Division B
Acceptable Solutions

Part 9 — Housing and Small Buildings

Section 9.9. Means of Egress

9.9.1. General

9.9.1.1. Application
1) Intent StatementStairways, handrails and guards in a means of egress shall conform to the requirements in Section 9.8. as well as to the requirements in this Section.
9.9.1.2. Fire Protection
1) Intent StatementIn addition to the fire protection requirements provided in Subsection 9.9.4., flame-spread ratings, fire-resistance ratings and fire-protection ratings for means of egress shall conform to Section 9.10.
9.9.1.3. Occupant Load
1) Intent StatementExcept for dwelling units, the occupant load of a floor area or part of a floor area shall be the number of persons for which such areas are designed, but not fewer than that determined from Table 3.1.17.1., unless it can be shown that the area will be occupied by fewer persons.
2) Intent StatementThe occupant load for dwelling units shall be based on 2 persons per bedroom or sleeping area.

9.9.2. Types and Purpose of Exits

9.9.2.1. Types of Exits
1) Intent StatementExcept as otherwise provided in this Section, an exit from any floor area shall be one of the following used singly or in combination:
a) an exterior doorway,
b) an exterior passageway,
c) an exterior ramp,
d) an exterior stairway,
e) a fire escape,
g) an interior passageway,
h) an interior ramp, or
i) an interior stairway.
2) Intent StatementFire escapes shall only be used as exits on existing buildings and shall be designed and installed in conformance with Subsection 3.4.7.
3) Intent StatementWhere a horizontal exit is used, it shall conform to Sentence 3.4.1.6.(1) and Article 3.4.6.10.
9.9.2.2. Purpose of Exits
1) Intent StatementAn exit shall be designed for no purpose other than for exiting except that an exit may also serve as an access to a floor area.
9.9.2.3. Elevators, Slide Escapes and Windows as Means of Egress
1) Intent StatementElevators, slide escapes and windows shall not be considered as part of a required means of egress.
9.9.2.4. Principal Entrances
1) Except for doors serving a single dwelling unit, at least one door at every principal entrance to a building providing access from the exterior at ground level shall be designed in accordance with the requirements for exits.

contentHistory

9.9.3. Dimensions of Means of Egress

9.9.3.1. Application
1) This Subsection applies to every means of egress except
a) exits that serve not more than one dwelling unit, and

contentHistory

9.9.3.2. Exit Width
1) Intent StatementExcept for doors and corridors, the width of every exit facility shall be not less than 900 mm. (See Article 9.9.6.3. for doors, Article 9.8.2.1. for stairs, change beginand Article 9.8.5.2. for ramps.change end)
9.9.3.3. Width of Corridors
1) Intent StatementThe width of every public corridor, corridor used by the public, and exit corridor shall be not less than 1 100 mm. (See also Subsection 9.9.5. for obstructions in corridors.)
9.9.3.4. Clear Height
1) Intent StatementExcept for stairways, doorways and storage garages, the minimum clear height in exits and access to exits shall be 2.1 m. (See Article 9.8.2.2. for stairs, Article 9.8.5.3. for ramps, Article 9.8.6.4. for landings and Article 9.9.6.2. for doorways.)
2) Intent StatementThe clear height in exits and access to exits in storage garages shall be not less than 2 m.

9.9.4. Fire Protection of Exits

9.9.4.1. Application
1) Intent StatementExcept as provided in Articles 9.9.4.4. change beginand 9.9.4.6.change end, this Subsection applies to the fire protection of all exits except exits serving not more than one dwelling unit.
9.9.4.2. Fire Separations for Exits
1) Intent StatementExcept as provided in Sentences (2) and (5) and Article 9.9.8.5., every exit other than an exterior doorway shall be separated from each adjacent floor area or from another exit
a) change beginwhere there is a floor assembly above the floor area,change end by a fire separation having a fire-resistance rating not less than that required for the floor assembly above the floor area (see Article 9.10.9.10.), and
b) change beginwhere there is no floor assembly above the floor area, by a fire separation having a fire-resistance rating not less than the greater ofchange end
i) that required by Subsection 9.10.8. for the floor assembly below, or
ii) change begin45 min.change end
2) change beginReserved.change end

