
CAN/CSA-P.7 | EF ≥ 0.8 |
> 73.2 kW |
ANSI Z21.10.3/CSA 4.3 and DOE 10 CFR, Part 431, Subpart G |
Et ≥ 80%
|
Oil-fired |
≤ 61.5 kW(5) | DOE 10 CFR, Part 430, Subpart B, Appendix
E
|
EF ≥ 0.59 − 0.0019Vm |
Other |
ANSI Z21.10.3/CSA 4.3 and DOE 10 CFR, Part 431, Subpart G |
Et ≥ 80%
|
Electric |
— |
— |
(6) |
Combined space- and water-heating systems (combos) |
≤ 87.9 kW if boiler-based |
CAN/CSA-P.9 | TPF = 0.65 |
≤ 73.2 kW if based on service water heater |
Integrated mechanical systems |
— |
CSA P.10 | OTPF = 0.78 |
Pool Heaters |
Component |
Input(1) | Standard |
Performance Requirement(2) |
Gas-fired(3) | < 117.2 kW |
ANSI Z21.56/CSA 4.7 or CSA P.6 | Et ≥ 82%
|
Oil-fired |
— |
CSA B140.12 | Et ≥ 75%
|
3) Except for components that are required to be installed outdoors, service water heating
equipment shall be installed in a
conditioned space. (See
Appendix A.)
9.36.4.3. Solar Domestic Hot Water Systems
1) Service water heating systems that use solar thermal technology shall conform to the
manufacturer’s design requirements and installation procedures.
2) Service water heating systems that use solar thermal technology shall be installed
in accordance with

Book II (Plumbing Systems) of this Code.