contentHistory

3) Intent StatementA fire separation common to 2 exits shall be smoke-tight and not be pierced by doorways, duct work, piping or any other opening that may affect the continuity of the separation.
4) Intent StatementA fire separation that separates an exit from the remainder of the building shall have no openings except those for electrical wiring, noncombustible conduit and noncombustible piping that serve only the exit, and for standpipes, sprinkler piping, exit doorways and wired glass and glass block permitted in Article 9.9.4.3.
5) The requirements in Sentence (1) do not apply to an exterior exit passageway provided the passageway has not less than 50% of its exterior sides open to the outdoors and is served by an exit stair at each end of the passageway.

contentHistory

9.9.4.3. Wired Glass or Glass Block
(See A-3.1.8.17.(1) in Appendix A.)
1) Intent StatementThis Article applies to wired glass in doors, and wired glass or glass block in sidelights, where these are installed in fire separations between exit enclosures and floor areas.
2) Intent StatementExcept as provided in Sentence (3), the combined area of glazing in doors and sidelights shall not exceed 0.8 m2.
3) Intent StatementWhere an exit enclosure connects with a floor area through an enclosed vestibule or corridor separated from the floor area by fire separations having not less than a 45 min fire-resistance rating, the glazed areas described in Sentence (1) need not be limited as required in Sentence (2).
9.9.4.4. Openings Near Unenclosed change beginExteriorchange end Exit Stairs and Ramps
1) change beginUnprotected openings in exterior walls of the building shall be protected with wired glass in fixed steel frames or glass block conforming to Articles 9.10.13.5. and 9.10.13.7.,change end where
a) an unenclosed exterior exit stair or ramp provides the only means of egress from a suite and is exposed to fire from unprotected openings in the exterior walls of
i) another fire compartment, or
ii) change beginanother dwelling unit, andchange end
b) change beginunprotected openingschange end in the exterior walls of the building are within 3 m horizontally and less than 10 m below or less than 5 m above the exit stair or ramp.

contentHistory

9.9.4.5. Openings in Exterior Walls of Exits
1) Intent Statement Either openings in exterior walls of an exit or openings in adjacent exterior walls of the building the exit serves shall be protected with wired glass in fixed steel frames or glass block installed in accordance with Articles 9.10.13.5. and 9.10.13.7., where
a) the exit enclosure has exterior walls that intersect the exterior walls of the building at an angle of less than 135° measured on the outside of the building, and
b) the openings in the exterior walls of the building are within 3 m horizontally and less than 2 m above the openings in the exterior walls of the exit.
(See Appendix A.)
9.9.4.6. Openings Near Exit Doors
1) change beginWhere an exterior exit door in one fire compartment is within 3 m horizontally of an unprotected opening in another fire compartment and the exterior walls of these fire compartments intersect at an exterior angle of less than 135°, the opening shall be protected with
a) wired glass in fixed steel frames conforming to Article 9.10.13.5., or
b) glass block conforming to Article 9.10.13.7.change end

contentHistory

9.9.4.7. Stairways in 2 Storey, Group D or E Buildings
1) Intent StatementWhere a suite of Group D or E occupancy is located partly on the first storey and partly on the second storey, stairways serving the second storey of that suite need not be constructed as exit stairs provided,
a) the building is not greater than 2 storeys in building height,
b) the suite is separated from other occupancies by at least a 45 min fire separation,
c) the area occupied by the suite is not greater than 100 m2 per storey,
d) the maximum travel distance from any point in the suite to an exterior exit is not greater than 25 m,
e) the floor assemblies have a fire-resistance rating of not less than 45 min or are of noncombustible construction, and
f) the basement and first storey are separated by a fire separation having a fire-resistance rating of not less than 45 min.