9.36.4.4. Piping
1) The first 2 m of outlet piping downstream and of inlet piping upstream leading from a storage tank
or heating vessel shall be covered with piping insulation that is at least 12 mm thick.
2) All piping forming part of a continuously operating recirculating service water heating
system shall be covered with piping insulation that is at least 12 mm thick.
3) Where piping forming part of the service water heating system is located outside the
building envelope or in an unconditioned space, it shall be insulated to a thermal resistance not less than the effective thermal resistance required for the exterior above-ground
walls.
9.36.4.5. Controls
1) Service water heating systems with storage tanks shall be equipped with automatic
temperature controls capable of adjustment between the minimum and maximum temperature
settings permitted for the intended use.
9.36.4.6. Indoor Swimming Pool Equipment Controls
1) Heaters for indoor swimming pools shall be equipped with
a) a thermostat, and
b) a readily accessible and clearly labeled device that allows the heater to be shut
off without adjusting the thermostat setting.
2) Pumps and heaters for indoor swimming pools shall be equipped with time switches or
other types of controls that can be set to automatically turn off the pumps and heaters
when their operation is not required. (See
Appendix A.)
9.36.5. Energy Performance Compliance
9.36.5.1. Scope and Application
2) Internal loads other than those described in
Sentence 9.36.5.4.(4) shall be excluded from the performance compliance calculations as they relate to
a) the lighting of unconditioned spaces,
b) exterior lighting, and
c) the ventilation of unconditioned spaces.
9.36.5.2. Definitions
(See Appendix A.)1) For the purpose of this Subsection, the term “reference house” shall mean a hypothetical replica of the proposed house design using the same energy sources for the same functions
and having the same environmental requirements,
occupancy, climatic data and operating schedules, but made to comply with all applicable prescriptive requirements of
Subsections 9.36.2. to 9.36.4. 2) For the purpose of this Subsection, the term “annual energy consumption” shall mean
the annual sum of service water heating and space-conditioning energy consumption
of the proposed house design, as calculated in accordance with this Subsection.
3) For the purpose of this Subsection, the term “house energy target” shall mean the
annual energy consumption of the reference house, as calculated in accordance with
this Subsection.
4) For the purpose of this Subsection, the term “principal ventilation rate” shall mean
the normal operating exhaust capacity of the principal ventilation fan as required
by
Article 9.32.3.3. 9.36.5.3. Compliance
1) The performance compliance calculations shall determine
a) the annual energy consumption of the proposed house, and
b) the house energy target of a reference house.
2) The annual energy consumption of the proposed house shall not exceed the house energy
target of the reference house. (See
Appendix A.)
3) In establishing the house energy target,
building components, systems and assemblies shall be accounted for in accordance with the prescriptive requirements of
Subsections 9.36.2. to 9.36.4. for the climate zone under consideration.
4) In establishing the annual energy consumption,
building components, systems and assemblies that are addressed in the scope of the prescriptive requirements of
Subsections 9.36.2. to 9.36.4. shall be accounted for for the climate zone under consideration.
5) Where the construction techniques or
building components, systems or assemblies used are more energy-efficient than those prescribed by the prescriptive requirements, the performance compliance calculations are permitted
to take this increased performance level into account in the determination of the
annual energy consumption, provided it can be quantified and is not dependent on occupant
interaction.
6) Both the proposed and reference houses shall be modeled using the same climatic data,
soil conditions, operating schedules in
Article 9.36.5.4. and temperature set-points.
9.36.5.4. Calculation Methods
1) Except as provided in
Sentence (2), the energy model calculations shall account for the annual energy consumption of systems and equipment required for
a) space heating,
b) ventilation,
c) service water heating, and
d) where installed, space cooling.
(See Appendix A.) 2) Redundant or back-up equipment for the systems and equipment listed in
Sentence (1) is permitted to be excluded from the energy model, provided it is equipped with controls and is not required to meet the space-conditioning load of the house. (See
Appendix A.)
3) The schedules used in the energy model shall
a) be based on a time interval not greater than one hour, where the energy model evaluates
the performance of the house over hourly intervals, or
b) be applied in an hourly-bin model then averaged, where the energy model does not evaluate
the performance of the house over hourly intervals.
4) The energy model calculations shall account for the loads due to heat gains from occupants,
lighting and miscellaneous equipment using the default schedule provided in
Table 9.36.5.4. for every day of the year and such loads shall be
a) multiplied by the following adjustment factors, as applicable:
b) increased for each hour by 3.58 W per square metre of
floor area in common spaces, if applicable.
Table 9.36.5.4. Default Schedule for Internal Heat Gain Loads(1) Forming part of Sentence 9.36.5.4.(4) |
Average Load, in W, Before Noon |
12 a.m. |
1 a.m. |
2 a.m. |
3 a.m. |
4 a.m. |
5 a.m. |
6 a.m. |
7 a.m. |
8 a.m. |
9 a.m. |
10 a.m. |
11 a.m. |
786 |
552 |
549 |
523 |
521 |
547 |
634 |
726 |
847 |
880 |
906 |
986 |
Average Load, in W, After Noon |
12 p.m. |
1 p.m. |
2 p.m. |
3 p.m. |
4 p.m. |
5 p.m. |
6 p.m. |
7 p.m. |
8 p.m. |
9 p.m. |
10 p.m. |
11 p.m. |
992 |
934 |
898 |
911 |
924 |
1 089 |
1 410 |
1 588 |
1 568 |
1 483 |
1 194 |
952 |