9.9.5. Obstructions and Hazards in Means of Egress

9.9.5.1. Application
1) Intent StatementThis Subsection applies to obstructions and hazards in every means of egress except those within a dwelling unit or serving not more than one dwelling unit.
9.9.5.2. Occupancies in Corridors
1) Intent StatementWhere a corridor contains an occupancy, the occupancy shall not reduce the unobstructed width of the corridor to less than the required width of the corridor.
9.9.5.3. Obstructions in Public Corridors
1) Intent StatementExcept as permitted in Sentence (2), obstructions located within 1 980 mm of the floor shall not project horizontally more than 100 mm into exit passageways, corridors used by the public or public corridors in a manner that would create a hazard for visually impaired persons travelling adjacent to walls.
2) Intent StatementThe horizontal projection of an obstruction referred to in Sentence (1) is permitted to exceed 100 mm where the obstruction extends to less than 680 mm above the floor. (See A-3.3.1.9.(4) in Appendix A.)
9.9.5.4. Obstructions in Exits
1) Intent StatementExcept as permitted in Subsection 9.9.6. and Article 9.8.7.6., no fixture, turnstile or construction shall project within the required width of an exit.
9.9.5.5. Obstructions in Means of Egress
1) Intent StatementNo obstructions such as posts or turnstiles shall be placed so as to restrict the width of a required means of egress from a floor area or part of a floor area to less than 750 mm unless an alternate unobstructed means of egress is provided adjacent to and plainly visible from the restricted egress.
2) Intent StatementExcept as provided in Sentence (3), no obstructions, such as counter gates, that do not meet the requirements for exit doors, shall be placed in a required means of egress from a floor area or part of a floor area unless an alternate unobstructed means of egress is provided adjacent to and plainly visible from the restricted egress.
3) Intent StatementObstructions, such as counter gates, that do not satisfy Sentence (2), are permitted to be placed in a required means of egress from a part of a floor area in mercantile occupancies and business and personal services occupancies, provided that the part of the floor area served by the obstructed means of egress is not generally accessible to the public.
9.9.5.6. Mirrors or Draperies
1) Intent StatementNo mirror shall be placed in or adjacent to any exit so as to confuse the direction of exit, and no mirror or draperies shall be placed on or over exit doors.
9.9.5.7. Fuel-Fired Appliances
1) Intent StatementFuel-fired appliances shall not be installed in an exit or corridor serving as an access to exit.
9.9.5.8. Service Rooms
1) Intent StatementService rooms containing equipment subject to possible explosion, such as boilers designed to operate at a pressure in excess of 100 kPa, and certain types of refrigerating and transformer equipment, shall not be located under required exits.
9.9.5.9. Ancillary Rooms
1) Ancillary rooms such as storage rooms, washrooms, toilet rooms, laundry rooms and service rooms shall not open directly into an exit.

contentHistory

9.9.6. Doors in a Means of Egress

9.9.6.1. Obstructions by Doors
1) Intent StatementExcept as provided in Sentence (4), obstructions created by doors shall be limited in accordance with Sentences (2) and (3)
a) at exit doors,
b) at doors that open into or are located within a public corridor, and
c) at doors that open into or are located within another facility that provides access to exit from a suite.
2) Intent StatementWhen fully open, doors described in Sentence (1) shall not decrease the required exit width by more than
a) 100 mm in exit corridors, and
b) 50 mm for other exit facilities.
3) Intent StatementThe swing of doors described in Sentence (1) shall not reduce the width of the path of travel to less than
a) the required exit width in exit corridors and passageways, and
b) 750 mm on exit stairs or landings.
4) Doors serving a single dwelling unit need not comply with Sentences (2) and (3).