5) The energy model calculations shall account for the following space-heating temperature
set-points:
a) 21°C in all living spaces above the
basement,
6) The energy model calculations shall account for a space-cooling temperature set-point
of 25°C in all
conditioned spaces served by the cooling system.
7) The energy model calculations shall account for a thermostatic control that responds
to fluctuations of ±0.5°C from the temperature set-point. (See
Appendix A.)
8) If a computer program is used to carry out the compliance calculations, the calculation
methods employed in the energy model shall
a) be used for both the reference and proposed houses, and
b) be tested in accordance with ANSI/ASHRAE 140, “Evaluation of Building Energy Analysis Computer Programs” with variations in the computer program from the range recommended therein reported
in accordance with Division C.
9) The proposed and reference houses shall both be modeled using the same approach and
assumptions, except where
building components or energy efficiency features are permitted by this Subsection to be different.
10) The energy model calculations shall account for the effect of airtightness in accordance
with
Article 9.36.5.10.
11) The energy model calculations shall account for heat transfer through elements separating
conditioned space from unconditioned space, the exterior or the ground.
9.36.5.5. Climatic Data
1) To calculate the effect of heating and cooling consumption, the energy model calculations
shall be performed using climatic data measured at time intervals no greater than
one hour for one year (8 760 hours) based on the average of at least 10 years of measured
data collected at the weather station nearest to the region in which the proposed
house is located. (See
Appendix A.)
2) For urban regions with several climatic data sets and for locations for which climatic
data are not available, the energy model calculations shall be performed using climatic
data that best represent the climate at the
building site.
3) The energy model calculations shall account for ground reflectance by
a) increasing ground reflectance due to snow cover in a ratio of 30% without snow cover
and 70% with snow cover, or
b) taking into account changes in ground reflectance throughout the heating season.
9.36.5.6. Building Envelope Calculations
1) For each hour of the year, the energy model calculations shall account for heat transfer
through wall assemblies, roof-ceiling assemblies, including attics where applicable,
and exposed floor assemblies due to the thermal characteristics of the particular
assembly and thermal bridging.
2) The following
building envelope assemblies and components shall be addressed in the energy model calculations:
a) above-ground walls and roof-ceiling assemblies,
b) floors and walls in contact with the ground, and
c) doors, windows and skylights.
(See Subsection 9.36.2.) 3) For each wall assembly, fenestration component, roof-ceiling assembly and exposed
floor assembly, the energy model calculations shall account for
a) the area of the interior side of the insulated surface,
b) emissivity, and
c) the effective thermal resistance or overall thermal transmittance, as applicable.
4) The energy model calculations shall account for the effect that each assembly in contact
with the ground has on below-
grade heat transfer due to
c) the configuration of the insulation.
5) The energy model calculations shall account for heat transfer through fenestration
separating
conditioned spaces from the outdoors, including skylights, while accounting for both temperature difference and transmission of solar radiation based on
a) orientation as a function of azimuth and tilt of the surface,
b) area of frame opening and glazed area,
c) overall thermal transmittance, and
d) solar heat gain coefficient.
6) Where the energy model calculations account for the effect of thermal mass, the contents
of the house shall be excluded. (See
Appendix A.)
7) The energy model calculations shall account for the presence of thermally active walls,
floors and ceilings with embedded conditioning systems that form part of the
building envelope.
8) Where skylights are installed in the roof, the gross roof area shall be determined
in accordance with
Sentence 9.36.2.3.(3).
9) Skylights shall be considered to have no shading.
10) The energy model calculations shall account for the effects of exterior permanent
and fixed shading only on solar heat gain from fenestration.
11) The ratio of fenestration area to opaque area of doors shall be the same for the proposed
and reference houses. (See
Appendix A.)
9.36.5.7. HVAC System Calculations
1) The energy model calculations shall account for the energy consumption of each heating,
ventilating and, where installed, cooling system for each hour of the year. (See
Appendix A.)
2) Each heating system and, where installed, cooling system shall be accounted for separately
in the energy model calculations.
3) Conditioned spaces in both the reference and proposed houses shall be modeled as being
a) heated, where only heating systems are provided in the proposed house,
b) cooled, where only cooling systems are provided in the proposed house, or
c) heated and cooled, where complete heating and cooling systems are provided in the proposed house.
4) The performance requirements stated in
Table 9.36.3.10. shall be used in the energy model calculations.
5) Where duct and piping losses are accounted for in the energy model calculations, they
shall be included for both the proposed and reference houses and calculated the same
way for both houses. (See
Appendix A.)
6) The same time periods shall be used in the simulation of the operation of the ventilation
system for both the proposed and reference houses.
7) During the heating season, any solar and internal heat gains that cause an increase
in space temperature beyond 5.5°C above the setpoint shall be
a) excluded from the energy model calculations, or
b) calculated as being vented from the house.