contentHistory

9.9.6.2. Clear Opening Height at Doorways
1) Intent StatementExcept as provided in Sentences (2) and (3), the clear opening height of doorways shall be not less than 2 030 mm high at
a) exit doors,
b) doors that open into or are located within a public corridor, and
c) doors that open into or are located within another facility that provides access to exit from a suite.
2) Intent StatementThe clear opening height under door closers and other devices in doorways described in Sentence (1) shall be not less than 1 980 mm.
3) Doorways serving a single dwelling unit need not comply with Sentences (1) and (2). change begin(See also Article 9.5.5.1.)change end

contentHistory

9.9.6.3. Clear Opening Width at Doorways
1) Intent StatementExcept as provided in Sentence (4), the clear opening width of doorways shall comply with Sentence (2) at
a) exit doors, and
b) doors that open into or are located within a public corridor or other facility that provides access to exit from a suite.
2) Intent StatementDoorways described in Sentence (1) shall be
a) not less than 800 mm wide where there is only one door leaf,
b) not less than 800 mm wide where multiple-leaf doors are installed with only one active leaf having a latching mechanism described in Article 9.9.6.7., and
c) not less than 1 210 mm wide where mutiple-leaf doors are installed with two active leaves.
3) Intent StatementIn doorways described in Sentence (1) that have multiple-leaf doors installed,
a) no active leaf shall be less than 810 mm wide where only one leaf is active, and
b) no single leaf shall be less than 610 mm wide where two leaves are active.
4) Doorways serving a single dwelling unit need not comply with Sentence (2). change begin(See also Article 9.5.5.1.)change end

contentHistory

9.9.6.4. Door Action
1) Intent StatementExcept as provided in Sentences (4) and (5), required exit doors and doors in required means of egress, except doors in means of egress within dwelling units, shall swing on the vertical axis.
2) Intent StatementExcept as provided in Sentence (5), breakaway sliding doors, installed as required exit doors or required doors in means of egress, shall be identified as swinging doors by means of a label or decal affixed to the door.
3) Intent StatementRevolving doors shall comply with Article 3.4.6.15.
4) Intent StatementMovable partitions used to separate a public corridor from an adjacent business and personal services occupancy or a mercantile occupancy need not conform to Sentence (1), provided the partitions are not located in the only means of egress. (See A-3.3.1.12.(3) in Appendix A.)
5) Intent StatementExit doors need not conform to Sentences (1) or (2), where
a) the doors serve accessory buildings where life safety is not adversely affected,
b) the doors serve storage garages or other accessory buildings serving not more than one dwelling unit, or
c) the doors
i) serve storage suites of not more than 20 m2 in gross area that are in warehousing buildings of not more than one storey, and
ii) open directly to the exterior at ground level.
9.9.6.5. Direction of Door Swing
1) Except for doors serving a single dwelling unit exit doors that are required to swing shall swing in the direction of exit travel.

contentHistory

2) Intent StatementDoors that open onto a corridor or other facility that provides access to exit from a room or suite having an occupant load of more than 60 persons shall swing on the vertical axis in the direction of exit travel.
3) Intent StatementDoors that divide a corridor that is not wholly contained within a suite shall swing in the direction of exit travel.
4) Intent StatementWhere a pair of doors is installed in a corridor that provides access to exit in both directions, the doors shall
a) swing in opposite directions, with the door on the right-hand side swinging in the direction of exit travel, or
b) swing in both directions.
9.9.6.6. Nearness of Doors to Stairs
1) Except as provided in Sentence (2), the distance between a stair riser and the leading edge of a door during its swing, except for doors serving a single dwelling unit shall be not less than 300 mm.

contentHistory

2) Intent StatementWhere there is a danger of blockage from ice or snow, an exit door, including doors serving a single dwelling unit, may open onto not more than one step, provided the riser of such a step does not exceed 150 mm.
9.9.6.7. Door Latching, Locking and Opening Mechanisms
1) Intent StatementPrincipal entrance doors, exit doors and doors to suites, including exterior doors of dwelling units, and other doors in an access to exit shall
a) be openable from the inside or in travelling to an exit without requiring keys, special devices or specialized knowledge of the door-opening mechanism, or
b) in the case of exit doors, be controlled by electromagnetic locking mechanisms in accordance with Sentence 3.4.6.16.(4).
2) Except for doors serving a single dwelling unit and doors to accessory buildings and to garages serving a single dwelling unit, door release hardware on doors in a means of egress shall be operable with one hand and the door shall be openable with not more than one releasing operation. (See also change beginClause 3.3.1.13.(10)(c)change end and A-3.3.1.13.(4) in Appendix A.)