8) The energy model calculations shall account for the part-load performance of equipment,
including electrical consumption.
9) The energy model calculations shall account for the heat-recovery efficiency of heat-recovery
ventilators using a minimum of 2 data test points derived from testing in accordance with
Clause 9.36.3.9.(3)(a) or (b), as applicable.
9.36.5.8. Service Water Heating System Calculations
1) The energy model calculations shall account for the energy consumption of all service
water heating systems.
2) The performance requirements stated in
Table 9.36.4.2. shall be used in the energy model calculations.
3) Where piping or standby losses are accounted for in the energy model calculations,
they shall be included for both the proposed and reference houses, including their
effect on space heating and cooling, and calculated the same way for both houses.
4) The energy model calculations shall use a supply cold water temperature, in °C, that
is
a) equal to –0.002 (HDD) + 20.3, where HDD < 7 999,
b) equal to 4.3, where HDD ≥ 8 000, or
c) determined based on the ground and air temperatures in the climatic data file.
5) The energy model calculations shall use a service water delivery temperature of 55˚C.
(See
Appendix A.)
6) The energy model calculations shall take into account the service water heating use
schedule presented in
Table 9.36.5.8. using a load of
Table 9.36.5.8. Default Schedule of Service Water Heating Use Forming part of Sentence 9.36.5.8.(6) |
Type of Small Residential Building | Distribution of Hourly Draws on Service Water Heating, L/h |
Houses with or without a secondary suite (225 L/day/house) |
12 a.m. |
1 a.m. |
2 a.m. |
3 a.m. |
4 a.m. |
5 a.m. |
6 a.m. |
7 a.m. |
8 a.m. |
9 a.m. |
10 a.m. |
11 a.m. |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
5 |
20 |
30 |
55 |
27.5 |
12 p.m. |
1 p.m. |
2 p.m. |
3 p.m. |
4 p.m. |
5 p.m. |
6 p.m. |
7 p.m. |
8 p.m. |
9 p.m. |
10 p.m. |
11 p.m. |
7.5 |
2.5 |
5 |
12.5 |
22.5 |
15 |
15 |
5 |
2.5 |
0 |
0 |
0 |
Dwelling units in other types of residential buildings (140 L/day/dwelling unit) |
12 a.m. |
1 a.m. |
2 a.m. |
3 a.m. |
4 a.m. |
5 a.m. |
6 a.m. |
7 a.m. |
8 a.m. |
9 a.m. |
10 a.m. |
11 a.m. |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
3.1 |
12.4 |
18.7 |
34.2 |
17.1 |
12 p.m. |
1 p.m. |
2 p.m. |
3 p.m. |
4 p.m. |
5 p.m. |
6 p.m. |
7 p.m. |
8 p.m. |
9 p.m. |
10 p.m. |
11 p.m. |
4.7 |
1.6 |
3.1 |
7.8 |
14 |
9.3 |
9.3 |
3.1 |
1.6 |
0 |
0 |
0 |
9.36.5.9. General Requirements for Modeling the Proposed House
1) Except where permitted by
Articles 9.36.5.10. to 9.36.5.12., the energy model calculations for the proposed house shall be consistent with the proposed construction specifications for that house with regard to
a) fenestration and opaque
building envelope assembly type, effective thermal resistance and areas,
b) HVAC system types and capacities, and
c) service water heating system types and capacities.
(See Appendix A.) 9.36.5.10. Modeling Building Envelope of Proposed House
1) Except as provided in
Sentences (2) and (3), the energy model calculations for the proposed house shall be consistent with the proposed construction specifications for that house with regard to
a) the area of the above-ground portion of
foundation walls,
b) the effective thermal resistance of above-ground walls, ceilings below attics, roof
assemblies and
rim joists,
c) the maximum overall thermal transmittance of doors, as calculated in accordance with
Sentence 9.36.2.2.(3),
d) the effective thermal resistance of below-ground walls and slabs-on-ground,
e) exterior walls, roof-ceiling assembly, doors, walls, exposed floors, and floors in
contact with the ground,
f) distribution, orientation and area of fenestration and doors, as calculated in accordance
with
Article 9.36.2.3.,
g) solar heat gain coefficient and overall thermal transmittance of fenestration, as
calculated in accordance with
Sentence 9.36.2.2.(3),
h) configuration of insulation in assemblies in contact with the ground, and
i) effective thermal resistance of
foundation walls.
2) Except for penetrations, slab-on-ground edge insulation and assemblies with embedded
heating pipes, where a
building envelope component or assembly covers less than 2% of the total area of the assembly type to which it belongs, its thermal characteristics are not required to be calculated
as belonging to a distinct assembly, provided the area of the component or assembly
is included in an adjacent assembly having the same orientation (See
Appendix A.)
3) Building envelope assemblies with the same thermal characteristics and orientation are not required to be calculated as distinct assemblies, provided their area is included
in an adjacent assembly.
4) Building envelope assemblies and components separating
conditioned space from enclosed unconditioned space shall have a solar heat gain coefficient equal to 0.
5) Except as stated in
Sentence 9.36.5.6.(9), the energy model calculations for the proposed house shall account for the effects of exterior permanent and fixed shading devices, including fins, overhangs, and light
shelves, on solar heat gain.
6) Where thermal mass is included in the energy model calculations for the proposed house,
it shall be set as
a) the specified mass up to the inside edge of insulation in exterior walls, the mass
of interior walls, the mass up to the centre-line of
party walls, and the mass of floors, as applicable,
b) the specified mass of the
building envelope assembly, where the energy model calculations include a transient analysis of thermal transfer of the entire
building envelope assembly, or
c) a default value of 0.060 MJ/m2∙°C.
7) Exterior walls, roofs and exposed floors shall have an solar absorptance of 0.4.
8) The orientation of the
foundation of the proposed house as constructed shall be within 22.5° of the orientation used in the energy model calculations.
9) The airtightness value used in the energy model calculations for the proposed house
shall be
a)

4.5 air changes

per hour at 50 Pa pressure differential, where the construction complies with
Section 9.25.,
c)

tested in accordance with
Sentence (11), and shall be

,
i) the number of air changes per hour at 50 Pa pressure differential, and
12) 
[Reserved.]

13) Where airtightness is determined in accordance with
Clause (11)(b), its rate shall be adjusted in the energy model calculations to account for air leakage
through mechanical equipment.
9.36.5.11. Modeling HVAC System of Proposed House
1) Where multiple HVAC systems serve a single space, the energy model calculations for
the proposed house shall call each system in the order of priority established by
the system control in the proposed house.
2) Where a heat pump is included in the proposed house, the energy model calculations
shall include
a) the effect of the source temperature on the heat pump’s efficiency, and
b) the temperature at which the heat pump shuts down.
3) Permanent supplementary heating systems that are operated by a thermostat or automatic
control shall be included in the energy model calculations for the proposed house.
4) The performance characteristics of the heat-recovery ventilation system of the proposed
house shall be as specified at not less than the principal ventilation rate required
for a system designed in accordance with
Section 9.32. 5) The ventilation system shall be modeled as operating 8 hours a day at the principal
ventilation rate.
6) 
[Reserved.]

7) The energy model calculations may include duct and piping losses, taking into account the properties of the specified duct and piping insulation of the proposed house.
8) The energy model calculations shall include a heating system and, where installed,
a cooling system sized according to the specifications for the proposed house.
9) The energy model calculations shall include the effect of part-load performance of
equipment using
c) measured data for the specified equipment.
(See Appendix A.) 10) Where a heat-recovery ventilator is installed in the proposed house, the energy model calculations shall only account for the recovery of sensible heat using the efficiency
ratings in
Sentence 9.36.3.9.(3). (See
Appendix A.)
11) Except as provided in
Sentence (12), where a forced-air system is installed in the proposed house, the energy model calculations shall assume the circulation fan operates when the heating, cooling or principal ventilation
system is operating. (See
Appendix A.)
12) Where a forced-air system is installed in the proposed house and where the principal
ventilation system in the proposed house is a separate, fully ducted ventilation system,
the energy model calculations shall assume the circulation fan operates only when
the heating or cooling system is operating.
13) Where the proposed house contains multiple HVAC systems, the circulation fan power
shall be the sum of the circulation fan power capacity of each system.
14) The ventilation fan power consumption shall be modeled
a) as being 2.32 W/L/s for each ventilation fan on the exhaust side and, where applicable, on the supply
side, or
b) as specified, where a heat-recovery ventilator is used.
15) Where a forced-air system is installed in the proposed house, the energy model calculations
shall determine the flow rate, in L/s, of the circulation fan in the reference house
by multiplying the capacity, in W, of the heating system in the proposed house by
a) 0.0604 for heat pumps, and
b)