contentHistory

3) Intent StatementDoor release hardware on doors in a means of egress shall be installed not more than 1 200 mm above the finished floor.
4) Intent StatementExcept for hotels and motels, a door opening onto a public corridor that provides access to exit from suites shall be designed not to lock automatically if it is equipped with an automatic self-closing device. (See A-3.3.4.5.(1) in Appendix A.)
9.9.6.8. Effort Required to Open
1) Every exit door, except doors serving a single dwelling unit shall be designed and installed so that when the latch is released the door will open in the direction of exit travel under a force of not more than 90 N applied to the door release hardware. (See Sentence 3.8.3.3.(7) for door opening forces in an accessible path of travel.)

contentHistory

9.9.7. Access to Exits

9.9.7.1. Egress from Roof Area, Podiums, Terraces, Platforms and Contained Open Spaces
1) Intent StatementAn access to exit shall be provided from every roof intended for occupancy and from every podium, terrace, platform or contained open space.
2) Intent StatementWhere a roof is intended for an occupant load of more than 60 persons, at least 2 separate means of egress shall be provided from the roof to stairs designed in conformance with the requirements for exit stairs and located remote from each other.
3) Intent StatementWhere a podium, terrace, platform or contained open space is provided, egress requirements shall conform to the appropriate requirements for rooms or suites in Article 9.9.7.4.
9.9.7.2. Means of Egress from Suites
1) Intent StatementExcept as required in Sentence 9.9.9.3.(1), each suite in a floor area occupied by more than one suite shall have
a) an exterior exit doorway,
b) a doorway to a public corridor, or
c) a doorway to an exterior passageway.
2) Intent StatementExcept as provided in Sentences 9.9.7.3.(1) and 9.9.8.2.(2), from the point where a doorway described in Clauses (1)(b) or (c) enters the public corridor or exterior passageway, it shall be possible to go in opposite directions to each of 2 separate exits.
9.9.7.3. Dead-End Corridors
1) Intent StatementExcept for a dead-end corridor that is  entirely within a suite and except as permitted in Sentence 9.9.9.2.(1), a dead-end corridor is permitted provided it is not more than 6 m long.
9.9.7.4. Number and Spacing of Egress Doors
1) Intent StatementExcept for dwelling units, at least 2 egress doors shall be provided when the area of a room or suite, or the distance measured from any point within the room or suite to the nearest egress door, exceeds the values in Table 9.9.7.4.
2) Intent StatementDoors required in Sentence (1) shall be spaced so that in the event that one door is made inaccessible by a fire within such room or suite, the other door will provide safe egress.
Table 9.9.7.4.
Maximum Areas and Travel Distances for Rooms, Suites and Mezzanines with a Single Means of Egress
Forming part of Sentences 9.9.7.4.(1) and 9.9.8.6.(2)

Occupancy of Room, Suite or Floor Area

Maximum Area of Room, Suite or Floor Area, m2

Maximum Distance to Egress Door, m
Group C (except dwelling units) 100 15
Group D 200 25
Group E 150 15
Group F, Division 2 150 10
Group F, Division 3 200 15
9.9.7.5. Independent Access to Exit
1) Intent StatementRequired access to exit from suites shall not be through any other dwelling unit, service room or other occupancy.
9.9.7.6. Travel Distance within Rooms and Suites
1) Intent StatementExcept for dwelling units, the travel distance from any point within the room or suite to the nearest egress door shall not exceed the maximum travel distance in Article 9.9.8.2.