0.0251

for all other types of heating systems.
16) Where a forced-air system is installed in the proposed house, the energy model calculations
shall determine the minimum electricity requirement, in W, of the circulation fan
by multiplying the flow rate, in L/s, of the circulation fan in the reference house,
determined in accordance with
Sentence (15), by a factor of 2.30.
17) Where a forced-air system is installed in the proposed house, the flow rate of the
circulation fan shall be modeled as being the larger of
a) the flow rate of the circulation fan of the reference house, determined in accordance
with
Sentence (15), or
b) the flow rate of the circulation fan for the forced-air system specified in the design
for the proposed house.
18) Except as provided in
Sentence (19), where a forced-air system is installed in the proposed house, the power capacity of the circulation fan shall be modeled as specified in the design for the proposed
house.
19) Where the design for the proposed house specifies a forced-air system with a circulation
fan flow rate that is lower than that of the flow rate of the circulation fan in the
reference house, as determined in accordance with
Sentence (15), the electricity capacity, in W, of the circulation fan shall be modeled as being the larger of
a) the electricity capacity specified for the circulation fan in the proposed forced-air
system, or
b) the minimum circulation fan electricity capacity determined in accordance with
Sentence (16).
20) For natural gas-, oil-, propane- and wood-burning heating systems, the energy model
calculations shall set the auxiliary electricity requirements, including that of combustion
fans, to those specified for the proposed house.
9.36.5.12. Modeling Service Water Heating System of Proposed House
1) The service water heating system used in the energy model calculations shall be sized
as specified in the design for the proposed house.
2) The energy model calculations may include
a) piping losses, and
b) drain-water heat recovery, provided the calculation of the heat recovered is based
on the efficiency of the drain-water heat-recovery unit specified for the proposed
house and the energy savings are determined using a drain-water
i) inlet temperature to the recovery system of 36°C,
ii) flow rate of 9.5 L/min, and
iii) flow that is available for recovery 15 min/day for a house and 10 min/day per suite for a multi-unit residential building with more than 2 suites. (See Appendix A.) 9.36.5.13. General Requirements for Modeling the Reference House
2) The energy model calculations for the reference house shall include the same values as those used for the proposed house with regard to
b) heated volume, and
c) number and types of rooms.
9.36.5.14. Modeling Building Envelope of Reference House
1) The energy model calculations for the reference house shall include the same values
as those used for the proposed house with regard to
a) the gross area of above-ground portion of
foundation walls,
d) the ratio of fenestration area to opaque area of doors.
2) The energy model calculations for the reference house shall use the following set
values:
a) 0.060 MJ/m2·°C for thermal mass,
b) a solar absorptance of 0.4 for the exterior walls, roofs and exposed floors,
c) 0.26 for the solar heat gain coefficient of fenestration, and
d) 2.5 air changes per hour at 50 Pa pressure differential for airtightness.
3) The effective thermal resistance and overall thermal transmittance values, as applicable,
used in the energy model calculations for the reference house shall be determined
for the applicable heating degree-day zone in accordance with
4) Except as provided in
Sentences (5) and (6), the exterior walls, roof-ceiling assembly, doors, walls, exposed floors, and floors of the reference house that are in contact with the ground shall have the same area
as those of the proposed house.
5) The area and orientation of fenestration and doors of the reference house shall be
modeled as being equally distributed on all sides of the house.
6) The gross wall area and the area of fenestration and doors of the reference house
shall be determined in accordance with
Article 9.36.2.3. 7) Windows and other glazed components in the reference house shall have a maximum overall thermal transmittance as required in
Table 9.36.2.7.A. for the applicable heating degree-day category.
8) The configuration of insulation in assemblies of the reference house that are in contact
with the ground shall be modeled as conforming to
Article 9.36.2.8. 10) The fenestration and door area to gross wall area ratio (FDWR) of the reference house
shall be
a) for houses containing 1 or 2
dwelling units,
i) as per the proposed house, where its FDWR is between 17% and 22%,
ii) 17%, where the FDWR of the proposed house is less than 17%, or
iii) 22%, where the FDWR of the proposed house is greater than 22%, and
(See Appendix A.) 9.36.5.15. Modeling HVAC System of Reference House
1) Where multiple HVAC systems serve a single space, the energy model calculations for the reference house shall use the same order of priority as that used for the proposed
house. (See
Sentence 9.36.5.11.(1).)
2) The energy model calculations for the reference house shall include the same features
as those used for the proposed house with regard to
a) the principal heating and cooling energy sources, which are gas, electricity, oil,
propane, wood or a heat pump,
b) the primary and secondary energy sources, which are gas, electricity, oil, propane,
wood or a heat pump, and
3) Except as required in
Sentence 9.36.3.8.(1), the reference house shall be modeled without a heat-recovery ventilator.
4) The ventilation system shall be modeled as operating 8 hours a day.
5) The heating system and, where installed, the cooling system shall be sized in accordance
with
Article 9.33.5.1. with regard to total heat output capacity and nominal cooling capacity. (See
Appendix A.)
6) The part-load performance of HVAC equipment in the reference house shall be calculated
using
a) modeled part-load performance characteristics, where applicable, or
b) the performance values for each type of system multiplied by an adjustment factor
from
Table 9.36.5.15.A, 9.36.5.15.B or 9.36.5.15.C as follows:
ii) for heat pumps and air conditioners, by multiplying the heat pump steady-state coefficient of performance by the adjustment factor given in Table 9.36.5.15.B, and iii) for boilers, combination space-heating and service water heating systems, and integrated mechanical systems, by multiplying the net-full-load heating efficiency by the adjustment factor
given in Table 9.36.5.15.C (See Appendix A.)
Table 9.36.5.15.A Part-Load Adjustment Factors for Furnaces Forming part of Subclause (6)(b)(i) |
Fuel Source |
Type of Equipment |
Capacity |
Part-Load Ratio |
0.15 |
0.4 |
1.0 |
Adjustment Factors |
Gas |
Warm-air furnaces | ≤ 65.9 kW |
1.03 |
1.02 |
1.0 |
> 65.9 kW |
0.91 |
0.97 |
1.0 |
Duct furnaces and unit heaters | All capacities |
0.91 |
0.97 |
1.0 |
Oil |
All types |
All capacities |
0.95 |
0.98 |
1.0 |
Table 9.36.5.15.B Part-Load Adjustment Factors for Heat Pumps and Air Conditioners Forming part of Subclause (b)(ii) |
Type of Equipment |
Part-Load Ratio |
0.15 |
0.4 |
1.0 |
Adjustment Factors |
Air-source heat pumps and air conditioners |
0.72 |
0.86 |
1.0 |
Water-source heat pumps |
0.93 |
0.98 |
1.0 |
Ground-source heat pumps |
0.93 |
0.98 |
1.0 |
Table 9.36.5.15.C Part-Load Adjustment Factors for Boilers, Combination Systems and Integrated Mechanical
Systems Forming part of Subclause (b)(iii) |
Fuel Source |
Type of Equipment |
Part-Load Ratio |
0.15 |
0.4 |
1.0 |
Adjustment Factors |
Gas |
Boiler | 1.03 |
1.02 |
1.0 |
Integrated mechanical systems(1) within the scope of CSA P.10(2) | N/A |
N/A |
N/A |
Combination space- and service water heating systems within the scope of CAN/CSA-P.9(2) | N/A |
N/A |
N/A |
Combination space- and service water heating systems not within the scope of CAN/CSA-P.9 | Same as gas boiler |
Oil |
Boiler | 1.03 |
1.02 |
1.0 |
Combination space- and service water heating systems within the scope of CAN/CSA-P.9(2) | N/A |
N/A |
N/A |
Combination space- and service water heating systems not within the scope of CAN/CSA-P.9 | Same as oil boiler |
7) The performance of the HVAC equipment in the reference house shall be modeled
a) as conforming to
Table 9.36.3.10. for the corresponding type, fuel source and capacity of equipment in the proposed house, or
b) where the HVAC equipment for the proposed house is not addressed in
Table 9.36.3.10., as a gas warm-air
furnace with a minimum performance rating of 92% annual fuel utilization efficiency.
8) Where a heat-recovery ventilator is installed in the reference house, the energy model
calculations shall only account for the recovery of sensible heat using the efficiency
ratings in
Sentence 9.36.3.9.(3). (See
Appendix A.)
9) The energy model calculations shall assume all ventilation and circulation fans required
to be modeled in the reference house are equipped with permanent-split capacitor (PSC)
motors.
10) Where a forced-air system is installed in the reference house, the energy model calculations
shall assume the circulation fan operates when the heating, cooling or principal ventilation
system is called for.
11) Where the reference house contains multiple HVAC systems, the circulation fan power
shall be the sum of the circulation fan power capacity of each system.
12) The principal ventilation flow rate, in L/s, prescribed in
Section 9.32. shall be multiplied by 2.32 W/L/s to determine the ventilation fan power capacity, in W, to be used in the energy model
calculations for each fan on the exhaust side and, where applicable, on the supply
side.
13) Where a heat-recovery ventilator is required in the reference house in accordance
with
Article 9.36.3.8., the ventilation flow rate, in L/s, in the zone served by the pool or hot tub shall be multiplied by 4.18 W/L/s to determine the heat-recovery ventilator power, in W, to be used in the energy model
calculations.
14) Where a forced-air system is installed in the reference house, the systems capacity,
in W, shall be multiplied by one of the following factors to determine the circulation
fan flow rate, in L/s:
a) 0.0604 for heat pumps, and
b)

0.0251

for all other types of heating systems.
15) Where a forced-air system is installed in the reference house, the circulation fan
flow rate, in L/s, shall be multiplied by 2.30 W/L/s to determine the circulation fan power capacity, in W.
16) For natural gas-, oil-, propane- and wood-burning heating systems, the energy model
calculations shall set the auxiliary electricity capacity, including that of combustion
fans, to 208 W during operation.
9.36.5.16. Modeling Service Water Heating System of Reference House
1) The energy source of the reference house’s service water heating system, which is
gas, electricity, oil, propane, wood or a heat pump, shall be the same as that for
the system in the proposed house.
2) The service water heating system in the reference house shall be sized in accordance
with
Subsection 9.31.6. with regard to output capacity.
3) Except as required by
Table 9.36.5.16., the performance of the service water heating equipment in the reference house shall be modeled as conforming to
Table 9.36.4.2. for the energy source, capacity and type of service water heating equipment in the proposed house.
Table 9.36.5.16. Performance of Service Water Heating (SWH) Equipment in the Reference House Forming part of Sentence 9.36.5.16.(3) |
Type of SWH Equipment in Proposed House |
Input for Proposed SWH Equipment |
Type of SWH Equipment to be Used for Reference House |
Input for Reference SWH Equipment |
Gas-fired tankless service water heater | ≤ 73.2 kW |
Gas-fired storage type |
≤ 22 kW |
> 73.2 kW |
> 22 kW |
Oil-fired tankless service water heater | ≤ 61.5 kW(1) | Oil-fired storage type |
≤ 30.5 kW(1) |
Other |
> 30.5 kW |
Not listed in Table 9.36.4.2. | — |
Gas-fired storage type |
≥ 22 kW (Et ≥ 80%)
|
9.36.6.
Energy Step Code
9.36.6.1. Application
9.36.6.2. Definitions
(See Appendix A.)1) For the purpose of this Subsection, the term “mechanical energy use intensity” shall
mean a metric of the energy used over a year

by the
building
, estimated by using an energy model in accordance with
Article 9.36.6.4., normalized per square metre of

floor area of
conditioned space
and expressed in kWh/(m
2⋅year), for all of the following combined:
a) space-heating equipment,
b) space-cooling equipment,
c) fans,
d) service water heating equipment,
e) pumps, and
2) For the purpose of this Subsection, the term “EnerGuide Rating % lower than EnerGuide
Reference House” shall mean the metric that results when, using HOT2000 software,
version 11 or newer and Natural Resources Canada’s EnerGuide Rating System, version
15 or newer, the energy consumption of the following are compared:
a) the proposed
building, not including the EnerGuide assumed electric base loads, and
b) the corresponding automatically-generated reference house, not including the EnerGuide
assumed electric base loads.
3) For the purpose of this Subsection, the term “thermal energy demand intensity” shall
mean a metric of the annual heating required by the
building for space conditioning and for conditioning of ventilation air, estimated by using an energy model in accordance with
Article 9.36.6.4., normalized per square metre of

floor area of
conditioned space
and expressed in kWh/(m
2⋅year), taking into account all of the following:
a) thermal transmittance of above-ground walls and roof-ceiling assemblies,
b) thermal transmittance of floors and walls in contact with the ground, or with space that is not
conditioned space,
c) thermal transmittance and solar heat gain of windows, doors and skylights,
e) internal heat gains from occupants and equipment, and
f) heat recovery from exhaust ventilation.
4) For the purpose of this Subsection, the term “peak thermal load” shall mean a metric
of the maximum heating energy required by the
building for space conditioning and for conditioning of ventilation air, estimated by using an energy model in accordance with
Article 9.36.6.4., at a 2.5% January design temperature