9.9.8. Exits from Floor Areas

9.9.8.1. Measurement of Travel Distance
1) Intent StatementExcept as provided in Sentences (2) and (3), for the purposes of this Subsection, travel distance means the distance from any point in the floor area to an exit measured along the path of exit travel.
2) Intent StatementWhere a room or suite is separated from the remainder of the floor area by a fire separation having a fire-resistance rating of at least 45 min or, in a sprinklered building, by a fire separation which is not required to have a fire-resistance rating, the travel distance may be measured from an egress door of the room or suite to the nearest exit.
3) Intent StatementWhere a public corridor is not less than 9 m wide and conforms to Subclauses 3.4.2.5.(1) (d)(i) to (d)(iv), the travel distance may be determined in accordance with those Subclauses.
9.9.8.2. Number of Required Exits
1) Intent StatementExcept as provided in Sentence (2) and Subsection 9.9.9., at least 2 exits shall be provided from every floor area, spaced so that the travel distance to the nearest exit is not more than
b) 45 m for all occupancies where the floor area is sprinklered, and
c) 30 m for all other occupancies.
2) Intent StatementExcept as provided in Subsection 9.9.9., a single exit is permitted from each storey in buildings of 1 and 2 storeys in building height provided the floor area and travel distance requirements conform to those required in Article 9.9.7.4. and the total occupant load served by an exit facility does not exceed 60 persons.
9.9.8.3. Contribution of Each Exit
1) Intent StatementWhere more than one exit is required from a floor area, each exit shall be considered as contributing not more than half the required exit width.
9.9.8.4. Location of Exits
1) Intent StatementWhere more than one exit is required from a floor area, at least 2 exits shall be independent of each other and be placed remote from each other along the path of travel between them. (See Appendix A.)
9.9.8.5. Exiting through a Lobby
1) Intent StatementNot more than one exit from a floor area above or below the first storey is permitted to lead through a lobby.
2) Intent StatementThe lobby referred to in Sentence (1) shall be not more than 4.5 m above grade, and the path of travel through the lobby to the outdoors shall not exceed 15 m.
3) Intent StatementThe lobby referred to in Sentence (1) shall conform in all respects to the requirements for exits, except that rooms other than service rooms, storage rooms and rooms of residential or industrial occupancy are permitted to open directly onto such lobby.
4) Intent StatementWhere the lobby referred to in Sentence (1) and adjacent occupancies that are permitted to open into the lobby are sprinklered, the fire separation between such occupancies and the lobby need not have a fire-resistance rating. (See A-3.4.4.2.(2)(e) in Appendix A.)
5) Intent StatementPassenger elevators are permitted to open onto the lobby referred to in Sentence (1) provided the elevator doors are designed to remain closed except while loading and unloading passengers.
9.9.8.6. Mezzanine Means of Egress
1) Intent StatementExcept as permitted by Sentences (2) and (3), the space above a mezzanine shall be served by means of egress leading to exits accessible at the mezzanine level, on the same basis as floor areas.
2) Intent StatementThe means of egress from a mezzanine need not conform to Sentence (1), provided
a) the mezzanine is not required to terminate at a vertical fire separation, as permitted by Sentence 9.10.12.1.(2),
b) the occupant load of the mezzanine is not more than 60,
c) the area of the mezzanine does not exceed the area limits stated in Table 9.9.7.4., and
d) the distance limits stated in Table 9.9.7.4., measured along the path of travel, are not exceeded from any point on the mezzanine to
i) an egress door serving the space that the mezzanine overlooks if the space is served by a single egress door, or
ii) an egress stairway leading to an access to exit in the space below if that space is required to be served by 2 or more egress doorways in conformance with Sentence 9.9.7.4.(1).
3) Intent StatementOne of the means of egress from a mezzanine that is not required to terminate at a fire separation, as permitted by Sentence 9.10.12.1.(2), and that exceeds the limits of Sentence (2) is permitted to lead through the room in which the mezzanine is located, provided all other means of egress from that mezzanine lead to exits accessible at the mezzanine level.
4) Intent StatementExcept as provided in Sentence (2), the maximum travel distance from any point on a mezzanine to the nearest exit shall be not more than
b) 45 m in a floor area that is sprinklered throughout, provided it does not contain a high-hazard industrial occupancy, or
c) 30 m in any floor area not referred to in Clauses (a) or (b).

9.9.9. Egress from Dwelling Units

9.9.9.1. Travel Limit to Exits or Egress Doors
1) Intent StatementExcept as provided in Sentences (2) and (3), every dwelling unit containing more than 1 storey shall have exits or egress doors located so that it shall not be necessary to travel up or down more than 1 storey to reach a level served by
a) an egress door to a public corridor, enclosed exit stair or exterior passageway, or
b) an exit doorway not more than 1.5 m above adjacent ground level.
2) Intent StatementWhere a dwelling unit is not located above or below another suite, the travel limit from a floor level in the dwelling unit to an exit or egress door may exceed 1 storey where that floor level is served by an openable window
a) providing an unobstructed opening of not less than 1 m in height and 0.55 m in width, and
b) located so that the sill is not more than
i) 1 m above the floor, and
ii) 7 m above adjacent ground level.
3) Intent StatementThe travel limit from a floor level in a dwelling unit to an exit or egress door may exceed 1 storey where that floor level has direct access to a balcony.
9.9.9.2. Two Separate Exits
1) Except as provided in Sentence 9.9.7.3.(1) where an egress door from a dwelling unit opens onto a public corridor or exterior passageway it shall be possible from the location where the egress door opens onto the corridor or exterior passageway to go in opposite directions to 2 separate exits unless the dwelling unit has a second and separate means of egress.

contentHistory

9.9.9.3. Shared Egress Facilities
1) Intent StatementA dwelling unit shall be provided with a second and separate means of egress where an egress door from the dwelling unit opens onto
a) an exit stairway serving more than one suite,
b) a public corridor
i) serving more than one suite, and
ii) served by a single exit,
c) an exterior passageway
i) serving more than one suite,
ii) served by a single exit stairway change beginor ramp,change end and
iii) more than 1.5 m above adjacent ground level, or
d) a balcony
i) serving more than one suite,
ii) served by a single exit stairway change beginor ramp,change end and
iii) more than 1.5 m above adjacent ground level.

contentHistory

9.9.10. change beginEgress from Bedroomschange end

9.9.10.1. change beginEgress Windows or Doors for Bedroomschange end
1) Intent StatementExcept where the suite is sprinklered, each bedroom or combination bedroom shall have at least one outside window or exterior door openable from the inside without the use of keys, tools or special knowledge and without the removal of sashes or hardware. (See Article 9.5.1.2. and Appendix A.)
2) Intent StatementThe window referred to in Sentence (1) shall
a) provide an unobstructed opening of not less than 0.35 m2 in area with no dimension less than 380 mm, and
b) maintain the required opening during an emergency without the need for additional support.
(See Appendix A.)
3) Intent StatementWhere a window required in Sentence (1) opens into a window well, a clearance of not less than change begin760 mmchange end shall be provided in front of the window. change begin(See Appendix A.)change end
4) Intent StatementWhere the sash of a window referred to in Sentence (3) swings towards the window well, the operation of the sash shall not reduce the clearance in a manner that would restrict escape in an emergency.
5) Intent StatementWhere a protective enclosure is installed over the window well referred to in Sentence (3), the enclosure shall be openable from the inside without the use of keys, tools or special knowledge of the opening mechanism.