, normalized per square metre of floor area of
conditioned space and expressed in W/m
2
, taking into account all of the items referred to in
Clauses (3)(a) through (f).
5) For the purpose of this Subsection, the term “Step” shall mean a Step referred to
in
Tables 9.36.6.3.A to C.
9.36.6.3. Compliance Requirements
1) Buildings conforming to the requirements of any of Steps 1 to 5 shall be designed and constructed to conform to the applicable energy performance requirements in
Tables 9.36.6.3.A to .C
Table 9.36.6.3.A Requirements for Buildings Located Where the Degree-Days Below 18°C Value is less
than 3000(1) Forming part of Sentence 9.36.6.3.(1) |
Step |
Airtightness (Air Changes per Hour at 50 Pa Pressure Differential)
|
Performance Requirement of Building Equipment and Systems |
Performance Requirement of Building Envelope |
1
|
N/A
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 0% lower energy consumption or conform to Subsection 9.36.5.
|
2
|
≤ 3.0
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 10% lower energy consumption or mechanical energy use intensity ≤ 60 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 45 kWh/(m2⋅year) or peak thermal load ≤ 35 W/m2
|
3
|
≤ 2.5
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 20% lower energy consumption or mechanical energy use intensity ≤ 45 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 40 kWh/(m2⋅year) or peak thermal load ≤ 30 W/m2
|
4
|
≤ 1.5
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 40% lower energy consumption or mechanical energy use intensity ≤ 35 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 25 kWh/(m2⋅year) or peak thermal load ≤ 25 W/m2
|
5
|
≤ 1.0
|
mechanical energy use intensity ≤ 25 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 15 kWh/(m2⋅year) or peak thermal load ≤ 10 W/m2
|
Table 9.36.6.3.B Requirements for Buildings Located Where the Degree-Days Below 18°C Value is 3000
to 3999(1) Forming part of Sentence 9.36.6.3.(1) |
Step |
Airtightness (Air Changes per Hour at 50 Pa Pressure Differential)
|
Performance Requirement of Building Equipment and Systems |
Performance Requirement of Building Envelope |
1
|
N/A
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 0% lower energy consumption or conform to Subsection 9.36.5.
|
2
|
≤ 3.0
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 10% lower energy consumption or mechanical energy use intensity ≤ 90 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 60 kWh/(m2⋅year) or peak thermal load ≤ 55 W/m2
|
3
|
≤ 2.5
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 20% lower energy consumption or mechanical energy use intensity ≤ 75 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 50 kWh/(m2⋅year) or peak thermal load ≤ 45 W/m2
|
4
|
≤ 1.5
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 40% lower energy consumption or mechanical energy use intensity ≤ 45 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 40 kWh/(m2⋅year) or peak thermal load ≤ 40 W/m2
|
5
|
≤ 1.0
|
mechanical energy use intensity ≤ 25 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 15 kWh/(m2⋅year) or peak thermal load ≤ 10 W/m2
|
Table 9.36.6.3.C Requirements for Buildings Located Where the Degree-Days Below 18°C Value is greater
than 3999(1) Forming part of Sentence 9.36.6.3.(1) |
Step |
Airtightness (Air Changes per Hour at 50 Pa Pressure Differential)
|
Performance Requirement of Building Equipment and Systems |
Performance Requirement of Building Envelope |
1
|
N/A
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 0% lower energy consumption or conform to Subsection 9.36.5.
|
2
|
≤ 3.0
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 10% lower energy consumption or mechanical energy use intensity ≤ 100 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 70 kWh/(m2⋅year) or peak thermal load ≤ 55 W/m2
|
3
|
≤ 2.5
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 20% lower energy consumption or mechanical energy use intensity ≤ 85 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 60 kWh/(m2⋅year) or peak thermal load ≤ 50 W/m2
|
4
|
≤ 1.5
|
EnerGuide Rating % lower than EnerGuide Reference House: not less than 40% lower energy consumption or mechanical energy use intensity ≤ 55 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 50 kWh/(m2⋅year) or peak thermal load ≤ 45 W/m2
|
5
|
≤ 1.0
|
mechanical energy use intensity ≤ 25 kWh/(m2⋅year)
|
thermal energy demand intensity ≤ 15 kWh/(m2⋅year) or peak thermal load ≤ 10 W/m2
|
3) Buildings designed and constructed to conform to Step 5 of any of
Tables 9.36.6.3.A to C and to the Passive House Planning Package, version 9 or newer, are deemed to comply
with this Subsection

provided the energy model

according to which the
building is designed and constructed is prepared by a Certified Passive House Designer, or Certified Passive House Consultant, who is approved by the Passive House Institute.
9.36.6.4. Energy Modelling
2) Energy modelling shall conform to
b) the EnerGuide Rating System, version 15 or newer, or (See
Appendix A.)
3) The Performance Requirement of Building Equipment and Systems and the Performance
Requirement of Building Envelope required under
Sentence 9.36.6.3.(1) shall both be modelled using the same
a) energy modelling methods, and
b) climatic data,
soil conditions, operating schedules and temperature set-points.
4) For
buildings conforming to the requirements of any of Steps 2 to 5, energy modelling shall account for the air leakage rate derived in accordance with
Article 9.36.6.5. (See Appendix A.)9.36.6.5. Building Envelope Airtightness Testing
1) Buildings shall be tested for airtightness in accordance with
2) Where airtightness is determined in accordance with
Sentence (1) with intentional openings for mechanical equipment left unsealed, the airtightness
rate shall be adjusted in the energy model calculations to account for air leakage
through mechanical equipment.
3) Buildings shall be tested for airtightness to an induced test pressure of not less than 50 Pa.