9.9.11. change beginSignschange end

9.9.11.1. Application
1) This Subsection applies to all exits except those serving not more than one dwelling unit.

contentHistory

9.9.11.2. Visibility of Exits
1) Intent StatementExits shall be located so as to be clearly visible or their locations shall be clearly indicated.
9.9.11.3. change beginExit Signs
1) Intent StatementEvery exit door shall have an exit sign placed over it or adjacent to it if the exit serves
a) a building that is 3 storeys in building height,
b) a building having an occupant load of more than 150, or
c) a room or floor area that has a fire escape as part of a required means of egress.
2) Intent StatementEvery exit sign shall
a) be visible on approach to the exit,
b) except as permitted in Sentence (3), consist of a green pictogram and a white or lightly tinted graphical symbol meeting the colour specifications referred to in ISO 3864-1, “Graphical symbols – Safety colours and safety signs – Part 1: Design principles for safety signs in workplaces and public areas,” and
c) conform to the dimensions indicated in ISO 7010, “Graphical symbols – Safety colours and safety signs – Safety signs used in workplaces and public areas,” for the following symbols (see A-3.4.5.1.(2)(c) in Appendix A):
i) E001 emergency exit left,
ii) E002 emergency exit right,
iii) E005 90-degree directional arrow, and
iv) E006 45-degree directional arrow.
3) Intent StatementInternally illuminated exit signs shall be continuously illuminated and
a) where illumination of the sign is powered by an electrical circuit, be constructed in conformance with CSA C22.2 No. 141, “Emergency Lighting Equipment,” or
b) where illumination of the sign is not powered by an electrical circuit, be constructed in conformance with CAN/ULC-S572, “Photoluminescent and Self-Luminous Signs and Path Marking Systems.”
4) Intent StatementExternally illuminated exit signs shall be continuously illuminated and be constructed in conformance with CAN/ULC-S572, “Photoluminescent and Self-Luminous Signs and Path Marking Systems.” (See A-3.4.5.1.(4) in Appendix A.)
5) Intent StatementThe circuitry serving lighting for externally and internally illuminated exit signs shall
a) serve no equipment other than emergency equipment, and
b) be connected to an emergency power supply as described in Sentences 9.9.12.3.(2), (3) and (7).
6) Intent StatementWhere no exit is visible from a public corridor, from a corridor used by the public, or from principal routes serving an open floor area having an occupant load of more than 150, an exit sign conforming to Clauses (2)(b) and (c) with an arrow or pointer indicating the direction of egress shall be provided.change end
9.9.11.4. Signs for Stairs and Ramps at Exit Level
1) Intent StatementIn buildings that are 3 storeys in building height, any part of an exit ramp or stairway that continues up or down past the lowest exit level shall be clearly marked to indicate that it does not lead to an exit, if the portion beyond the exit level may be mistaken as the direction of exit travel.
9.9.11.5. Floor Numbering
1) Intent StatementArabic numerals indicating the assigned floor number shall be
a) mounted permanently on the stair side of the wall at the latch side of doors to exit stair shafts,
b) not less than 60 mm high, raised approximately change begin0.8 mmchange end above the surface,
c) located 1 500 mm from the finished floor and not more than 300 mm from the door, and
d) contrasting in colour with the surface on which they are applied. (See A-3.4.6.19.(1)(d) in Appendix A.)

9.9.12. Lighting

9.9.12.1. Application
1) This Subsection applies to the lighting of all change beginmeans of egresschange end except those within dwelling units.

contentHistory

9.9.12.2. Required Lighting in Egress Facilities
1) Intent StatementEvery exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps.
2) Intent Statementchange beginThe minimum value of the illumination required by Sentence (1) shall be not less than 10 lx.change end
9.9.12.3. Emergency Lighting
1) Intent StatementEmergency lighting shall be provided in
a) exits,
b) principal routes providing access to exit in an open floor area,
c) corridors used by the public,
d) underground walkways, and
2) Intent StatementEmergency lighting required in Sentence (1) shall be provided from a source of energy separate from the electrical supply for the building.
3) Intent StatementLighting required in Sentence (1) shall be designed to be automatically actuated for a period of at least 30 min when the electric lighting in the affected area is interrupted.
4) Intent StatementIllumination from lighting required in Sentence (1) shall be provided to average levels of not less than 10 lx at floor or tread level.
5) Intent Statementchange beginThe minimum value of the illumination required by Sentence (4) shall be not less than 1 lx.change end
6) Intent StatementWhere incandescent lighting is provided, lighting equal to 1 W/m2 of floor area shall be considered to meet the requirement in Sentence (4).
7) Intent StatementWhere self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141, “Emergency Lighting Equipment.”